Irs 30-2005
Irs 30-2005
GOVERNMENT OF INDIA
MINISTRY OF RAILWAY
INDIAN RAILWAYS
STANDARD SPECIFICATION
FOR
UNDERGROUND RAILWAY JELLY FILLED TELECOM QUAD CABLES
FOR SIGNALLING & TELECOM INSTALLATIONS
0. FOREWORD
0.1 This specification is issued under fixed serial no. IRS:TC 30 followed by the year of original
adoption as standard or in the case of revision the year of last revision.
Adopted - 1983, First revision - 1995,
Second revision - 1996
Third revision - 1997
Fourth revision - 2005
0.2 This specification requires reference to the following Indian Railway Specification (IRS),
Indian Standard Specification (IS), British Standard Specifications (BS), American
Standard Specifications (ASTM) and Association of German Electrical Engineers
Specification (VDE).
0.3 Whenever in this specification, any of the above mentioned specifications are referred by
number only without mentioning the year of issue, the latest issue of that specification is
implied; otherwise the particular issue referred to is meant.
0.4 This specification is intended chiefly to cover the technical provisions and does not include
all the necessary provisions of a contract.
1. SCOPE:
1.1 This specification covers the requirements of the physical and electrical characteristics of
Polyethylene insulated, polythene inner sheathed, PVC intermediate sheathed, Aluminium
screened in the form of wire/strip/ welded Aluminium tubing, galvanised steel armoured in
the form of tape & PVC jacketed for telecom quad cables required for signalling & telecom
installations
1.2 The cables covered in this specification are suitable for use where the combination of
ambient temperature and temperature due to loads results in a conductor temperature not
exceeding 70ºC.
2. TERMINOLOGY
2.1 For the purpose of this specification terminology given in IRS:S 23, in addition to the
following, shall apply;
2.6 LOT:
The product of same type and category manufactured by the same factory during the same
period, using the same process and materials.
Page 3 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
3. GENERAL REQUIREMENTS:
3.1 CONDUCTOR:
3.1.1 The conductor shall be composed of plain annealed high conductivity copper wire(s)
complying with IS:8130 except for the requirements mentioned in this specification. The
dimensions and resistance of conductors shall be in accordance with the values given below :
3.1.2 The conductor shall be uniformly drawn, circular in cross-section, uniform in quality, free
from splits, cracks, corrosion and other surface imperfections.
3.1.3 No joints shall be made in the conductor except in very exceptional cases. When it is
necessary to join conductors during manufacture, it shall fulfill the requirements of clause
3.1. The joints shall be soldered, brazed or welded with smooth surfaces. The particulars of
such joints shall be mentioned by the manufacturer in the routine test certificate.
3.1.4 The tensile strength of a 250 mm length of conductor containing a joint shall not be less than
95% of that of a similar sample of conductor not containing a joint.
3.1.5 The resistance of 100 cm length of conductor containing joint/s shall not be more than
101.2% of that of an adjacent sample of conductor not containing joint/s.
3.2.1 Each conductor shall be insulated with solid polythene of one of the types specified below.
Recycled or reclaimed material shall not be used.
Test values for these parameters shall be as per standards specification ASTM: D-1248 or
BS: 6234. These values are applicable to the raw materials used and not for materials
removed from the cables.
3.2.2 The insulation shall be applied by extrusion in one continuous process and shall be
homogeneous and free from joints and repairs. It shall fit closely on the conductor but shall
not adhere to it so that it is possible to remove it without damage to the conductor.
Page 4 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Thickness of insulation shall not fall below nominal value t1 by more than 0.2 t1.
3.2.4 The colour scheme of Polyethylene insulated quads shall be as per Table given below:-
Note:- Wire A and wire B shall form a pair. Similarly wire C and wire D shall form a pair.
3.2.5 The colour scheme shall conform reasonably with the standard colour shown in IS:9938.
3.2.6 The insulation resistance of each insulated conductor shall not be less than 5000 M ohm/Km
at room temperature.
3.2.7 Unless otherwise specified by the purchaser there shall be six quads in the cable.
3.2.8 The insulated conductor shall be subjected to spark test at 3 KV AC (RMS) or 4.5 KV DC.
There shall not be more than one spark over per 5 Km length of the insulated conductor on
insulating line. The test shall be done at extrusion stage.
3.3 QUADDING:
3.3.1 Four conductors insulated as above shall be stranded to form a star quad each, two
conductors diagnonally opposite forming one pair and the remaining two diagonally opposite
conductors forming the second pairs of the quad. Polythylene centre strings of required
diameter may be used. The quad shall be held together firmly by means of an open helical
whipping of cotton/nylon yarn or colored tape of suitable material of appropriate thickness.
3.3.1.1 The lays of the conductors forming the quads shall differ for adjacent quads. The lay of the
conductor shall be so chosen as to ensure that the cross-talk between the pairs in the cable is
minimum.
Page 5 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
3.3.2 The colour scheme of the quad whipping shall be in accordance with the Table given below :
3.3.3 The colour of the quad whipping shall conform reasonably with the colour shown in IS:9938.
3.4.1 The quads shall be assembled to form a symmetrical core with a right lay. Polyethylene
strings of required diameter may be used as fillers, if necessary, for proper circular core
formation.
3.4.2 Each quad shall retain its position in the cable with reference to the other quads. The
manufacturing process shall be such that there is no physical displacement of the quads,
either during manufacture of the cable or during its subsequent handling.
3.5.2 CORE WRAPPING: After application of the filling compound a closed helical or
longitudinal lapping of a polyester tape shall be laid over the cable core. The tape may be
impregnated or flooded with jelly to meet the water penetration test requirements.
3.6.1 Polythene coated aluminium tape shall be applied longitudinally on the quad with a
minimum overlap of 6mm. The thickness of aluminium tape shall be 0.2mm ±10% and that
of polythene/copolymer coating on each side 0.05mm nominal. The thickness of composite
tape shall be 0.3mm ±15%.
3.6.2 The laminate shall be bonded to the inner surface of the polythene sheathing extruded over it
by any suitable method. The Poly-Al laminate shall be mechanically and electrically
continuous.
Page 6 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
3.6.3 PEEL STRENGTH: The peel strength of polythene from the Aluminium shall not be less
than 25 gm per mm width when tested as per Annexure-A (III). This test shall be applicable
on raw material Poly-Al tape only.
3.7.3 Cable shall be sheathed with the polythene grade 03C or H03C as per BS: 6234, and
containing a suitable anti-oxidant system. The material shall be virgin as per ASTM-D-883
and meet the requirements specified below:
i) Melt Flow Index- Shall not be more than 1.0 g/10 minutes (190ºC, 2160 gm load)
ii) Density- For 03C shall be 0.910 to 0.940 gm/cc.
For H03C, shall be 0.941 to 0.959 gm/cc.
iii) Anti-oxidant - OIT test in a copper pan at 199ºC as per the method in Annexure-A (v)
and the value to be recorded, the value should be such that the
requirement of Cl. 5.8.36 of this specification is met.
NOTE: The Melt Flow Index & Density test shall be applicable on raw material while
(OIT) shall be applicable on completed cable.
3.8 SCREENING:
3.8.1 The cores with inner sheath shall be surrounded by a reasonably close fitted screen of
Aluminium in the form of wires/strips/welded aluminium tubing.
3.8.2 The aluminium used for screening shall contain not less than 99.5% aluminium and shall
generally conform to IS:2067-75
3.8.3 The number and the size of the aluminium wires/strips used for screening shall be such as
to comply with the requirements of Cl. 5.9.9 If the Aluminium wires/strips used for
screening are laid in two layers, they shall be in opposite directions.
3.8.4 The layer of the aluminium wires/strips used for screening shall be compact and the length
of the lay shall be high. It shall also be ensured that the screening wires/strips are as close
as practicable so that inner sheath is not visible throughout the length of cable.
3.8.6 The innermost layer of the screening shall have left hand lay and the successive layer
shall be laid with opposite lay.
3.8.7 Drift expansion test to IS: 2335-1985 shall be carried out on a test piece of length, twice
the external dia of the tube by conical mandrel having height three times its base
diameter. The test piece shall show no crack or flaw until the outside diameter of the
expanded end is increased by at least 30%. This test is applicable where welded
aluminium tubing is used for screening.
3.8.8 Flattening test to IS: 2328-1983 shall be carried out on a test piece of not less than 50mm
long, cut from each selected tube. The test tube when close-flattened with the weld bead
position equidistant from the flattening places shall not show any visible crack or flaw in
the weld region. This test is applicable where welded aluminium tubing is used for
screening
3.9 PROTECTION:
3.9.1 The aluminium screen shall be wrapped with a single layer of woven tape impregnated
with Barium chromate with minimum 20% overlap.
3.9.2 The tape used shall be fine woven cloth tape of about 0.15mm thickness.
3.10.2 The nominal thickness (ts) of intermediate sheath shall be 1.0 mm.The smallest of
measured values shall not fall below the nominal value (ts) by more than (0.1mm+ 0.1ts).
The average thickness shall not fall below the nominal thickness ts.
3.10.3 The PVC used for intermediate sheath shall meet the requirements of ST-1 (General
purpose sheath for use at maximum rated conductor temperature 70ºC ) compound of
IS:5831-84, except for the requirements mentioned in this specification. Re-cycled or re-
claimed material shall not be used.
3.10.5 The PVC used for intermediate sheath shall meet the requirements as indicated in CL.5.8.
3.10.6 The Intermediate PVC sheath shall be subjected to spark test at 6 KV AC (RMS) or 9 KV
DC for all conductors sizes. There shall not be any spark over .
3.11 ARMOURING:
3.11.1 The galvanised steel tape armouring conforming to IS:3975 shall be applied tightly over
the intermediate sheath with two layers. The armour shall be free from rust, blooming,
oxidation, cracks, splits etc.
3.11.2 The sheathed cable shall be armoured with two applications of Galvanised steel tape
conforming to IS: 3975, each applied helically in the same direction with a gap in the first
tape of 25%±10% of the width of the tape, the second tape evenly covering the gap of
first tape. In any case, the overlap of second tape over the first tape shall not be less than
20% of the width of tape. The intermediate sheath shall not be visible throughout the
length of the cable.
3.11.3 The direction of the lay of the armour shall be opposite to that of the outermost layer of
screening.
3.11.4 When joints in tapes are necessary, they shall be made by brazing or welding and any
surface irregularity shall be removed. A joint in any tape shall not be less than 300 mm
from a joint in any other armour tape in the completed cable. The tape shall be
continuous throughout the length of cable.
3.12.2 The PVC used for outer sheath shall meet the requirements of ST-1 (General purpose
sheath for use maximum rated conductor temperature 70ºC ) compound of IS:5831-84,
except for the requirements mentioned in this specification. Re-cycled or re-claimed
material shall not be used.
3.12.4 The thickness of PVC outer sheath shall be determined in accordance with the procedure
laid down in IS:10810 (Part-6). The average thickness shall not be less than the nominal
value (ts) specified below and the smallest of the measured values shall not fall below the
nominal value by more than (0.2mm + 0.2 ts).
3.12.5 The PVC used for outer sheath shall meet the requirements as indicated in Cl. 5.8
Page 9 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
3.12.6 The outer sheath shall be subjected to spark test at 15 KV AC (RMS) or 23 KV DC.
There shall not be any spark over.
3.13 The cross-sectional view of 4 quad & 6 quad cable shall be as per Fig.1& 2 respectively.
4. MARKING:
4.1 The following information shall be legibly and indelibly indicated at every meter or less
throughout the length of the cable by embossing or engraving/indenting on outer sheath
of the cable. All the marking shall be in white or yellow colour. The marking shall be
clear, distinct and visible to the naked eye from a distance of about 1 meter; the size of
marking shall be of minimum 3 mm.
4.2 The following information shall be stenciled on the cable drum in black paint over yellow
painted background.
5.1 Unless otherwise specified, all tests shall be carried out under ambient atmospheric
conditions.
5.1.1 For inspection of material, relevant clause of IRS:S-23 shall also apply.
5.2 TYPE TESTS: The following shall constitute type tests and shall be carried out once
in three years or earlier at the discretion of the inspecting authority.
5.2.1 At least two drums shall be taken statistically from the lot. There shall be no failure.
Sampling plan for type tests is enclosed as Table-3 (Clause 5.2).
Page 11 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.3.2 For conductor diameter and resistance, thickness of insulation, and sheaths, zinc coating
of armour tape, fire resistance, high voltage, shrinkage, thermal stability, melt flow index,
visual inspection and electrical tests, there shall be no failure.
5.3.3 For annealing, %elongation and tensile strength test of insulation, sheaths and armour,
not more than one specimen of a sample shall fail. If more than one specimen of a
sample fails, the lot shall be rejected. If only one specimen has failed, two further
samples of the same drum shall be tested. There shall be no failure.
5.4.1 Electrical tests except high voltage test (Cl. 5.9.1) & IR (Cl. 5.9.2.2 & 5.9.2.3) to be done
on 100% basis. High voltage tests (Cl.5.9.1) & IR tests (Cl. 5.9.2.2 & 5.9.2.3) under
routine tests (Cl. 5.4) shall be done at least on 20% of the offered lot for inspection.
5.4.2 The results of routine test shall be made available to the inspecting authority along with
the inspection call letter.
Page 12 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.5.1 DIMENSIONS:
The diameter of the conductor (s) shall be measured on a sample from the finished cable.
The measurement shall be made at least at three different points (at intervals of not less
than 100mm ) with two readings at 90º along the length of the sample. The values shall
meet the requirements given in Clause 3.1.1.
5.6.1 DIMENSIONS:
The dimensions of armour tapes shall be measured in accordance with the procedure laid
down in IS:10810 (Part-36). The measured values shall meet the requirements of Cl.
3.11.5 of this specification.
5.6.2.1 Steel tapes removed from the completed cable shall be tested as per IS: 10810 (Part- 37)
and shall have the following values:-
5.6.2.2 Steel tapes taken from raw material lot shall be tested as per IS: 10810 (Part-37) and shall
have the following values: -
NOTE: In either case the load shall be increased gradually at a uniform rate and the rate of
straining shall not be greater than 75mm/minute.
5.6.3.1.1 This test shall be carried out in accordance with the procedure laid down in IS:10810 (Part-
41). The weight of zinc coating shall be 210 g/sq.meter on each side.
Page 13 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.6.3.2.1 This test shall be carried out in accordance with the procedure laid down in IS: 10810
(Part-40). The sample shall not show any red deposit of copper upon the base metal with
two dips of one minute each in copper sulphate solution prepared as per IS: 2633.
5.7.2 The measurement in case of conductor insulation, inner, intermediate and outer sheath shall
be made at three different points at intervals of not less than 75mm along the length of the
sample and at each point the minimum thickness of the insulation, inner, intermediate &
outer sheath shall be measured along with two more readings made at equidistant points
around the periphery. The minimum thickness at any point and the average thickness at the
three points selected shall comply with the requirements given in clauses 3.2.3, 3.7.1,
3.10.2 & 3.12.4.
5.8.1.1 This test shall be conducted in accordance with the procedure laid down in IS:10810 (Part-
7). The speed of separation of jaws of tensile testing machine shall be between 400 mm to
500 mm/minute. The material shall fulfill the requirements indicated below;
SHEATHS INSULATION
a). BEFORE AGEING PE PVC
i) Tensile strength min, kg/cm2. 70 150 100
ii) Elongation min. % 300 200 300
b). AFTER AGEING
(In air oven at 80± 2º C for 168 hours )
i). Tensile strength min, kg/cm2. -- 150 -
ii). Elongation min. % -- 200 -
Page 14 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.8.1.2 The maximum variation after ageing shall be ± 20% of the values obtained before ageing.
For test before and after ageing, samples shall be from the same drum. However, values
after ageing for tensile strength and % elongation shall not be less than given in clause
5.8.1.
5.8.1.3 The values of all the four samples in case of each sheath shall be averaged and then %
variation calculated.
5.8.1.4 For acceptance test, the sample shall be kept in air oven at 130º C ±2ºC for 5 hours.
5.8.1.5 Tensile Strength & Elongation at Break for Polythene Sheath and Insulation shall be carried
out before ageing only and value shall comply as per the Table given in sub clause 5.8.1.1
5.8.2.1 This test shall be conducted in accordance with IS: 10810 (Part -12). During test no cracks
shall occur.
5.8.2.2 For PVC Intermediate and Outer Sheath shrinkage shall not exceed 2% of original length
and temperature shall be 150±2ºC for 15 minutes.
5.8.2.3 For PE Insulation, temperature shall be 100±2ºC for a period of 24 hours and average
shrinkage of 4 samples of length 150mm of each colour of insulation shall not exceed
6.35mm.
5.8.4.2 For acceptance test the sample shall be kept in air oven at 130ºC ±2ºC for 5 hours.
The loss of mass shall be within the limits as indicted above.
Page 15 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.8.11.2 The time taken for the universal indicating paper to change colour from a pH value of 5 to
a pH value of 3 shall be 40 minutes in case of sheaths. However, this test is not applicable
in case of insulation.
5.8.12 For tests from clause 5.8.3 to clause 5.8.11, at least of two samples shall be taken from each
type of material in each colour used. There shall be no failure.
Page 16 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.8.16.2 The length of sample shall be sufficient to give at least one complete turn around the test
drum. The bending shall be carried out at reasonably uniform speed between 15 and 30
seconds per half cycle.
5.8.16.3 The cable shall, on close examination, reveal that the cable serving is free from splits, the
armour not noticeable displaced and the sheaths free from splits and cracks.
5.8.18.1 Retraction of insulation on insulated conductor when cut at a point not less than one meter
from one end at room temperature shall not exceed 2.5 mm after one minute.
The Carbon Black Dispersion in inner PE sheath shall conform to BS: 6234 and shall not
be more than rating four.
5.8.37 BOND STRENGTH: (Applicable on Poly-Al bonded inner PE sheath from completed
cable)
The bond strength of the Poly-Al Laminate to the Polythene Sheath and at the overlap shall
meet the requirements indicated in Annexure-A (III) of the specification.
5.9.1.2 The insulation shall be capable of withstanding for ten seconds without intermittent or
permanent breakdown, when the above voltage is applied between a conductor and all
other conductors bunched together.
5.9.1.3 All the conductors shall be bunched together and 2 KV rms applied between them and the
steel armouring connected with screening wires for ten seconds. There shall be no
intermittent or permanent breakdown of the dielectric.
5.9.2.1 This test shall be carried out on drums which have been subjected to the high voltage test.
5.9.2.2 Insulation resistance test may be conducted on factory length between each conductor and
all other conductors in accordance and shorted with the armouring in air at the prevailing
temperature. The drum shall be in the test room at a reasonably constant temperature for
sufficient time to ensure that the core insulation is at ambient temperature. The DC test
voltage shall be 500 volts and shall be applied for one minute. The value of insulation
resistance shall not be less than 5000 mega ohms/Km at room temperature irrespective of
the size of the conductor.
5.9.2.4 VOLUME RESISTIVITY: (Applicable on PE insulation moulded sheet made from the
raw material PE granules.)
The volume resistivity at room temperature shall be conducted on Polythelene Insulation in
accordance with the procedure laid down in ASTM: D 257. The volume resistivity shall not
be less than 1x1015 Ohm-cm.
Page 20 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.9.3.2 The DC resistance of the conductor shall be measured at room temperature. It shall be
corrected to 20º C by means of the appropriate factors given in Table-1.
5.9.3.3 The corrected resistance shall not exceed the value given in Cl. 3.1.1.
5.9.3.4 The maximum loop resistance of any pair in a finished cable shall not exceed the average
value by more than 2%.
5.9.3.5 The maximum specific resistance of the conductor shall be 17.241 ohm cm.
5.9.4.1 The mutual capacitance of the pairs shall have nominal value of 0.05 microfarad per Km.
In any length the average value of mutual capacitance of all the pairs shall not differ by
more than ± 5% from nominal value. The mutual capacitance of any pair shall not differ
by more than ± 12% from the nominal value.
5.9.5.1 The capacitance unbalance measurements between pairs in the same quad and between
pairs in the adjacent quads shall be made for all the pairs at 800 Hz to 1000 Hz at ambient
temperature on each length of cable. All conductors other than those under test shall be
connected to the screen and earthed.
5.9.5.2 The capacitance unbalance/km shall not exceed the value given below:
Length shorter than 500 meters shall satisfy the same condition as length of 500 meters.
5.9.6.1 The characteristic impedance of any pair shall be in accordance with the table below :
The RMS and individual value shall be better than 67.8 dB/km and 55.0 dB/km
respectively.
The RMS dB is given by
5.9.7.2.1.1 For lengths other than 1 Km, the measured value shall be corrected by 10
log10L/1000, L being the cable length, tested in meters
5.9.7.3.1 The near end cross talk between adjacent pairs shall be better than 55 dB.
5.9.8.2 The value of attenuation shall not exceed 2 dB/km for any frequency in the frequency
range 300 Hz – 3400 Hz at 20°C.
5.9.9.2 The screening of the cable shall be suitable so as to give a reduction factor in the field
intensity of 50 volts to 450 volts per km as specified below :
6. PACKING:
6.1 The cable shall be wound on strong wooden drums of suitable size treated with ASCU
fungicide. The timber used for the manufacture of drums shall be seasoned, reasonably
straight grained, uniform in thickness, free from insect attack, splits, warping and other
defects which may reduce the overall strength of the drums.
6.2 The drums shall be of general construction as shown in Fig.3. The dimensions D, X, X1 and
Y shall be suitable for the size of the cable and the ratio of X1 to Y shall not be greater than
0.65. Dimensions D shall not be less than 20 times the overall diameter of the cable. The
size of drum must be such that the cable when packed the outer most layer of cable is 50
mm below the flange tip.
6.3 Nails used in the manufacture of the drums shall be of the clout headed type to IS:723.
They shall be properly clenched and shall be so driven as to avoid splitting of the wood.
The end shall not protrude into the surface where the cable has to be wound.
6.4 The thickness of batons fitted on the circumference of the cable drum shall not be less than
25 mm and the gap between the batons shall not be more than 5 mm to cater for
unevenness in the wooden surface.
6.5 Flange made of wooden planks shall not be less than 25 mm thick. Wooden planks shall be
closely fitted and gap in between planks shall not be more than 5 mm to cater for
unevenness in the wooden surface.
6.6 Steel boss shall be fitted with its diagonal at right angles to wooden planks of flange and
shall not be fitted over not less than 2 wooden planks of flange.
Unless otherwise specified, the cable shall be supplied either in length of 500 meters or
1000 meters. The tolerance shall be +5%, -2% irrespective of the length of cable. Non-
standard length, each not less than 200 meters shall be acceptable up to 2% of the total
quantity ordered. Unless otherwise specified by the purchaser the tolerance on total
quantity shall be ± 2%.
6.11 Before dispatch the drums shall be effectively lagged with suitable closely fitted batons of
thickness 25 mm minimum. Every baton shall be secured to prevent it from getting
displaced or damaged during transit and storage. The lagging shall further be strengthened
by steel straps bound circumferentially over the drum. The steel strapping of not less than
12 mm wide and 0.6mm thick shall be used.
Page 23 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
6.12 The flange portion of drum shall be made of two batons. The thickness of each baton shall be
25 mm for flange dia. upto 1070 mm. If the flange dia. exceeds 1070 mm, the baton
thickness shall be 37.5 mm.
6.13 The batons on the drums to be removed for obtaining access to the cable end shall be painted
red.
6.14 Both the ends of the cable shall be firmly secured and brought to the outer layer of the drum
with suitable protective arrangement to prevent damage during testing and transit. In the
inside portion of one side flange, suitable arrangement to guide lower end of the cable upto
the top must be provided. The initial and final sequential length marking shall be properly
visible at the outer layer. The batons coming above the top and bottom SLM shall be marked
with red paint.
7. SAMPLING:
7.1 All cable drums having cable of same conductor diameter, number of cores and similar
construction shall constitute a lot.
7.2 For taking samples, drums shall be chosen at random from the lot. From each of these drums,
one sample of cable shall be taken. The length of the sample shall be sufficient so as to
provide test pieces of required length as laid down in various test clauses.
7.3 The number of drums to be random selected for taking samples shall be as per column 3 of
table 2. The number of drums has been expressed as a percentage of the total number of
drums in the lot.
7.4 The number of the test pieces to be taken from each sample shall be as per column 4 of Table
2.
7.5 The lot shall be offered to the inspecting authority within two months of the month of
manufacture.
In case any of the above information is not provided by the purchaser, default value
shall be assumed.
Page 24 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
TABLE-1
Temp. Correction Temp. Corre. Temp Corre. Temp. Corre. Temp. Corre.
Deg C factor deg C Factor deg C factor deg C factor deg C Factor
1. 2. 1. 2. 1. 2. 1. 2. 1. 2
5. 1.0638 17 1.0122 29 0.9653 41 0.9225 53 0.8834
5.5 1.0618 17.5 1.0101 29.5 0.9634 41.5 0.9208 53.5 0.8818
6. 1.0593 18 1.0081 30 0.9615 42 0.9191 54 0.8803
6.5 1.0571 18.5 1.0060 30.5 0.9597 42.5 0.9174 54.5 0.8787
7. 1.0549 19. 1.0040 31. 0.9579 43. 0.9158 55. 0.8772
7.5 1.0526 19.5 1.0020 31.5 0.9560 43.5 0.9141 55.5 0.8757
8. 1.0504 20. 1.0000 32. 0.9542 44.. 0.9124 56. 0.8741
8.5 1.0482 20.5 0.9980 32.5 0.9524 44.5 0.9107 56.5 0.8726
9. 1.0460 21. 0.9960 33. 0.9506 45. 0.9091 57. 0.8711
9.5 1.0438 21.5 0.9940 33.5 0.9488 45.5 0.9074 57.5 0.8696
10. 1.0417 22. 0.9920 34. 0.9470 46. 0.9058 58. 0.8681
10.5 1.0395 22.5 0.9900 34.5 0.9452 46.5 0.9048 58.5 0.8667
11. 1.0373 23. 0.9881 35. 0.9434 47. 0.9025 59. 0.8651
11.5 1.0352 23.5 0.9862 35.5 0.9416 47.5 0.9009 59.5 0.8636
12. 1.0331 24. 0.9843 36. 0.9398 48. 0.8993 60. 0.8621
12.5 1.0309 24.5 0.9823 36.5 0.9380 48.5 0.8977 60.5 0.8606
13. 1.0288 25. 0.9804 37. 0.9363 49. 0.8961 61. 0.8591
13.5 1.0267 25.5 0.9785 37.5 0.9346 49.5 0.8945 61.5 0.8576
14. 1.0246 26. 0.9766 38. 0.9328 50. 0.8929 62. 0.8562
14.5 1.0223 26.5 0.9747 38.5 0.9311 50.5 0.8913 62.5 0.8547
15. 1.0204 27. 0.9728 39. 0.9294 51. 0.8897 63. 0.8532
15.5 1.0183 27.5 0.9709 39.5 0.9276 51.5 0.8881 63.5 0.8518
16. 1.0163 28. 0.9690 40. 0.9259 52. 0.8863 64. 0.8503
16.5 1.0142 28.5 0.9671 40.5 0.9242 52.5 0.8850 64.5 0.8489
Page 25 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Table-2: SAMPLING PLAN FOR ACCEPTANCE TEST (Clause 7) No. IRS: TC 30-05
18. Density/specific gravity of 4% subject to min. of one Min. one sample from each
PVC Sheaths (Cl. 3.10.7) drum from each lot. sampled drum.
19. T.S. & % Elongation of PE 4 % subject to min. of one Min. two samples from
sheath before ageing only drum from each lot. each sampled drum.
(Cl. 5.8.1.5)
20. Shrinkage test of PE sheath 4% subject to min. of one Min. one sample from each
(Cl. 5.8.2.4) drum from each lot. sampled drum.
21. Number of size, 10% subject to min. of 1 All sampled drums.
compactness & lay drum from each lot.
direction of aluminium
wires (Cl. 3.8.3, 3.8.4 &
3.8.6)
22. Tensile strength of 10 % subject to min. of 1 Minimum 5 wires or 2
aluminium wires/ strips/ drum from each lot. strips/tubing from each
welded aluminium tubing sampled drum.
(Cl. 3.8.5)
23. Drift Expansion test of 5% subject to min. of 1 drum Min. 2 samples from each
welded aluminium tubing from each lot. sampled drum.
(Cl. 3.8.7)
24. Flattening test of welded -do- -do-
aluminium tubing (Cl.
3.8.8)
25. Dimensions & Overlap of 10 % subject to min. of 1 All sampled drums.
Barium Chromate Tape drum from each lot.
(Cl. 3.9)
26. Flame Retardant Test (Cl. 4% subject to min. of one Min. one sample from each
5.8.13) drum from each lot. sampled drum.
27. Visual Inspection test (Cl. 5% subject to min.2 drums All sampled drums.
5.8.22, 3.3 & 3.11) from each lot.
28. Conductor resistance & 20% subject to minimum 2 All insulated conductors &
loop resistance tests (Cl. drum from each lot. pairs of all quads of
5.9.3) except 5.9.3.5 sampled drums.
29. High voltage tests (Cl. -do- All insulated conductors
5.9.1)
30. Mutual capacitance test -do- -do-
(Cl. 5.9.4)
31. Capacitance unbalance test -do- -do-
(Cl. 5.9.5)
32. Characteristic impedance -do- -do-
test (Cl. 5.9.6)
33. Cross-talk test (Cl. 5.9.7) -do- -do-
34. Attenuation test (Cl.5.9.8) -do- -do-
35. Insulation resistance test -do- -do-
(Dry) (Cl.5.9.2.1 &
5.9.2.2)
Page 27 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
36. Reduction factor test (Cl. 5% subject to minimum of 2 2 conductors from one
5.9.9) drums from each lot. drum. The conductors may
be selected randomly
without repeating the same
colour code or conductor
from drums in the lot.
37. Water Penetration Test (Cl. 20% subject to minimum of All sampled drums.
5.8.23) 5 drums from each lot.
38. Insulation Resistance Test 4% subject to minimum of 1 Minimum one conductor
(Wet) (Clause No. 5.9.2.3) drum from each lot. selected from each colour
of insulated conductor of
sampled drum.
39. Carbon Black Content of Minimum of 1 drum from All sampled drums.
PE inner sheath (Cl. each lot.
5.8.25)
40. Carbon Black Dispersion Minimum of 1 drum from All sampled drums.
of PE inner sheath (Cl. each lot.
5.8.26)
41. Drip test (Cl. 5.8.33) Minimum of 1 drum from Minimum one sample each
each lot. from inner and outer end of
the sampled cable drum.
42. Water Penetration Test (Cl. Minimum of 1 drum from One sample from the
5.8.23) (from middle each lot. ( One meter sample sampled drum from the
portion of the drum) to be taken from exactly lot.
middle portion of the
sampled cable drum).
43. Conductor diameter Minimum of 1 drum from All insulated conductors.
(Cl.5.5.1) each lot. ( Sample taken for
W.P.T test at S.No. 42 shall
be tested ).
44. Overlap & continuity of Minimum of 1 drum from Minimum one sample from
Poly-Al Tape (Cl. 3.6.1 & each lot. (Sample taken for each sampled drum.
3.6.2) W.P.T test at S.No. 42 shall
be tested).
45. Specific resistance tests 4% subject to minimum of One sample of each colour
(Cl. 5.9.3.5) one drum from each lot. of insulation from sampled
drums.
46. Specific Density of jelly ( Minimum of one drum from Minimum one sample from
Cl. 5.8.32) each lot. each sampled drum.
NOTE:- The shortage in cable drum length on account of tests at S.No. 42 to 44 above shall be
accepted as good length in the lot in addition to short length permissible in the specification.
Page 28 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
5.8.1.1 a (i) i) Tensile Strength 4 samples each from both the drums of
6 and 4 Quad cables.
5.8.1.1a (ii) ii) Elongation at Break -do-
5.8.35 iii) Environmental Stress 2 samples each from sheath from both
Cracking (ESCR) the drums of 6 and 4 Quad cables.
5.8.25 v) Carbon Black Content 1 Sample each from sheath from both
the drums of 6 Quad & 4 Quad cables.
(Annexure-A test
(V))
3.11.2 Gap in the application of Both the drums of 6 and 4 Quad cables.
the first tape
3.11.2 Overlap of 2nd tape over -do-
the first one on either side
3.11.5 Thickness 2 Samples each from inner and outer
steel tape from both the drums of 6 and
4 quad cable
5.6.2.1 Tensile strength -do-
3.10.7 Density of PVC Inter & 2 Samples from each sheath from both
Outer Sheaths the drums of 6 & 4 Quad cables.
3.10.2 & 3.12.4 Thickness of PVC Inter & 4 Samples each from PVC intermediate
Outer Sheaths. and outer sheath from both the drums
of 6 and 4 Quad cables
5.8.2.1& Shrinkage test for PVC 1 Sample each from PVC intermediate
5.8.2.2 Intermediate and Outer & outer sheath from both the drums of
Sheaths 6 Quad & 4 Quad.
5.8.2.1 & Shrinkage test for PE 4 Samples each from each colour of
5.8.2.3 Insulation insulation from both the drums of 6
Quad & 4 Quad cables.
5.8.2.1 & Shrinkage test for PE Inner 2 Samples each from both the drums
5.8.2.4 Sheath
5.8.4 Loss of Mass (before and 4 Samples each from PVC intermediate
after ageing) and outer sheath from both the drums
of 6 and 4 Quad cables
ANEXURE-I
The cable core shall be fully filled with a suitable water resistant compound like Jelly, which
is fully compatible with the Polythene insulation of the conductors.
The compatibility between the polythene insulation and the filling compound shall be
established by the tests as per annexure below.
The compatibility shall be assessed for each colour of insulation as given in Table in clause
no. 3.2.4. This test shall be conducted from the insulated bobbins of each colour of insulation
at insulated conductor stage.
(iii) The second set of 10 samples shall be aged in a test tube or beaker full of filling compound
and maintained at 70º C±1ºC for 14 days. After ageing as above, the 10 lengths shall be
tested in a tensile testing machine for tensile properties in a similar manner as above.
The average percentage elongation at break and tensile strength after ageing shall not change
by more than 30% and 15% respectively of the values before ageing.
air oven maintained at 70º C±1ºC for 14 days. At the end of this period they will be removed
from the oven and observed for cracks with naked eye. There shall be no cracks.
ANNEXURE-A
The compound shall remain intact in the container after 120 hours and shall not show
any separation of the constituents of the compound.
(III) PEEL STRENGTH FOR LAMINATE AND COMPOSITE SHEATH & BOND
STRENGTH:
1.0(a) A parallel sided test piece 150mm long and 13 to 16mm wide of the laminate or sheath shall
be cut longitudinal from the Laminate or sheath in one operation using a sheath.
(b) Test piece taken for testing the strength of the bond between the sheath and Aluminium tape
shall exclude the overlap of Aluminium foil. For small diameter cables, it may not be
possible to get sheath test pieces 13 cms wide. In such cases test pieces of less width may be
taken (excluded the Poly-Al Overlap).
(c) Test pieces taken for testing the strength of the bond between the interfaces of the
Aluminium tape at the seal shall include only the overlap of the tape.
2.0 (a) For testing Peel Strength of Laminate only, separate the Aluminium and Polythene tape at
one end. Insert the Aluminium in the fixed grip and Polythene tape in the moving grip of the
tensile tester.
(b) For testing bond strength of sheath, insert the Aluminium in the fixed grip and polythene
sheath in the moving grip.
Page 38 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
(c) For testing Bond Strength of Laminate at the overlap, insert the Aluminium tape in the fixed
grip and Poly-Al – Polythene sheath (other edge) in the other grip. For 4.0 a, b & c of this
item, the grip can be brought closer up to 3 cms. An electric operated tensile tester shall be
used. Rate of separation between grips shall be 100 to 135 mm/min. and the steady force
required to separate the materials shall be noted.
3.0 Initial separation of the Laminate or laminated sheath to facilitate insertion in the grips can
be made by immersing about 25mm at the end of the test piece in boiling industrial alcohol
for about 30 seconds.
(a) Peel Strength of the Laminate raw material shall be 25-gms/mm width (minimum). 5
samples shall be tested.
(b) Bond Strength of the Laminate to Sheath shall be 40gms/mm (Minimum) and
60gms/mm width (Average) on 5 samples.
(c) Peel Strength of the Laminate at overlap shall be the same as (b) above on 5 samples.
Testing Arrangement: This arrangement is shown in fig.5. The sample under test is kept
straight in a horizontal plane on a test bench prepared for this purpose. One end of the sample
shall be connected suitably through a watertight gland to a water pipe containing 1 metre
head of water. The connection shall be such that the cable sheath shall not be squeezed tight
or shall in allow leakage of water at this point. The other end of the cable shall be free.
One metre head of water shall be applied for 7/14 days at ambient temperature. The
pipe connecting the water tank to the cable shall be vertical. No air bubbles shall remain
trapped in this pipe. Any bubbles that may be present initially should be removed by
agitating the water column using a thin wire for this purpose.
The test shall be deemed to have started after ensuring that the head of water is one
metre and all air bubbles have been eliminated. The sample shall not be disturbed during the
period under test. During this period, no water shall have seeped from the cable sample. This
test shall be conducted after inner sheath stage.
equilibration, five samples shall be taken of each colour of insulation, each one from a
different conductor. Each sample shall be wiped clean of grease and foreign objects using a
dry cloth (without solvents). Each sample shall be individually tested by means of a
Differential Scanning Calorimeter (DSC) or by Differential Thermal Analysis (DTA). The
sample shall be clean and dry.
Temperature Calibration:
The temperature scale should be adjusted according to the instrument manual until the
determined melting point of pure indium metal is 156.6ºC at a heat rate of 5º C per minute.
Engineering Notes:
Sample preparation:
Remove the insulation from the conductor. Flatten the resin to bout 15 mils thickness ( not
critical), clip sample to approximate roundness, bout 2mm in diameter.
Sample should weigh approximately 1 to 2 mg. Position in center of oxidized copper
pan, cover with clean 316 stainless steel screen (40 mesh) and crimp the pan.
Nitrogen Purge:
Place sample pan in instrument cell. Flush 5 minutes with cylinder nitrogen at 60±10 cc per
minute.
Oxidation Test: Rapidly increase sample temperature (20ºC±1ºC. After thermal equilibrium
(steady recorder signal) simultaneously switch to 50±5cc/minute oxygen flow and start time-
base recording. Other flow rates, 150cc/minute inclusive maximum, can be used. Record rate
flow used. Oxygen should be equivalent to or better than 99.66 extra dry grade.
Page 40 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Induction Period: This oxygen induction point shall be recorded as time zero, and the chart
speed shall be sufficient to provide a clearly discernible slope at the start of the exothermic
shall continue until the exothermic peak is produced. The intersection of the tangent of the
exothermic sloped line with the extended base line will be drawn. The time from time zero to
this intersection point is read from the base line and recorded as oxidation induction time.
Page 41 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Page 42 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Page 43 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Page 44 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
Page 45 of 44 Effective from 01-01-2006 DOC No. IRS:TC 30-05 Ver. 1
STT/Tele/RE/4quad/379 Date: 22.08.2006
Based on 33rd TCSC recommendation & approval of Rly. Board, Amendment No. 1 for the above
specification is hereby issued for its implementation with effect from 1st September 2006.
Cl. No. 5.9.7.2 and its sub-clauses No.5.9.7.2.1 & 5.9.7.2.1.1 shall be replaced by
following:-
2. For lengths other than 1 Km, the measured value shall be corrected by
10 log10L/1000, L being the cable length, tested in meters
Typographical error in value of specific resistance in clause no. 5.9.3.5 has been
corrected and enclosed as Amendment No. 2 .
The speed of separation of jaws of tensile testing machine in clause no. 5.8.1.1,
sample size of thermal stability test of PVC sheath & cable bend test in table-2 has
been corrected and enclosed as Amendment No. 3. This shall come in force with
immediate effect.
The following corrections are made in specification no. IRS:TC 30-05 Ver.1
Clause 5.8.1.1 :- The speed of separation of jaws of tensile testing machine shall be between
250mm ± 50 mm/minute instead of 400mm to 500 mm/minute.
Table–2 (SN 16) Thermal stability test of PVC sheath (Cl. 5.8.11)
Sample size (Nos. of drums) shall be read as: Minimum one drum from each
lot.
Page 1 of 5
Necessary amendment regarding Weight of 6 quad cable alongwith its
constituents as recommended by 35th TCSC and approved by Railway Board shall
be issued in due course after proper study.
Page 2 of 5
AMENDMENT No.4
of
SPECIFICATION No. IRS:TC 30-05 VER.1
for
UNDERGROUND RAILWAY JELLY FILLED TELECOM QUAD CABLES
for
SIGNALLING & TELECOM INSTALLATIONS
Page 3 of 5
shall be carried out and if successful, shall be approved.
The list of raw materials/component and corresponding
partial tests are given below:-
Page 4 of 5
ps/welded
aluminium
tubing for
screening
8. Poly-Al 3.6.1, 3.6.1, 3.6.2, - -
tape 3.6.3 5.8.37 (Annexure A-III)
laminate
9. Barium 3.9.2 3.9.1, 3.9.2 - -
Chromate
tape
Page 5 of 5