Data Download HAT700 en

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 51

HAT700 SERIES

HAT700/HAT700I/HAT700B/HAT700BI/HAT700S

ATS CONTROLLER

USER MANUAL

SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.


HAT700 SERIES ATS CONTROLLER USER MANUAL

Chinese trademark

English trademark

SmartGen — make your generator smart


SmartGen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou
Henan Province
P. R. China
Tel: 0086-371-67988888/67981888
0086-371-67991553/67992951
0086-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: [email protected]
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should
be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.

SmartGen Technology reserves the right to change the contents of this document without prior notice.

Software Version
Version Date Note
1.0 2014-09-09 Original release.
1.1 2015-03-04 HAT700s is added.
1.2 2015-04-30 Renew character strings.
1.3 2015-11-16 Change the name of VITZRO wiring diagram as VITZRO/PHETENG.
1.4 2016-11-07 S1,S2 Start type add “Not Used” option.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 2 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

CONTENT
1 OVERVIEW ......................................................................................................................................... 5
2 ORDER INFORMATION AND MODULES COMPARISON ............................................................... 5
2.1 ORDER INFORMATION .............................................................................................................. 5
2.2 MODULES COMPARISON .......................................................................................................... 5
3 PERFORMANCE AND CHARACTERISTICS .................................................................................... 6
4 SPECIFICATION................................................................................................................................. 7
5 MEASURE AND DISPLAY DATA ....................................................................................................... 8
6 OPERATION ....................................................................................................................................... 9
6.1 INDICATORS ............................................................................................................................... 9
6.2 KEY FUNCTION DESCRIPTION............................................................................................... 10
7 LCD DISPLAY ................................................................................................................................... 11
7.1 MAIN SCREEN ...........................................................................................................................11
7.2 STATUS DESCRIPTION ............................................................................................................ 13
7.2.1. S1 VOLTAGE STATUS ........................................................................................................... 13
7.2.2. S2 VOLTAGE STATUS ........................................................................................................... 13
7.2.3. GENSET STATUS................................................................................................................... 13
7.2.4. SWITCH STATUS ................................................................................................................... 14
7.2.5. WARN ALARMS...................................................................................................................... 14
7.2.6. FAULT ALARMS...................................................................................................................... 15
7.2.7. INDICATION............................................................................................................................ 15
7.2.8. OTHERS ................................................................................................................................. 16
7.3 MAIN MENU............................................................................................................................... 16
8 START/STOP OPERATION ............................................................................................................. 17
8.1 MANUAL START/STOP ............................................................................................................. 17
8.1.1. PANEL START/STOP ............................................................................................................. 17
8.1.2. REMOTE START/STOP ......................................................................................................... 17
8.2 AUTO START/STOP .................................................................................................................. 17
8.2.1 INPUT PORT START/STOP OPERATION .............................................................................. 17
8.2.2. “S1 GENS S2 GENS” START/STOP ...................................................................................... 18
8.2.3. SCHEDULED RUN ................................................................................................................. 19
8.2.4. SCHEDULED NOT RUN ........................................................................................................ 19
9 PARAMETERS CONFIGURATION .................................................................................................. 20
9.1 ILLUSTRATION ......................................................................................................................... 20
9.2 PARAMETERS TABLE .............................................................................................................. 20
9.3 INPUT/OUTPUT FUNCTION DESCRIPTION ........................................................................... 28
9.3.1 INPUT PORTS FUNCTION ................................................................................................ 28
9.3.2 OUTPUT PORTS FUNCTION ............................................................................................ 29
9.3.3 CUSTOM PERIOD OUTPUT ............................................................................................. 32
9.4 DEFINITE TIME DELAY AND INVERSE DEFINITE MINIMUM TIME SETTING ....................... 33
10 EVENT LOG .................................................................................................................................. 34
11 ATS OPERATION ......................................................................................................................... 36
11.1 MANUAL OPERATION .............................................................................................................. 36
11.2 AUTOMATIC OPERATION ........................................................................................................ 36
11.3 SYNC CLOSING ........................................................................................................................ 36

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 3 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
12 ATS POWER SUPPLY.................................................................................................................. 39
13 LOAD SHEDDING ......................................................................................................................... 40
14 COMMUNICATION CONFIGURATION ........................................................................................ 41
15 DESCRIPTION OF CONNECTING TERMINALS ........................................................................ 41
16 TYPICAL WIRING DIAGRAM ....................................................................................................... 43
17 INSTALLATION ............................................................................................................................. 51
18 FAULT FINDING ........................................................................................................................... 51

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 4 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
1 OVERVIEW
HAT700 series ATS controller is intelligent dual-supply module with configurable function, automatic
measurement, LCD display, and digital communication. It combines digital, intelligence and networking.
Automatic measurement and control can reduce incorrect operation. It is an ideal option for ATS.
The powerful Microprocessor contained within the unit allows for precision voltage (2-way-3-phase)
measuring and make accurate judgment; in addition, the corresponding digital output port will active
when there is over/under voltage, over/under frequency, loss of phase and other abnormal condition
occurs. This controller has full consideration in various application of ATS (automatic transfer system)
and can be directly used for PC ATS, CB ATS, CC ATS etc. It has compact structure, advanced circuits,
simple wiring and high reliability, and can be widely used in electrical devices, automatic control and
testing system of electric power, telecommunications, petroleum, coal, metallurgy, railways, municipal
administration, intelligent building, etc.

2 ORDER INFORMATION AND MODULES COMPARISON


2.1 ORDER INFORMATION

2.2 MODULES COMPARISON

Function

AC
DC AC Power Sync Input Ports Output Ports
Type Current RS485
Power Supply Close (Fixed+Config.) (Fixed+Config.)
& Power
HAT700 ● 2+4 2+6 ●

HAT700B ● 2+4 2+6 ●
(LN90V~280V)
HAT700I ● ● 2+4 2+6 ●

HAT700BI ● ● 2+4 2+6 ●
(LN90V~280V)

HAT700S ● ● ● 2+4 2+6 ●
(LN90V~280V)

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 5 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
3 PERFORMANCE AND CHARACTERISTICS
1) System type can set as: S1 (Mains) & S2 (Mains), S1 (Mains) & S2 (Generator), S1 (Generator) &
S2 (Mains), S1 (Generator) & S2 (Generator).
2) 132x64 LCD with backlight, multilingual interface (including English, Chinese or other languages),
push-button operation.
3) Collect and display 2-way 3-phase Voltage, Frequency and Phase.
4) Collect and display Active Power, Reactive Power, Apparent Power, Power Factor and Current.
5) S1/S2 separated over current warning/ trip alarm.
6) NEL (Non-essential Load) trip function.
7) Display S1/S2 Total kW Energy, Total kvar Energy, Total Close Times.
8) Display continuous power supply time and S1/S2 total power supply time.
9) Sync Transfer function; in addition, Voltage Difference, Frequency Difference and Phase
Difference can be displayed.
10) For Stored-Energy type ATS, its close relay will active after the PF Input is active.
11) Over/under voltage, loss of phase, reverse phase sequence, over/under frequency protection.
12) Phase Sequence Transfer function.
13) Automatic/Manual mode. In manual mode, can force the switch to close or open;
14) All parameters can be set on site. Passwords authentication ensures authorized staff operation
only.
15) The genset can be Manual Test on site to achieve start/stop operation.
16) ATS Controller has function of automatic Re-closing.
17) Closing output signal can be set as on intervals or as continuous output.
18) Applicable for PC Three-stage, PC Two-stage, CB and CC switch.
19) Applicable for 2 isolated neutral line.
20) Real-time clock (RTC); Event log Function (Event log can record 99 items circularly).
21) Scheduled Run & Scheduled Not Run (can be set as start genset once a day/week/month whether
with load or not).
22) Can control two generators to work as Cycle Run mode, Master Run mode and Balance Run
mode.
23) Widely power supply range DC(8~35)V allows the controller can bear 80V instantaneous current.
24) Large terminal space allows the controller can bear maximum 625V input voltage.
25) With RS485 isolated communication interface. With "remote controlling, remote measuring,
remote communication, remote regulating" function by the ModBus communication protocol. Can
remote start/stop the genset and remote control the ATS to close or open.
26) Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase 2-wire, and
2-phase 3-wire).
27) Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting,
compact structure with easy installation.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 6 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
4 SPECIFICATION
Items Contents
1. DC 8.0V~35.0V, continuous power supply.
Operating Voltage 2. AC90V~280V during AC power supply L1N1/L2N2 (HAT700B/HAT700BI
/HAT700S).
Power Consumption <5W (Standby mode: ≤2W)
HAT700B/HAT700BI/
AC system HAT700/HAT700I
HAT700S
3P4W (L-L) (80~625)V (80~480)V
AC Voltage Input
3P3W (L-L) (80~625)V (80~625)V
1P2W (L-N) (50~360)V (50~280)V
2P3W (A-B) (80~625)V (80~480)V
Rated Frequency 50/60Hz
Close Relay Output 16A AC250V Volts free output
Auxiliary Relay Output 16A/7A AC250V Volts free output
Digital Input GND (B-) connect is active.
Communication RS485 isolated interface, MODBUS Protocol
Case Dimensions 197mmx152mmx47mm
Panel Cutout 186mmx141mm
Temperature: (-25~+70)°C;
Working Conditions
Humidity: (20~93)%RH
Storage Condition Temperature: (-25~+70)°C
Protection Level IP55 Gasket
Apply AC2.2kV voltage between high voltage terminal and low voltage
Insulation Strength terminal;
The leakage current is not more than 3mA within 1min.
HAT700/HAT700I: 0.7kg
Weight
HAT700B/HAT700BI/HAT700S: 0.8kg

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 7 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
5 MEASURE AND DISPLAY DATA
Data Items HAT700/HAT700B HAT700I/HAT700BI HAT700S
S1/S2 Phase Voltage ( L1-N,L2-N,L3-N) ● ● ●
S1/S2 Line Voltage ( L1-L2,L2-L3,L3-L1) ● ● ●
S1/S2 Phase (L1-L2-L3) ● ● ●
S1/S2 Frequency (L1) ● ● ●
3-Phase Current (I1,I2,I3) ● ●
Phase Sequence (L1-L2-L3) ● ●
3-Phase Active Power kW(P1,P2,P3) ● ●
3-Phase Total Active Power kW(P1+P2+P3) ● ●
3-Phase Reactive Power kvar (Q1,Q2,Q3) ● ●
3-Phase Total Reactive Power kvar (Q1+Q2+Q3) ● ●
3-Phase Apparent Power kVA(A1,A2,A3) ● ●
Total Apparent Power kVA(A1+A2+A3) ● ●
3-Phase Power Factor PF(PF1,PF2,PF3) ● ●
Average Power Factor PF(PF1,PF2,PF3) ● ●
Voltage Difference between S1 and S2 ●
Frequency Difference between S1 and S2 ●
Phase Angle between S1 and S2 ●
Continuous Power Supply Time ● ● ●
Continuous Power Supply Time (Last Time) ● ● ●
S1 Total Power Supply Time ● ● ●
S2 Total Power Supply Time ● ● ●
S1 Total kW Energy kWh ● ●
S2 Total kW Energy kWh ● ●
S1 Total kvar Energy kvarh ● ●
S2 Total kvar Energy kvarh ● ●
S1 Total Close Times ● ● ●
S2 Total Close Times ● ● ●
Real Time Clock ● ● ●
Event Log ● ● ●

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 8 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
6 OPERATION
6.1 INDICATORS

INDICATORS DESCRIPTION
Indicator Type Description
Slow flashing (1time per sec) when warn alarm occurs.
Alarm
Fast flashing (5 times per sec) when fault alarm occurs.
Running Flash when module countdown running (1time per sec)
It is light on when S1 is normal; flashing when S1 is abnormal ((1time per
S1 Power Normal
sec)); off when there is no S1 power.
S1 Close Status It is light on when S1 close input is activated.
It is light on when S2 is normal; flashing when S2 is abnormal ((1time per
S2 Power Normal
sec)); off when there is no S2 power.
S2 Close Status It is light on when S2 close input is activated.
Manual Mode It is light on when the module is in Manual mode.
Auto Mode It is light on when the module is in Auto mode.
Generator Start It is light on when the Start signal is be initiated.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 9 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
6.2 KEY FUNCTION DESCRIPTION

Icon Button Name Function Description


Active in Manual mode.
Press this key, if S1 load is opened, then the S1 closing relay will be
energized; if S1 load is closed, then the S1 opening relay will be energized.
S1 Close/Open
When sync closing is active, if S2 load is closed, press the key will energize
the S1 Sync closing relay; During the S1 is waiting to synchronizing, pressing
this key will de-energize the S1 sync closing relay.
Active in Manual mode.
Press this key, if S2 load is opened, then the S2 closing relay will be
energized; if S1 load is closed, then the S2 opening relay will be energized.
S2 Close/Open
When sync closing is active, if S2 load is closed, press the key will energize
the S2 Sync closing relay; During the S2 is waiting to synchronizing, pressing
this key will de-energize the S2 sync closing relay.

Manual Mode Set controller as Manual mode.

Auto Mode Set controller as Auto mode.

Trial Run Press this key to enter into genset manual start/stop operation interface.

Pressing and holding the key to enter lamp test mode, all LED lamps are lit
Lamp Test
and LCD screen display black.
Press this key to enter into alarm interface; Pressing it again can clear fault
Alarm Reset
alarm.
Press this key to return the main screen; Press it again to enter into menu
Menu interface.
When setting parameters, press this key to return prior menu.
In main screen, press this key to scroll page.

Confirm In menu screen, press this key can move cursor and confirm setting
information.

In main screen, press this key to scroll screen.


Up/Increase In menu interface, press this key to up cursor or increase value in setting
menu.
In main screen, press this key to scroll screen.
Down/Decrease In menu interface, press this key to down cursor or decrease value in setting
menu.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 10 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
7 LCD DISPLAY
7.1 MAIN SCREEN

Status
S1 Normal S1 Voltage Status
S2 Inactive S2 Voltage Status
Genset Standby Genset Status
S1 On Load Switch Status
Auto Mode Current Mode, Alarm Status, Indications, Others
Power
U1LL 380 380 380V S1 Line Voltage (L1-L2、L2-L3、L3-L1)
U1LN 220 220 220V S1 Phase Voltage
Phase 0 120 240° S1 Phase
F1 50.00Hz BAT 27.5V S1 Frequency and genset battery voltage
Auto Mode Current Mode, Alarm Status, Indications, Others
U2LL 0 0 0V S2 Line Voltage(L1-L2、L2-L3、L3-L1)
U2LN 0 0 0V S2 Phase Voltage
Phase #### #### ####° S2 Phase
F2 0.00Hz Load 100% S2 Frequency and present on-load percentage.
Auto Mode Current Mode, Alarm Status, Indications, Others
Load
I 500 500 500A 3-phase current
Phase 0 120 240° 3-phase current phase
TkW 329 PF 1.00 Total active power, power factor
Tkvar 1.3 TkVa 330 Total inactive power, Total apparent Power.
Auto Mode Current Mode, Alarm Status, Indications, Others
kW 126 129 130 3-phase active power
kvar 0.5 0.8 0.7 3-phase reactive power
kVA 127 129 131 3-phase apparent power
PF 1.00 1.00 1.00 3-phase power factor
Auto Mode Current Mode, Alarm Status, Indications, Others
Sync
Volt Diff. 74V x Volt Diff., D-value of 3-phase volt mean
Freq Diff. 0.13Hz ok Freq Diff.
Phase Diff. 12° x Phase Diff.

Auto Mode Current Mode, Alarm Status, Indications, Others


Total

Cont. Power Suppy Time Cont. Power Suppy Time


5:25:18 HH:MM:SS
Last Cont. Powe Supply Last Cont. Powe Supply
8:15:37 HH:MM:SS
Auto Mode Current Mode, Alarm Status, Indications, Others

S1 Total Supply Time S1 Total Supply Time


125:25:18 HH:MM:SS

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 11 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
S2 Total Supply Time S2 Total Supply Time
35:43:29 HH:MM:SS

Auto Mode Current Mode, Alarm Status, Indications, Others

S1 Total kWh S1 Total kWh


16263.6kWh
S2 Total kWh
S2 Total kWh
2879.9kWh

Auto Mode Current Mode, Alarm Status, Indications, Others

S1 Total kvarh S1 Total kvarh


3285.5kvarh
S2 Total kvarh
S2 Total kvarh
672.4kvarh

Auto Mode Current Mode, Alarm Status, Indications, Others

S1 Total Close Nums S1 Total Close Times


25
S2 Total Close Nums
S2 Total Close Times
13

Auto Mode Current Mode, Alarm Status, Indications, Others

Alarms
Alarms 1/2 Alarm number and account
Warn Alarm Alarm type(Warn Alarm、Fault Alarm)
S1 Over Current Alarm event
Fault Alarm Alarm type(Warn Alarm、Fault Alarm)
S1 Failed to Closed Alarm event
Others
S1 S2 1 2 3 4 5 6 Inputs, outputs number
IN Input status, S1/S2 closing input, 1~4 are configurable ports
OUT Output status, S1/S2 closing output, 1~6 are configurable ports
2014-09-09(2)16:53:24 Real-time clock
Auto Mode Current Mode, Alarm Status, Indications, Others
RS485 RS485 Communication
Address 1 Communication Address
Baud Rate 9600bps RS485 Baud Rate
Stop Bit 2bit RS485 Stop Bit
Auto Mode Current Mode, Alarm Status, Indications, Others

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 12 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
7.2 STATUS DESCRIPTION

7.2.1. S1 VOLTAGE STATUS

No. Item Description


1 S1 Available S1 Normal Delay
2 S1 Unavailable S1 Abnormal Delay
3 S1 Available Power supply voltage is within the setting range.
4 S1 Blackout Voltage is 0.
5 S1 Over Volt Voltage is higher than the set value.
6 S1 Under Volt Voltage has fallen below the set value.
7 S1 Over Freq Frequency is higher than the set value.
8 S1 Under Freq Frequency has fallen below the set value.
9 S1 Loss of Phase Loss of any phase of A, B and C.
10 S1 Phase Seq Wrong A-B-C phase sequence is wrong.
7.2.2. S2 VOLTAGE STATUS

No. Item Description


1 S2 Available S2 Normal Delay
2 S2 Unavailable S2 Abnormal Delay
3 S2 Available Power supply voltage is within the setting range.
4 S2 Blackout Voltage is 0.
5 S2 Over Volt Voltage is higher than the set value.
6 S2 Under Volt Voltage has fallen below the set value.
7 S2 Over Freq Frequency is higher than the set value.
8 S2 Under Freq Frequency has fallen below the set value.
9 S2 Loss of Phase Loss of any phase of A, B and C.
10 S2 Phase Seq Wrong A-B-C phase sequence is wrong.

7.2.3. GENSET STATUS

No. Item Description


1 Genset Start Delay Delay time before genset start
2 Genset Return Delay Delay time before genset stop
When scheduled not run is active, its duration time will be
3 Scheduled Not Work
displayed.
4 Scheduled Work When scheduled run is active, its duration time will be displayed.
S1 cycle run countdown will be terminated when cycle start is
5 Gen1 Cycle Run
active.
S2 cycle run countdown will be terminated when cycle start is
6 Gen2 Cycle Run
active.
7 S1 Genset Working Active when system type is “S1 Gens S2 Gens”.
8 S2 Genset Working Active when system type is “S1 Gens S2 Gens”.
9 Genset Working Genset start signal output.
10 Genset Standby There is no start genset signal output.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 13 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

7.2.4. SWITCH STATUS

No. Item Description


1 Ready to Transfer Switch transfer begins.
2 Closing S1 S1 closing delay is in progress.
3 Opening S1 S1 opening delay is in progress.
4 Closing S2 S2 closing delay is in progress.
5 Opening S2 S2 opening delay is in progress.
6 Transfer Rest Interval time between switch transfer
When the S1 “Fail to open” condition occurs, it’s the delay time
7 Closing S1 Again
before the close relay is active for the second time.
When the S1 “Fail to close” condition occurs, it’s the delay time
8 Opening S1 Again
before the open relay is active for the second time.
When the S2 “Fail to open” condition occurs, it’s the delay time
9 Closing S2 Again
before the close relay is active for the second time.
When the S2 “Fail to close” condition occurs, it’s the delay time
10 Opening S2 Again
before the open relay is active for the second time.
It’s the delay time that waiting S1 and S2 sync requirements (volt
11 Waiting Sync
diff. freq diff. phase diff.) are satisfied.
Sync closing S1 is active when the sync requirements are
12 Sync Closing S1
satisfied.
Sync closing S2 is active when the sync requirements are
13 Sync Closing S2
satisfied.
Before S1 is closed, it’s the delay time to confirm “S1 PF Input”
14 Waiting S1 PF
signal is active.
Before S2 is closed, it’s the delay time to confirm “S2 PF Input”
15 Waiting S2 PF
signal is active.
16 Elevator Delay Elevator control output before ATS transfer.
17 S1 On Load S1 was already closed and S1 is taking load.
18 S2 On Load S2 was already closed and S2 is taking load.
19 Offload Switch was already opened and load is disconnect.
7.2.5. WARN ALARMS

Warn alarms are active when controller detects the alarm signals. Alarm indicator will flash slowly (1time
per sec) while illuminated when alarm reset. Warn alarms are not latched.
No. Item Description
When the S1 current has exceeded the pre-set value and the
1 S1 Over Current Warn
action select “Warn”, it will initiate a warning alarm.
When the S2 current has exceeded the pre-set value and the
2 S2 Over Current Warn
action select “Warn”, it will initiate a warning alarm.
When the input is active and the action select “Warn”, it will
3 Forced Open Warn
initiate a warning alarm.
When the battery voltage has fallen below the pre-set value, it
4 Battery Under Volt
will initiate a warning alarm.
When the battery voltage has exceeded the pre-set value, it will
5 Battery Over Volt
initiate a warning alarm.
When the genset fail to sync after the “Waiting Sync” delay has
6 Sync Fail Warn
expired, it will initiate a warning alarm.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 14 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

7.2.6. FAULT ALARMS

Fault alarms are active when controller detects the alarm signals. Alarm indicator will flash rapidly (5
times per sec) and the alarm will last until it was removed manually. Fault alarms are latched.
No. Item Description
1 S1 Failed to Close In Auto mode, S1 close failure is occurs.
2 S1 Failed to Open In Auto mode, S1 open failure is occurs.
3 S2 Failed to Close In Auto mode, S2 close failure is occurs.
4 S2 Failed to Open In Auto mode, S2 open failure is occurs.
When the S1 current has exceeded the pre-set value and the
5 S1 Over Current Trip
action select “Trip”, it will initiate a fault alarm.
When the S2 current has exceeded the pre-set value and the
6 S2 Over Current Trip
action select “Trip”, it will initiate a fault alarm.
When the input is active and the action select “Fault”, it will
7 Forced Open Fault
initiate a fault alarm.
If there is “S1 fail to start” failure occurs when “S1 Gens S2
8 S1 Genset Fault
Gens” system is selected, it will initiate a fault alarm.
If there is “S2 fail to start” failure occurs when “S1 Gens S2
9 S2 Genset Fault
Gens” system is selected, it will initiate a fault alarm.
10 Switch Trip Alarm it will initiate a fault alarm. when the input is active.
When the genset fail to sync after the “Waiting Sync” delay has
11 Sync Fail Fault
expired, it will initiate a fault alarm.

7.2.7. INDICATION

The indication information will continuously display for 2s after it is active.


No. Item Description
When there is fault alarm occurs, the indication will be displayed
1 Please reset the alarm
when change the genset mode to Auto Mode manually.
After S1 was already closed, the indication will be displayed
2 S1 was already closed.
when “S2 close” button is pressed.
After S2 was already closed, the indication will be displayed
3 S2 was already closed.
when “S1 close” button is pressed.
When panel lock is active, the indication as pressing panel
button (expect Up/Down, Confirm and lamp test button).
4 Panel Locked When the input is active, the indication will be displayed when

the panel button is pressed (except ).

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 15 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

7.2.8. OTHERS

No. Item Description


1 Start Inhibit Genset start Inhibit is active.
2 S1 Load Inhibit S1 Load Inhibit input is active.
3 S2 Load Inhibit S2 Load Inhibit input is active.
4 NEL 1 Trip NEL1 off load signal is output.
5 NEL2 Trip NEL2 off load signal is output.
6 NEL3 Trip NEL3 off load signal is output.
7 Remote Gen On Load Remote start (on load) signal is active.
8 Remote Gen Off Load Remote start (off load) signal is active.
9 Gen Start Mains NG Start genset when mains is abnormal.
Cycle Run Start Mode is active when “S1 Gens S2 Gens” system
10 Cycle Gen Start Mode
is active.
Balance Run Start Mode is active when “S1 Gens S2 Gens”
11 Balance Gen Hours Mode
system is active.
Master-Slave Gen Start Master Run Start Mode is active when “S1 Gens S2 Gens”
12
Mode system is active.
13 Auto Mode Current mode is Auto mode.
14 Manual Mode Current mode is Manual mode.

7.3 MAIN MENU

In the main screen, press key will enter into the menu interface.
1.Configuration
2.Data Calibration Press Up/Down key to choose parameters (the current line was
3.Historical Records highlighted with black) and then press Confirm key to enter into the
4.Start/Stop Genset corresponding display screen.
5.About

NOTE:Default password is 01234, user can change it in case of others change the parameters

setting. Please clearly remember the password after changing. If you forget it, please contact Smartgen
services.

NOTE:Data Calibration is for factory use only and correct passwords must be input before entered.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 16 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
8 START/STOP OPERATION
8.1 MANUAL START/STOP

8.1.1. PANEL START/STOP

In the main screen, press key will enter into manual start operation interface.

1.Return
Press Up/Down key to choose parameters (the current line was
2.Stop Genset
highlighted with black) and then press Confirm key to confirm.
3.Start Genset
Genset Stop:Disconnect the start signal, i.e. stop the running genset.
Genset Start:Output the start signal, i.e. start the genset.
When system is “S1 Gens S2 Gens”, manual start/stop menu interface is as follows:
1.Return
2.S1 Genset Stop
Press Up/Down key to choose parameters (the current line was
3.S1 Genset Start
highlighted with black) and then press Confirm key to confirm.
4.S2 Genset Stop
5.S2 Genset Start
S1 Genset Stop:Disconnect the S1 start signal, i.e. stop the running S1 genset.
S1 Genset Start:Output the S1 start signal, i.e. start the S1 genset.
S2 Genset Stop:Disconnect the S2 start signal, i.e. stop the running S2 genset.
S2 Genset Start:Output the S2 start signal, i.e. start the S2 genset.

8.1.2. REMOTE START/STOP

Send remote start/stop signals using MODBUS protocol via RS485 port.
Remote Stop:Disconnect the start signal, i.e. stop the running genset.
Remote Start:Output the start signal, i.e. start the genset.

8.2 AUTO START/STOP

8.2.1 INPUT PORT START/STOP OPERATION

Set input port as “Remote Start On Load” or “Remote Start Off Load”, both could not be set
simultaneously.
Remote Start on Load:When the input is active, genset close relay will active after genset is normal;
when the input inactive, genset will stop automatically.
Remote Start off Load:When the input is active, mains close relay will active after mains is normal;
genset close relay will active when the mains is abnormal while genset is normal; when the input inactive,
genset will stop automatically.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 17 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

8.2.2. “S1 GENS S2 GENS” START/STOP

When system is “S1 Gens S2 Gens”, input port start/stop function is as follows:
Remote Start on Load: Detect S1 or S2 start output according to start mode. Genset close relay will
active after genset is normal.
Remote Start off Load: Detect S1 or S2 start output according to start mode. Both genset S1 close
relay and S2 close relay are deactivated after genset start.
S1,S2 Gens Start Type: Cycs Run, Master Run, Balance Run and Not Used.
Start Mode: Cycle Run Start, Master Run Start, Balance Run Start.
Cycle Run Start:
When remote start is active, S1 and S2 cycle run start according to the cycle run time. At the first time to
start the genset, choose “S1 Start” or “S2 Start” depends on the “Master Set” information. e.g. S1 start
at the first time if “S1 Master” is selected. The S1 cycle run countdown is started according to the preset
delay. At the same time, genset fault delay will be initiated. If S1 genset is normal before the fault delay
has expired, S1 will take load; S2 start after the preset S1 cycle run delay has expired and the S2 loading
process is same as S1. S1 will stop automatically after the S2 has take load successfully. S1 and S2 will
cycle run in this way alternately until the remote start signal deactivated.
During the start process, if there is genset fault alarm (genset fault delay overtime or genset fault input is
active), fail to close or load inhibit alarm occurs, the starting genset will be stop immediately and the
additional genset will be start automatically.
During the cycle run process, if “Auto Mode” is selected, the current status will be hold and the “cycle run
countdown” will be suspended.
Master Run
Mater genset will be start when remote start signal is active. During the start process, if there is genset
fault alarm (genset supply delay overtime or genset fault input is active), fail to close or load inhibit alarm
occurs, the starting genset will be stop immediately and the additional genset will be start automatically.
Otherwise, the master run genset will running continuously until the remote start signal deactivated.
Balance Run
The gensets which has the shortest running hours will be start when remote start signal is active. During
the start process, if there is genset fault alarm (genset supply delay overtime or genset fault input is
active), fail to close or load inhibit alarm occurs, the starting genset will be stop immediately and the
additional genset will be start automatically. Otherwise, the current genset will running continuously until
the remote start signal deactivated.
In system “S1 Gens S2 Gens” to start/stop genset should meet following several conditions:
1) It is active in Auto mode;
2) System set as “S1 Gens S2 Gens”;
3) Output port should be set as “S1 Genset Start” and “S2 Genset Start ”;
4) Input port should be set as “S1 Genset Fault Input”, “S1 Genset Fault Input” and “Remote Start
On Load” or “Remote Start Off Load”;
5) Should set start mode when “S1 Gens S2 Gens” system is selected;
6) Should configure setting “Genset Supply Delay”,If start mode is cycle run, also should set “S1
Cycs Run Time” and “S2 Cycs Run Time”;
Among input ports, “S1 Genset Fault Input” and “S2 Genset Fault Input” are selective setting, Genset
fault can be judged by “Genset Supply Delay” and there no need to inquire the fault alarm via input port.
When S1, S2 start type configured as “Not Used”, there is no start genset signals output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 18 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

8.2.3. SCHEDULED RUN

Once Scheduled Run enables, users can set the scheduled start time. Controller will send start signal at
preset start time. Start signal will deactivated after the start delay has expired.
Scheduled Run On Load or Scheduled Run Off Load can be set.
Scheduled Run On Load: When the input is active, genset close relay will active after genset is normal.
Scheduled Run Off Load: When the input is active, mains close relay will active after mains is normal;
genset close relay will active when the mains is abnormal while genset is normal.
Cycle time of Scheduled Run can be set as start monthly, weekly and daily.
Run Monthly: Monthly start date and time can be set.
Run Weekly: Can start the genset at the same time in couple days of a week. Eg. Start the genset at
8:00 a.m. from Monday to Friday and keep 10 hours.
Run Daily: Can start the genset at same time everyday.

8.2.4. SCHEDULED NOT RUN

Once Scheduled Not Run enables, users can set the “scheduled not start” time. Start signal will
deactivated at preset time and it will be inhibited before the delay has expired.
Cycle time of Scheduled Not Run can be set as monthly, weekly and daily.
Not Run Monthly: Monthly Not start Date and time can be set.
Not Run Weekly: Can Not start the genset at the same time in couple days of a week. Eg. Not Start the
genset at 19:00 p.m. from Monday to Friday and keep 12 hours.
Not Run Daily: Can Not start the genset at same time everyday.

Note: Scheduled Not Run operation is prior to Scheduled Run operation.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 19 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
9 PARAMETERS CONFIGURATION
9.1 ILLUSTRATION

In the main interface, press key, choose Configuration and press again to enter into
password confirmation interface. If password is correct, enter into parameter setting interface, otherwise,
exit to main interface directly. Factory default password is 01234. In parameters configuration interface,

pressing key to return the prior menu.

9.2 PARAMETERS TABLE

Parameters Item Table


No. Item Range Default Description
AC System
The delay from S1 voltage abnormal to
1 S1 Available Delay (0-3600) s 10
normal.
The delay from S1 voltage normal to
2 S1 Unavailable Delay (0-3600)s 5
abnormal.
The delay from S2 voltage abnormal to
3 S2 Available Delay (0-3600)s 10
normal.
The delay from S2 voltage normal to
4 S2 Unavailable Delay (0-3600)s 5
abnormal.
0: S1 Master
5 Master-Slave Set (0-2) 0 1: S2 Master
2: No Master
0: S1 Mains S2 Gen
1: S1 Gen S2 Mains
6 System Type Set (0-3) 0
2: S1 Mains S2 Mains
3: S1 Gen S2 Gen
0: 3-Phase,4-Wire
1: 3-Phase,3-Wire
7 AC System (0-3) 0
2: 2-Phase,3-Wire
3: Single Phase,2-Wire
8 PT Fitted (0-1) 0 0: Disable ; 1: Enable
9 PT Primary (30-30000)V 100 Primary voltage of voltage transformer
10 PT Secondary (30-1000)V 100 Secondary voltage of voltage transformer
11 Rated Voltage (0-30000)V 220 Rated voltage of AC system
12 Over Volt (0-1) 1 0: Disable ; 1: Enable
Upper limit value of voltage; it is abnormal if
13 Over Volt Set Value (0-200)% 120
the value has exceeded the set value.
Upper limit return value of voltage; it is
14 Over Voltage Return (0-200)% 115 normal only when the value has fallen below
the set value.
15 Under voltage (0-1) 1 0: Disable ; 1: Enable
Under Voltage Set Lower limit value of voltage; it is abnormal if
16 (0-200)% 80
Value the value has fallen below the set value.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 20 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
Lower limit return value of voltage; it is
Under Voltage Return
17 (0-200)% 85 normal only when the value has exceeded
Value
the set value.
18 Rated Frequency (10.0-75.0)Hz 50.0 Rated frequency of AC system
19 Over Frequency (0-1) 1 0: Disable ; 1: Enable
Over Frequency Set Upper limit value of frequency; it is abnormal
20 (0-200)% 110
Value if the value has exceeded the set value.
Upper limit return value of frequency; it is
Over Frequency
21 (0- 200)% 104 normal only when the value has fallen below
Return Value
the set value.
22 Under Frequency (0-1) 1 0: Disable ; 1: Enable
Under Frequency Set Lower limit value of frequency; it is abnormal
23 (0- 200)% 90
Value if the value has fallen below the set value.
Lower limit return value of frequency; it is
Under Frequency
24 (0- 200)% 96 normal only when the value has exceeded
Return Value
the set value.
Phase Sequence
25 (0-1) 1 0: Disable ; 1: Enable
Wrong
SWITCH SETTING
0: Disable ; 1: Enable
Disable: The output time was judged
depends on the close relay; the longest
1 Definite C/O Time (0-1) 0
output time up to the set delay.
Enable: The output time last for the preset
time.
2 Close Time (0.1-20.0)s 5.0 Pulse time of close relay.
3 Open Time (0.1-20.0)s 5.0 Pulse time of open relay.
Interval time from S1 switch open to S2
4 Transfer Interval (0-9999)s 1 switch close; or from S2 switch open to S1
switch close.
When the breaker fail to open for the first
time, then the module will close for the
second time and the Again Close Delay
5 Again Close Delay (0-20.0)s 1.0
begins, after the delay has expired, if still
failed to open for the second time, the
module will send out fail to open alarm.
When the breaker fail to close for the first
time, then the module will open for the
second time and the Again Open Delay
6 Again Open Delay (0-20.0)s 1.0
begins, after the delay has expired, if still
failed to close for the second time, the
module will send out fail to close alarm.
0: CB/CC (Use S1 Open and S2 Open to
control)
7 Switch Type (0-2) 0
1: PC Three-stage (PC switch with OFF
position, use S1 Open to control)

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 21 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
2: PC Two-stage (PC switch without OFF
position)
8 Forced Open Action (0-1) 0 0: Warn Alarm 1: Fault Alarm
0: Disable ; 1: Enable
9 Continuously Close (0-1) 0 If “Enable” is selected, “Close Time” and
“Open Time” are deactivated.
10 Sync Enabled (0-1) 0 0: Disable ; 1: Enable
11 Volt diff. Enabled (0-1) 0 0: Disable ; 1: Enable
It’s the maximum voltage difference when
12 Volt diff. (0-50)V 5
the synchronization is successful.
It’s the maximum frequency difference when
13 Freq diff. (0-0.50)Hz 0.20
the synchronization is successful.
It’s the maximum phase difference when the
14 Phase diff. (0-20) ° 5
synchronization is successful.
0: Warn Alarm 1: Fault Alarm
If the “Fail to Sync” failure occurs, “Sync
Waiting” signal will output continuously until
the synchronization is successful.
When the “Warn Alarm” is selected, the
15 Fail to Sync Action (0-1) 0
alarm will be removed after the
synchronization is successful or exit.
When the “Fault Alarm” is selected, the
alarm will be removed only when the “Reset”
button is pressed.
0: Disable ; 1: Enable
If the “Fail to Sync” failure occurs, the alarm
16 Transfer in Sync Fail (0-1) 0
will NOT be initiated and “non-sync close”
will be initiated.
“Fail to Sync”alarm will be initiated after the
17 Fail to Sync Delay (0-9999)s 120
delay has expired.
When the input is active, its delay time will
be initiated. If the correct signal is detected
before the delay has expired, pulse output
Breaker Feedback
18 (0.1-1.0)s 0.6 will be terminated; If the correct signal is
Time
NOT detected after the delay has expired,
“Fail to Close” or “Fail to Open” alarm will be
initiated.
19 ATS Power Type (0-1) 1 0: DC Power;1: AC Power
Lower limit voltage of switch power; The
20 ATS Power Low Point (0-100)% 70 switch can not transfer when the value has
fallen below the set value.
Upper limit voltage of switch power; The
21 ATS Power High Point (0-200)% 130 switch can not transfer when the value has
exceeded the set value.
Generator Setting
1 Gen Start Delay (0-9999)s 1 When the genset is ready to start, start

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 22 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
delay begins, after the start delay has
expired, start signal will be initiated.
When the genset is ready to stop, stop delay
2 Gen Stop Delay (0-9999)s 5 begins, after the stop delay has expired,
stop signal will be initiated.
0: Cycles Gens
1: Master-Slave Gens
3 Gen-Gen Start Mode (0-2) 0
2: Balance Gens Hours
3: Not Used
4 S1 Cycles Work Time (0-9999)min 720 Gens cycle start S1 running time.
5 S2 Cycles Work Time (0-9999)min 720 Gens cycle start S2 running time.
When the start signal is active, the start
delay will be initiated. If the gen voltage lasts
6 Genset Available Time (0-9999)s 120
abnormal after the delay has expired,
“Genset Fault” alarm will be initiated.
7 Battery Volt Enable (0-1) 0 0: Disable ; 1: Enable
8 Battery LV Warn (0-1) 0 0: Disable ; 1: Enable
“Battery Under Volts” alarm will be initiated if
Battery Under Volt Set
9 (0-100.0)V 10.0 the battery voltage has fallen below the set
Value
value.
“Battery Under Volts” alarm will be removed
Battery Under Volt
10 (0-100.0)V 10.5 if the battery voltage has exceeded the set
Return Value
value.
If the battery voltage has fallen below the set
Battery Under Volt
11 (0-3600)s 60 value, “Battery Under Volts” alarm will be
Delay
initiated after the delay has expired.
12 Battery OV Warn (0-1) 0 0: Disable ; 1: Enable
“Battery Over Volts” alarm will be initiated if
Battery Over Volt Set
13 (0-100.0)V 30.0 the battery voltage has exceeded the set
Value
value.
“Battery Over Volts” alarm will be removed if
Battery Over Volt
14 (0-100.0)V 29.5 the battery voltage has fallen below the set
Return Value
value.
If the battery voltage has exceeded the set
Battery Over Volt
15 (0-3600)s 60 value, “Battery Over Volts” alarm will be
Delay
initiated after the delay has expired.
Scheduler Config
1 Schedule Gen Enable (0-1) 0 0: Disable ; 1: Enable
0: Off Load
2 Schedule Load (0-1) 0
1: On Load
0: Monthly
3 Schedule Period (0-2) 0 1: Weekly
2: Daily
4 Schedule Monthly (1-31) 1 The date of start the genset
Bit0: Sunday
5 Schedule Weekly (1-127) 1
Bit1: Monday

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 23 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
Bit2: Tuesday
Bit3: Wednesday
Bit4: Thursday
Bit5: Friday
Bit6: Saturday
6 Schedule Hours (0-23)h 0
The time of start the genset
7 Schedule Minutes (0-59)min 0
8 Schedule Work Time (0-30000)min 30 The duration time of genset running
9 Gen Inhabit Work Set (0-1) 0 0: Disable ; 1: Enable
0: Monthly
10 Inhabit Period (0-2) 0 1: Weekly
2: Daily
11 Inhabit Monthly (1-31) 1 The date of NOT start the genset
Bit0: Sunday
Bit1: Monday
Bit2: Tuesday
12 Inhabit Weekly (1-127) 1 Bit3: Wednesday
Bit4: Thursday
Bit5: Friday
Bit6: Saturday
13 Inhabit Hours (0-23) 0
The time of NOT start the genset
14 Inhabit Minutes (0-59) 0
15 Inhabit Rest Time (0-30000) 30 The duration time of genset NOT running
Load Setting
1 Current CT Enable (0-1) 1 0: Disable ; 1: Enable
2 CT Primary/5 (5-6000)A 500 The primary current of CT.
3 S1 Full Load Rating (5-6000)A 500 The current of S1 taking full load
4 S2 Full Load Rating (5-6000)A 500 The current of S2 taking full load
The maximum active power of S1 taking
5 S1 Max kW Rating (1-20000)kW 200
load
The maximum active power of S2 taking
6 S2 Max kW Rating (1-20000)kW 200
load
7 Over Current Enable (0-1) 1 0: Disable ; 1: Enable
8 Over Current (0-200)% 120 Over current set value
9 Over Current Action (0-1) 0 0: Warn 1: Trip
10 Over Current Type (0-1) 0 0:Definite Time 1:Inverse Definite
It’s the over current delay time when
11 Over Current Delay (0-3600)s 10
“Definite Time” is selected.
It’s the over current multiply when “IDMT” is
12 Multiply (1-36) 36
selected.
13 Elevator Enable (0-1) 0 0: Disable ; 1: Enable
It’s the delay time before the load disconnect
or switch transfer. Used for control the
14 Elevator Delay (0-300)s 300
running elevator stop at the nearest floor
until the switch transfer is terminated.
15 NEL Enable (0-1) 0 0: Disable ; 1: Enable

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 24 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
16 NEL1 Set Value (0-200)% 90 Off load output will active if the load power
has exceeded the set value and the delay
17 NEL1 Delay (0-3600)s 5
time has expired.
18 NEL2 Set Value (0-200)% 100 Off load output will active if the load power
has exceeded the set value and the delay
19 NEL2 Delay (0-3600)s 1
time has expired.
20 NEL Return Enable (0-1) 0 0: Disable ; 1: Enable
21 NEL Return Set Value (0-200)% 50 NEL control will deactivated if the load
power has fallen below the set value and the
22 NEL Return Delay (0-3600)s 5
delay time has expired.
23 NEL Nums (1-3) 3 NEL number
Mains Load NEL
24 (0-1) 0 0: Disable ; 1: Enable
Enable
Digital Input
1 Digital Input 1 (0-29) 1 Forced Open
0: Closed to active;
2 Active Type (0-1) 0
1: Open to active
3 Digital Input 2 (0-29) 8 Switch Trip Input
0: Closed to active;
4 Active Type (0-1) 0
1: Open to active
5 Digital Input 3 (0-29) 0 Not Used
0: Closed to active;
6 Active Type (0-1) 0
1: Open to active
7 Digital Input 4 (0-29) 0 Not Used
0: Closed to active;
8 Active Type (0-1) 0
1: Open to active
Relay Output
0:Normally open;
1 Relay Output 1 (0-1) 0
1:Normally close
2 Contents Setting (0-92) 49 ATS Power L1
0:Normally open;
3 Relay Output 2 (0-1) 0
1:Normally close
4 Contents Setting (0-92) 52 ATS Power N
0:Normally open;
5 Relay Output 3 (0-1) 0
1:Normally close
6 Contents Setting (0-92) 35 S1 Open Control
0:Normally open;
7 Relay Output 4 (0-1) 0
1:Normally close
8 Contents Setting (0-92) 37 S2 Open Control
0:Normally open;
9 Relay Output 5 (0-1) 0
1:Normally close
10 Contents Setting (0-92) 1 Custom Combined 1
0:Normally open;
11 Relay Output 6 (0-1) 0
1:Normally close
12 Contents Setting (0-92) 32 Genset Start Output
13 Combined 1 Or Out 1 (0-1) 0 0:Normally open;

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 25 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
Active Type 1:Normally close
Combined 1 Or Out 1
14 (0-92) 23 S1 Normal
Contents Setting
Combined 1 Or Out 2 0:Normally open;
15 (0-1) 0
Active Type 1:Normally close
Combined 1 Or Out 2
16 (0-92) 25 S2 Normal
Contents Setting
Combined 1 And Out 0:Normally open;
17 (0-1) 1
Active Type 1:Normally close
Combined 1 And Out
18 (0-92) 0 Not Used
Contents Setting
Combined 2 Or Out 1 0:Normally open;
19 (0-1) 0
Active Type 1:Normally close
Combined 2 Or Out 1
20 (0-92) 0 Not Used
Contents Setting
Combined 2 Or Out 2 0:Normally open;
21 (0-1) 0
Active Type 1:Normally close
Combined 2 Or Out 2
22 (0-92) 0 Not Used
Contents Setting
Combined 2 And Out 0:Normally open;
23 (0-1) 0
Active Type 1:Normally close
Combined 2 And Out
24 (0-92) 0 Not Used
Contents Setting
Combined 3 Or Out 1 0:Normally open;
25 (0-1) 0
Active Type 1:Normally close
Combined 3 Or Out 1
26 (0-92) 0 Not Used
Contents Setting
Combined 3 Or Out 2 0:Normally open;
27 (0-1) 0
Active Type 1:Normally close
Combined 3 Or Out 2
28 (0-92) 0 Not Used
Contents Setting
Combined 3 And Out 0:Normally open;
29 (0-1) 0
Active Type 1:Normally close
Combined 3 And Out
30 (0-92) 0 Not Used
Contents Setting
Combined 4 Or Out 1 0:Normally open;
31 (0-1) 0
Active Type 1:Normally close
Combined 4 Or Out 1
32 (0-92) 0 Not Used
Contents Setting
Combined 4 Or Out 2 0:Normally open;
33 (0-1) 0
Active Type 1:Normally close
Combined 4 Or Out 2
34 (0-92) 0 Not Used
Contents Setting
Combined 4 And Out 0:Normally open;
35 (0-1) 0
Active Type 1:Normally close
36 Combined 4 And Out (0-92) 0 Not Used

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 26 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
No. Item Range Default Description
Contents Setting
Combined 5 Or Out 1 0:Normally open;
37 (0-1) 0
Active Type 1:Normally close
Combined 5 Or Out 1
38 (0-92) 0 Not Used
Contents Setting
Combined 5 Or Out 2 0:Normally open;
39 (0-1) 0
Active Type 1:Normally close
Combined 5 Or Out 2
40 (0-92) 0 Not Used
Contents Setting
Combined 5 And Out 0:Normally open;
41 (0-1) 0
Active Type 1:Normally close
Combined 5 And Out
42 (0-92) 0 Not Used
Contents Setting
Combined 6 Or Out 1 0:Normally open;
43 (0-1) 0
Active Type 1:Normally close
Combined 6 Or Out 1
44 (0-92) 0 Not Used
Contents Setting
Combined 6 Or Out 2 0:Normally open;
45 (0-1) 0
Active Type 1:Normally close
Combined 6 Or Out 2
46 (0-92) 0 Not Used
Contents Setting
Combined 6 And Out 0:Normally open;
47 (0-1) 0
Active Type 1:Normally close
Combined 6 And Out
48 (0-92) 0 Not Used
Contents Setting
Module Setting
0: Previous Mode (Keep the working mode
last time running)
1 Power On Mode (0-2) 0
1: Manual
2: Auto
2 Module Address (1-254) 1 RS485 communication address
0: Chinese
1: English
3 Language (0-2) 0
2: Others(Language can be set via PC
software)
4 Password (00000-65535) 01234 For entering parameters setting.
0:2400
1:4800
5 Baud Rate (0-3) 2
2:9600
3:19200
6 Stop Bit (1-2) 2 2 stop bits or 1 stop bit can be set.
7 Date and Time

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 27 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
9.3 INPUT/OUTPUT FUNCTION DESCRIPTION

9.3.1 INPUT PORTS FUNCTION


No. Item Description
0 Not used Invalid
No matter the genset is in manual mode or Auto mode, when the
1 Forced Open input is active, this will force the breaker to transfer the ATS to OFF
position. “No Breaking” ATS is unavailable.
When active, controller will send genset start signal immediately.
2 Remote Start on Load
When mains is normal, genset will close the breaker.
When active, controller will send a genset start signal immediately.
3 Remote Start Off Load
When mains is normal, genset will not close the breaker.
When active, all LED lights on the front panel are illuminated and
4 Test lamp the backlight of the LCD is illuminated while the LCD screen is
black in color.
5 Gen1 Fault Input In Cycle start, if the input is active, S1 Gens start will be inhibited.
6 Gen2 Fault Input In Cycle start, if the input is active, S2 Gens start will be inhibited.
In Auto mode, start signal will deactivated after the stop delay has
7 Start Inhibit Input expired. In Manual mode, if the genset is running, users should
stop it manually; then the manual start signal will deactivated.
8 Breaker Trip Input Trip failure input
In Manual mode, S1 manual close is inhibited; if breaker already
9 S1 Close Inhibit closed, users should open it manually. In Auto mode, if breaker
already closed, then close relay will deactivated or S2 take load.
In Manual mode, S2 manual close is inhibited; if breaker already
10 S2 Close Inhibit closed, users should open it manually. In Auto mode, if breaker
already closed, then close relay will deactivated or S1 take load.
11 S1 Breaker PF Input When the S1 PF input is active, S1 close relay will activated.
12 S2 Breaker PF Input When the S2 PF input is active, S2 close relay will activated.
Simulate the panel S1 O/C button to control the S1 close/open.
13 S1 O/C Key
Self-reset button is recommended.
Simulate the panel S2 O/C button to control the S2 close/open.
14 S2 O/C Key
Self-reset button is recommended.
15 Alarm Reset Reset the current alarm.
16 Alarm Mute Silence the audible alarm.
Control the NEL off load manually. Self-reset button is
17 NEL Trip Key
recommended.
Control the NEL on load again manually. Self-reset button is
18 NEL Return Key
recommended.
19 S1 Master Input Set S1 master use compulsively.
20 S2 Master Input Set S2 master use compulsively.
21 Forced Manual Mode Set the controller in Manual mode compulsively.
22 Forced Auto Mode Set the controller in Auto mode compulsively.

23 Panel Lock Panel button operation are inhibited (Except and

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 28 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL

).
24 Sync Inhibit Sync transfer function is deactivated.
25 Scheduler Inhibit Schedule Start and Schedule Not Start function are deactivated.
Simulate S1 voltage is normal; the S1 voltage abnormal delay is
26 Simulate S1 OK
deactivated.
Simulate S2 voltage is normal; the S2 voltage abnormal delay is
27 Simulate S2 OK
deactivated.
28 Reserved
29 Reserved
9.3.2 OUTPUT PORTS FUNCTION
No. Items Description
0 Not Used Invalid
1 Custom Period 1
2 Custom Period 2
3 Custom Period 3
4 Custom Period 4
5 Custom Period 5
6 Custom Period 6
7 Reserved
8 Reserved
9 Reserved
10 Reserved
11 Common Alarm It includes fault alarm and warn alarm.
12 Common Fault Alarm It includes Transition Fault alarm and Over Current alarm.
It includes S1 Phase Sequence Wrong alarm, S2 Phase Sequence
13 Common Warn Alarm
Wrong alarm, Over Current and Forced Open alarm.
It includes S1 Fail to Close alarm, S1 Fail to Open alarm, S2 Fail to
14 Transition Fault
Close alarm, S2 Fail to Open alarm,.
Action when common alarm occurs. Can be connected annunciator
15 Audible Alarm externally. When “alarm mute” input is active or 60s delay has
expired, it can remove the alarm.
16 Reserved
17 Genset Start Delay Output when start signal is initiated.
18 Genset Stop Delay Output when stop signal is initiated.
Output before the load disconnect or switch transfer. Used for
19 Elevator Control control the running elevator stop at the nearest floor until the switch
transfer is terminated.
20 Reserved
21 Reserved
22 Reserved
23 S1 Available Output when S1 power is normal.
24 S1 Unavailable Output when S1 power is abnormal.
25 S2 Available Output when S2 power is normal.
26 S2 Unavailable Output when S2 power is abnormal.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 29 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
27 S1 Over Current Output when S1 over current occurs.
28 S2 Over Current Output when S2 over current occurs.
29 Reserved
30 Auto Mode Output when the genset is in Auto mode.
31 Manual Mode Output when the genset is in Manual mode.
32 Genset Start Output Control the genset to start.
33 Reserved
34 S1 Close Control Control the S1 switch to close.
Control the S1 switch to open. If PC Three-stage is selected, it also
35 S1 Open Control
control the S2 switch to open.
36 S2 Close Control Control the S2 switch to close.
37 S2 Open Control Control the S2 switch to open.
38 Reserved
39 Reserved
40 NEL1 Trip
Control the NEL off load when the output is active; It can control the
41 NEL2 Trip
NEL on load again when the output deactivated.
42 NEL3 Trip
43 Reserved
44 Reserved
45 Breaker1 On Feedback The close status of S1 switch
46 Breaker2 On Feedback The close status of S2 switch
When the system type is “S1 Gen S2 Gen”, it controls the S1
47 S1 Genset Start
genset start.
When the system type is “S1 Gen S2 Gen”, it controls the S2
48 S2 Genset Start
genset start.
49 ATS Power L1
50 ATS Power L2
ATS power supply
51 ATS Power L3
52 ATS Power N
53 Remote Control Control the output via RS485 command.
54 Input 1 Status
55 Input 2 Status
Input status
56 Input 3 Status
57 Input 4 Status
58 Reserved
59 Reserved
60 Reserved
61 Reserved
62 Reserved
63 Reserved
64 S1 Blackout
65 S1 Over Volt
66 S1 Under Volt S1 power supply status
67 S1 Over Freq
68 S1 Under Freq

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 30 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
69 S1 Loss Of Phase
70 S1 Phase Seq Wrong
71 Reserved
72 Reserved
73 S2 Blackout
74 S2 Over Volt
75 S2 Under Volt
76 S2 Over Freq S2 power supply status
77 S2 Under Freq
78 S2 Loss Of Phase
79 S2 Phase Seq Wrong
80 Reserved
81 Reserved
82 Sync Fail Output when the synchronization is failed.
83 Sync Waiting Output when the genset is waiting for synchronization.
84 Switching Output during the switch transfer process.
85 Battery Under Volt Output when battery under voltage alarm occurs.
86 Battery Over Volt Output when battery over voltage alarm occurs.
87 Gen Inhabit Work Output during the Schedule Not Run process.
88 Scheduler Gen Start Output during the Schedule Run process.
89 Reserved
90 Reserved
91 Reserved
92 Reserved

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 31 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
9.3.3 CUSTOM PERIOD OUTPUT
Defined combination output is composed by 3 parts, condition output SW1 or SW2 and condition output
SW3.

SW1 or SW2 is TRUE, while SW3 is TRUE, Defined combination output is active;
SW1 and SW2 are FALSE, or SW3 is FALSE, Defined combination output isdeactivated.

NOTE: SW1, SW2, SW3 can be set as any contents except for “defined combination output” in the

output setting.

NOTE: 3 parts of defined combination output (SW1, SW2, SW3) couldn’t include or recursively include

themselves.
Example,
Contents of probably condition output SW1: output port 1 is active;
Close when probably condition output SW1 is active /inactive: close when active (disconnect when
inactive);
Contents of probably condition output SW2, output port 2 is active;
Close when probably condition output SW2 is active /inactive: close when active (disconnect when
inactive);
Contents of probably condition output SW3: output port 3 is active;
Close when probably condition output SW3 is active /inactive: close when active (disconnect when
inactive);
When input port 1 active or input port 2 active, if input port 3 is active, Defined combination output is
outputting; If input port 3 inactive, Defined combination output is not outputting;
When input port 1 inactive and input port 2 inactive, whatever input port 3 is active or not, Defined
combination output is not outputting.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 32 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
9.4 DEFINITE TIME DELAY AND INVERSE DEFINITE MINIMUM TIME SETTING

Definite Time:overcurrent delay is definite time delay. Different overcurrent value has corresponding
delay.
Inverse Definite Minimum Time(IDMT):overcurrent delay decrease with the increase of overcurrent.
Different overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)2
T:Overcurrent delay (second)
t:Timing multiplier ratio
IA:Current max. load current(L1/L2/L3)
IT:Overcurrent setting value
Example:
t = 36
IA = 550A
IT =500A
Conclusion: T = 3600s(1hour)

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 33 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
10 EVENT LOG

On the main screen press key and select Event log, and then press key again, the screen will
show the event log interface as follow:
After enter into the “Event Log” interface, press / to view records.
Action Event 10/99 Alarm type, number and total count.
S1Genset Start Event Log;
S1 Inactive S1Power supply status;
S2 Inactive S2 Power supply status;
2014-09-12 16:57:26 Date and time;

Press to view the detailed record information; press it again to exit the current record.
Action Event 10/99 Alarm type, number and total count.
S1 Genset Start Event Log;
S1 Inactive S1Power supply status;
S2 Normal S2 Power supply status;
2014-09-12 16:57:26 Date and time;

Press / to view the detailed record information; press it again to exit the current record.
Action Event 10/99 Alarm type, number and total count.
S1 Genset Start Event Log;
U1LN 0 0 0V S1 Phase Voltage;
U2LN 220 221 219V S2 Phase Voltage;
F1 0.00Hz F2 0.00Hz S1 Frequency,S2 Frequency;

Press / to view the detailed record information; press it again to exit the current record.
Action Event 10/99 Alarm type, number and total count.
S1 Genset Start Event Log;
I 130 145 136A Load Current;
TkW 220 PF 1.00 Active Power and Power Factor;

Event log includes: event log type, event log, S1 power supply, S2 power supply, S1 3-phase voltage, S2
3-phase voltage, S1 frequency, S2 frequency, load current, active power, power factor and the record
date and time.
Event log type includes: Action Event, Warn Event and Fault Event. All fault event actions are fault alarm
while all warn event actions are warn alarm.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 34 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
Action events are as follows:
No. Action Events Description
1 Closing S1 Record when the S1 close relay activated.
2 Closing S2 Record when the S2 close relay activated.
3 Opening Record when the open relay (S1 Open or S2 Open) activated.
4 Sync Closing S1 Record when the S1 sync close relay activated.
5 Sync Closing S2 Record when the S2 sync close relay activated.
6 NEL1 Trip Record when the NEL 1 Trip output.
7 NEL2 Trip Record when the NEL 2 Trip output.
8 NEL3 Trip Record when the NEL 3 Trip output.
9 Genset Start Record when the Genset Start signal output.
10 S1 Genset Start Record when the S1 Genset Start signal output.
11 S2 Genset Start Record when the S2 Genset Start signal output.
12 Genset Stop Record when the Genset Start signal deactivated.
13 S1 Genset Stop Record when the S1 Genset Start signal deactivated.
14 S2 Genset Stop Record when the S2 Genset Start signal deactivated.
15 Auto Mode Record when the genset mode transferred to Auto Mode.
16 Manual Mode Record when the genset mode transferred to Module Mode.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 35 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
11 ATS OPERATION
11.1 MANUAL OPERATION

Manual mode is selected by pressing the button; a LED besides the button will illuminate to

confirm the operation.


 Press S1 button, S1 close relay will active, after the close delay has expired, S1 close relay
will deactivated and the S1 take load. Press S1 button again (Invalid for the ATS without
Open Control), S1 open relay will active, after the open delay has expired, S1 open relay will
deactivated and the S1 off load.
 Press S2 button, S2 close relay will active, after the close delay has expired, S2 close relay
will deactivated and the S2 take load. Press S2 button again (Invalid for the ATS without
Open Control), S2 open relay will active, after the open delay has expired, S2 open relay will
deactivated and the S2 off load.

11.2 AUTOMATIC OPERATION

Auto mode is selected by pressing the button; a LED besides the button will illuminate to confirm

the operation. The controller will select S1 power or S2 power according to the preset “master set” and
control the genset to start according to the preset conditions.

11.3 SYNC CLOSING

If both of S1 Power and S2 power are normal, “Sync Closing” means transfer the load from the current
power to the other power after the synchronization requirements have reached.
Sync Closing:If “Sync Closing” is enabled, its function will active; otherwise, “Sync Closing” function will
Not be implemented.
Volt Difference:It’s the maximum voltage difference between S1 and S2 during “Sync Closing”. If “Volt
Difference” is disabled, then the voltage difference will not be detected during “Sync Closing”.
Freq Difference:It’s the maximum frequency difference between S1 and S2 during “Sync Closing”.
Phase diff.:It’s the maximum phase difference between S1 and S2 during “Sync Closing”. In general,
the phase difference value should not be too large in order to avoid the too large load shock when
closing.
Fail to Sync Action:Can be set as “Warn Alarm” or “Fault Alarm”. If the “Fail to Sync” failure occurs,
“Sync Waiting” signal will output continuously until the synchronization is successful. When the “Warn
Alarm” is selected, the alarm will be removed after the synchronization is successful or exit. When the
“Fault Alarm” is selected, the alarm will be removed only when the “Reset” button is pressed.
Fail Sync Coercion Close:If it is enabled, when the “Fail to Sync” failure occurs, the alarm will NOT be
initiated and “non-sync close” will be initiated.
Fail to Sync Delay:“Fail to Sync”alarm will be initiated after the delay has expired.
Sync Transfer Time:When the input is active, its delay time will be initiated. If the correct signal is
detected before the delay has expired, pulse output will be terminated; If the correct signal is NOT

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 36 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
detected after the delay has expired, “Fail to Close” or “Fail to Open” alarm will be initiated.

Sync Transfer Diagram:

S1 Sync Closing:
If both of S1 Power and S2 power are normal, S2 has taken load, then S1 close relay will active until S1
close signal is detected or “Sync Transfer Time” has expired; After that, S1 close relay will deactivated.
At the same time, S2 open relay will active until S2 open signal is detected or “Sync Transfer Time” has
expired; then S2 open relay will deactivated.
During the synchronization process, if Close (or Open) action is not successful after the “Sync Transfer
Time” has expired, “Fail to Close” or “Fail to Open” alarm will be initiated.
S1 Sync Closing Diagram:

S2 Sync Closing:
If both of S1 Power and S2 power are normal, S1 has taken load, then S2 close relay will active until S2
close signal is detected or “Sync Transfer Time” has expired; After that, S2 close relay will deactivated.
At the same time, S1 open relay will active until S1 open signal is detected or “Sync Transfer Time” has
expired; then S1 open relay will deactivated.
During the synchronization process, if Close (or Open) action is not successful after the “Sync Transfer
Time” has expired, “Fail to Close” or “Fail to Open” alarm will be initiated.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 37 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
S2 Sync Closing Diagram:

MANUAL SYNC CLOSING


In Manual mode, both of S1 Power and S2 power are normal: if S1 has taken load, press S2 button
will lead S2 sync closing; if S2 has taken load, press S1 button will lead S1 sync closing. During
“Waiting Sync” process, press again will stop Sync Closing; Long pressing button will initiate
“Non-sync Closing” operation immediately. If synchronization is not successful after the “Waiting Sync”
delay has expired, “Fail to Sync” alarm will be initiated while “Sync Waiting” signal will output
continuously until the synchronization is successful or press to cancel the operation.
AUTO SYNC CLOSING
In Auto mode, if backup power is normal and it is already closed, after master power return to normal, it
will sync closing.

Warn:After the “Sync Closing” is active, S1 and S2 paralleling situations that may arise. If “S1 Mains
S2 Mains” system is selected, please make sure the switch are self-locking to avoid the S1 and S2
closed simultaneously. Otherwise, damage the switch and circuit, or endanger personal safety situation
may happen.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 38 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
12 ATS POWER SUPPLY
Switch Power Type can be set as DC Power or AC Power. If DC Power is selected, then the switch can
be transferred at any time (even when both S1 and S2 are outage). If AC Power is selected, whether the
power is normal or not should be judged according to the ATS power setting and AC power voltage.
The power of ATS is supplied by controller, as long as one power is normal, this can ensure ATS voltage
power supply normally and can be transferred properly.
Users should select power supply voltage (phase voltage or line voltage) based on ATS type. If choose
phase voltage, connect the phase voltage of S1 and S2 (e.g. A phase) to normally close (Pin5) and
normally open (Pin7) contact of auxiliary output 1; connect N phase of S1 and S2 to normally close (Pin8)
and normally open (Pin10) contact of auxiliary output 2. And then connect the common output of
auxiliary output 1 and auxiliary output 2 to ATS power supplies. Enter into the parameter setting interface,
set the configurable output 1 as "ATS power L1" while set the configurable output 2 as "ATS power N". If
the ATS power supplied by Line Voltage, same procedures as above but change phase N to phase
voltage and the auxiliary output 2 should be configured according to the set. Wiring diagrams are shown
as following:

ATS phase voltage power supply ATS line voltage power supply

Note: Normally Close (N/C) input voltage must come from S1 voltage.

Note: ATS Close/Open relay will active only when the ATS power is normal. If ATS Power output port

is not configured, then the ATS power is supplied by L1-N phase (system default).

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 39 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
13 LOAD SHEDDING
Non-essential load ---- NEL for short.
The controller can control the NEL1, NEL2 and NEL3 to trip separately. The order of the essentiality is:
NEL3 > NEL2 > NEL1
 Auto trip:
When NEL auto trip is enabled:
If the genset power has exceed the NEL trip value, after the trip delay, NEL1 will trip the earliest, and
then is NEL2,NEL3;
When NEL auto reconnection is enabled:
If the genset power has fallen below the auto reconnection set value, after the auto reconnection delay,
NEL3 will reconnection the earliest, and then is NEL2,NEL1;

 Manual Trip
If NEL manual trip input is active (earthed failing edge is active), NEL1 will trip without delay; If NEL
manual trip input is active again, NEL2 will trip; If NEL manual trip input is active the third time, NEL3 will
trip. During this process, the controller do not detect if the genset power has exceed the NEL trip value or
not.
If NEL manual reconnection input is active (earthed failing edge is active), NEL3 will reconnect without
delay; If NEL manual reconnection input is active again, NEL2 will reconnect; If NEL manual
reconnection input is active the third time, NEL1 will reconnect. During this process, the controller
detects the genset power: if the genset power has fallen below the NEL reconnection value, then the
input is active; if it doesn’t, the input is deactivated.

Note: When auto trip and auto reconnection are enabled, manual trip is still active.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 40 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
14 COMMUNICATION CONFIGURATION
HAT700 series controller equips with RS485 serial port which enable the connection of LAN. It uses
Modbus protocol via PC or system software, it can also be applicable to dual power switching
management to factories, telecom, industrial and civil buildings, which achieves “remote control, remote
measuring, remote communication” functions.
More information of Communication Protocol, please refer to “HAT600 Communication Protocol”.
Communication parameters:
Module address 1 (range: 1-254, User can set it)
Baud rate 9600 bps (2400/4800/9600/19200bps)
Data bit 8bit
Parity bit None
Stop bit 1 bit or 2-bits

15 DESCRIPTION OF CONNECTING TERMINALS

Terminal description,
NO. Items Description Remark
1 Volts free; Relay contact; Normally
S1Close Output Capacity: 250V 16A
2 Open output
3 Volts free; Relay contact; Normally
S2 Close Output Capacity:250V16A
4 Open output
5 Normally Close
Default: ATS Power Volts free; Relay contact Output
6 Aux. Output 1 COM
L1 Capacity: 250V16A
7 Normally Open
8 Aux. Output 2 Normally Close Default: ATS Power Volts free; Relay contact Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 41 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
NO. Items Description Remark
9 COM N Capacity: 250V16A
10 Normally Open
11 A1
12 B1 For single phase, only connect A1,
S1 AC System 3P4W voltage input
13 C1 N1
14 N1
15 A2
16 B2 For single phase, only connect A2,
S2 AC System 3P4W voltage input
17 C2 N2
18 N2
Connected with negative of starter
19 B- Ground terminal
battery.
Connected with positive of starter DC(8-35)V; Power supplied by
20 B+
battery. controller.
Detect the S1 ATS closing status. Volts
21 S1 Close Output Ground connected is active.
free contact input.
Detect the S2 ATS closing status. Volts
22 S2 Close Output Ground connected is active.
free contact input.
23 Aux. Input 1 Ground connected is active.
24 Aux. Input 2 Ground connected is active.
User-defined.
25 Aux. Input 3 Ground connected is active.
26 Aux. Input 4 Ground connected is active.
27 Volts free; Relay contact; Normally
Aux. Output 3 Capacity: 250V7A
28 Open output
29 Volts free; Relay contact; Normally
Aux. Output 4 Capacity: 250V7A
30 Open output
31 Volts free; Relay contact; Normally
Aux. Output 5 Capacity: 250V7A
32 Open output
33 Volts free; Relay contact; Normally
Aux. Output 6 Close output Capacity: 250V7A
34
Default: Genset Start Output
35 IA In
CT Secondary A-Phase current input
36 IA Out
37 IB In
CT Secondary B-Phase current input Only suitable for HAT700I/HAT700BI
38 IB Out
39 IC In
CT Secondary C-Phase current input
40 IC Out
41 RS485 A+ 120Ω impedance matched resistance
42 RS485 B- RS485 Communication Port should be connected according to the
43 RS485 different situation.
Programming
LINK Used for PC program updating.
Port

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 42 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
16 TYPICAL WIRING DIAGRAM
ATYS3 Wiring Diagram

Parameters Setting
Switch Type PC Three-stage
Aux. Output 1 ATS Power L
Aux. Output 2 ATS Power N
Aux. Output 4 S1 Open Control
Aux. Output 6 Gen Start Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 43 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
SGQ-N/T Wiring Diagram

Parameters Setting
Switch Type PC Two-stage
Aux. Output 1 ATS Power L
Aux. Output 2 ATS Power N
Aux. Output 6 Gen Start Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 44 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
SGQ-M Wiring Diagram

Parameters Setting
Switch Type PC Two-stage
Aux. Output 1 ATS Power L
Aux. Output 2 ATS Power N
Aux. Output 6 Gen Start Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 45 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
VITZRO/PHETENG Wiring Diagram

Parameters Setting
Switch Type CB/CC
Aux. Output 1 ATS Power L
Aux. Output 2 ATS Power N
Aux. Output 4 S1 Open Control
Aux. Output 5 S2 Open Control
Aux. Output 6 Gen Start Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 46 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
Contactor Wiring Diagram

Parameters Setting
Switch Type CB/CC
Aux. Output 6 Gen Start Output
Close Continuous Out Enable

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 47 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
ATYSM3S Wiring Diagram

Parameters Setting
Switch Type PC Three-stage
Aux. Output 1 ATS Power L
Aux. Output 2 ATS Power N
Aux. Output 4 S1 Open Control
Aux. Output 6 Gen Start Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 48 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
Breaker Wiring Diagram

MCH:Stored Energy Motor;MN:Under Voltage Trip;MX:Open Relay;XF:Close Relay;


Parameters Setting
Switch Type CB/CC
Aux. Output 4 S1 Open Control
Aux. Output 5 S2 Open Control
Aux. Output 6 Gen Start Output

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 49 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
ASCO Series 230 RTS

Parameters Setting
Switch Type PC Three-stage
Aux. Output 1 ATS Power L
Aux. Output 2 ATS Power N
Aux. Output 4 S1 Open Control
Aux. Output 6 Gen Start Output

NOTE: All above are application diagrams of HAT700 series ATS controllers. However, HAT700 and

HAT700B have no sample current input, please skip over the current part of the diagram.

Note:Auxiliary Output 6 is default set as Genset Start Output (Normally Open) and there is only

normally close contact in it. The controller also can control the genset start even if there is no power
supply. If DC Power is selected, Genset Start Output port can be set as other items.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 50 of 51


HAT700 SERIES ATS CONTROLLER USER MANUAL
17 INSTALLATION

Controller is panel built-in design; it is fixed by clips when installed. The controller’s overall dimensions and
cutout dimensions for panel, please refers to as following,
Unit: mm

18 FAULT FINDING
Symptoms Possible Solutions
Check DC voltage.
Controller no response with
Check DC fuse.
power.
Check AC Power supply.
Check RS485’s connections of A and B is reverse connect or not.
Check RS485 transfer model whether damage or not.
RS485 communication is
Check the module address.
abnormal
If above methods can't solve the problem, parallel connection 120Ω
resistor between RS485 A terminal and B terminal is recommended.
Check auxiliary output connections, pay attention to normally open
Auxiliary Output Error contact and normally close contact.
Check the output settings in parameters settings.
Ensure that the auxiliary input is soundly connected to GND when it’s
active, while hung up when it is inactive.
Auxiliary Input Abnormal ( Note: The input port will be possibly destroyed when connected with
voltage)
Check the input settings in parameters settings.
Check ATS.
Genset running while ATS Check the connection wirings between the controller and the ATS.
not transfer Ensure that the switch type is same as the setting.
Check ATS power and its connection.
Check system type setting.
Genset Start Abnormal Check the output settings in parameters settings.
Check all Start/Stop settings.

HAT700 Series ATS Controller 2016-11-07 Version 1.4 Page 51 of 51

You might also like