Active Reactive Apparent Power
Active Reactive Apparent Power
long exposure of city lights. Light is emitted twice each cycle. Power in an electric circuit is the rate of flow of energy past a given point of the circuit. In alternating current circuits, energy storage elements such as inductance and capacitance may result in periodic reversals of the direction of energy flow. The portion of power that, averaged over a complete cycle of the AC waveform, results in net transfer of energy in one direction is known as real power. The portion of power due to stored energy, which returns to the source in each cycle, is known as reactive power.
Contents
[hide]
1 Real, reactive, and apparent power 2 Power factor 3 Reactive power 4 Unbalanced polyphase systems 5 Basic calculations using real numbers 6 Multiple frequency systems 7 See also 8 References
The apparent power is the vector sum of real and reactive power. Real power (P) Reactive power (Q) Complex power (S) Apparent Power (|S|) In a simple alternating current (AC) circuit consisting of a source and a linear load, both the current and voltage are sinusoidal. If the load is purely resistive, the two quantities reverse their polarity at the same time. At every instant the product of voltage and current is positive, indicating that the direction of energy flow does not reverse. In this case, only real power is transferred. If the load is purely reactive, then the voltage and current are 90 degrees out of phase. For half of each cycle, the product of voltage and current is positive, but on the other half of the cycle, the product is negative, indicating that on average, exactly as much energy flows toward the load as flows back. There is no net energy flow over one cycle. In this case, only reactive energy flowsthere is no net transfer of energy to the load. Practical loads have resistance, inductance, and capacitance, so both real and reactive power will flow to real loads. Power engineers measure apparent power as the vector sum of real and reactive power. Apparent power is the product of the root-mean-square voltage and current. Engineers care about apparent power, because even though the current associated with reactive power does no work at the load, it heats the wires, wasting energy. Conductors, transformers and generators must be sized to carry the total current, not just the current that does useful work. Another consequence is that adding the apparent power for two loads will not accurately give the total apparent power unless they have the same displacement between current and voltage (the same power factor). If a capacitor and an inductor are placed in parallel, then the currents flowing through the inductor and the capacitor tend to cancel out rather than adding. Conventionally, capacitors are considered to generate reactive power and inductors to consume it. This is the fundamental mechanism for controlling the power factor in electric power transmission; capacitors (or inductors) are inserted in a circuit to partially cancel reactive power 'consumed' by the load.
Engineers use the following terms to describe energy flow in a system (and assign each of them a different unit to differentiate between them):
Real power (P) or active power [1]: watt [W] Reactive power (Q): volt-amperes reactive [var] Complex power (S): volt-ampere [VA] Apparent Power (|S|), that is, the absolute value of complex power S: volt-ampere [VA]
In the diagram, P is the real power, Q is the reactive power (in this case positive), S is the complex power and the length of S is the apparent power. Reactive power does not transfer energy, so it is represented as the imaginary axis of the vector diagram. Real power moves energy, so it is the real axis. The unit for all forms of power is the watt (symbol: W), but this unit is generally reserved for real power. Apparent power is conventionally expressed in volt-amperes (VA) since it is the product of rms voltage and rms current. The unit for reactive power is expressed as VAr, which stands for volt-amperes reactive. Since reactive power transfers no net energy to the load, it is sometimes called "wattless" power. It does, however, serve an important function in electrical grids and its lack has been cited as a significant factor in the Northeast Blackout of 2003.[2] Understanding the relationship between these three quantities lies at the heart of understanding power engineering. The mathematical relationship among them can be represented by vectors or expressed using complex numbers, (where j is the imaginary unit).
Where the waveforms are purely sinusoidal, the power factor is the cosine of the phase angle () between the current and voltage sinusoid waveforms. Equipment data sheets and nameplates often will abbreviate power factor as "cos" for this reason. Example: The real power is 700 W and the phase angle between voltage and current is 45.6. The power factor is cos(45.6) = 0.700. The apparent power is then: 700 W / cos(45.6) = 1000 VA. [3]
that is, the quotient of the sums of the real powers for each phase over the sum of the apparent power for each phase.
that is, the quotient of the sums of the real powers for each phase over the magnitude of the sum of the complex powers for each phase. The 1920 committee found no consensus and the topic continued to dominate discussions. In 1930 another committee formed and once again failed to resolve the question. The transcripts of
their discussions are the lengthiest and most controversial ever published by the AIEE (Emanuel, 1993). Further resolution of this debate did not come until the late 1990s.
For a perfect capacitor or inductor there is no net power transfer, so all power is reactive. Therefore for a perfect capacitor or inductor:
Where X is the reactance of the capacitor or inductor. If X is defined as being positive for an inductor and negative for a capacitor then we can remove the modulus signs from Q and X and get.
however the time average of a function of the form cos(t+k) is zero provided that is nonzero. Therefore the only product terms that have a nonzero average are those where the frequency of voltage and current match. In other words it is possible to calculate real (average) power by simply treating each frequency separately and adding up the answers. Furthermore, if we assume the voltage of the mains supply is a single frequency (which it usually is), this shows that harmonic currents are a bad thing. They will increase the rms current (since there will be non-zero terms added) and therefore apparent power, but they will have no effect on the real power transferred. Hence, harmonic currents will reduce the power factor. Harmonic currents can be reduced by a filter placed at the input of the device. Typically this will consist of either just a capacitor (relying on parasitic resistance and inductance in the supply) or a capacitor-inductor network. An active power factor correction circuit at the input would generally reduce the harmonic currents further and maintain the power factor closer to unity.