FIRE ALARM CONTROL PANEL - BS-200

Autroprime Interactive Fire Detection System


Product Datasheet

Features
• SelfVerify function for automatic testing of detectors
• Automatic setup
• Automatic addressing of detectors
• Two loops
• USB for data transfer to/from memory stick
• User-friendly display and operator controls
• Backlit operating buttons. Text display suitable for night-
time operation
• Surface mounting
• Designed to meet EN 54 requirements and conforms to CE
standards
• Complies with environmental conditions of IEC-721-3-3
class 3k5

Application/Description
The BS-200 is an integrated fire alarm control panel for small to
medium sized installations. The panel serves as a stand-alone panel. A
maximum of 8 additional panels can be freely mixed and connected to
the Fire Alarm Control Panel via the RS-485 Panel Bus, including
Repeater Panels BS-211, Information Panels BV-210, Fire Brigade Panels
BU-210 and Mimic Drivers BUR-200.

All alarm handling and system features can be configured, controlled


and monitored from the panel. Indicators
The standard panel is prepared for two detection loops, but it can • 8x40 character alphanumeric display
accommodate up to a maximum of four detection loops using the loop • Alarm, more alarms, Pre-alarm, Remote call, Remote
extension pack BSD-200A/PACK*. The loops support most of AutroSafe Call Response, Fault, Disabled Function, Supervisory
detectors, several types of I/O devices for monitored outputs, open Condition, Test condition, System Fault, Power,
collector outputs, galvanic isolated inputs and monitored inputs. It has Delayed Activation,
a 5A power module for battery charging.
• Annunciator Fault, Remote Call Fault, Annunciator
The panel is menu operated on a 8-line display, with 40 characters per Disabled, Remote Call Disabled, Reduced Detection
line. • Internal buzzer

The Operator Panel (BS-210), which is an integrated part of the BS-200


panel, can also be mounted separately outside the cabinet.
Operator Controls
Capacity • More Events, Mute Panel, Silence, Reset, Prolong
Maximum number of: Delay, Activate Outputs
Detection loops per fire alarm control panel 2 (4*) • Keypad with navigational functions (Cancel/Back,
Loop Units per detection loop 127 Enter, directional keys (arrow up/down and
Loop Units per branch on a detection loop 32 left/right)), Function and Select (MultiSelect) key
• Backlit buttons and text
Loop sounders per detection loop 40
• Fireman’s key
Fire Brigade/Information/Repeater Panels and Mimic
8
Drivers per fire alarm control panel
Serial ports 1
Ethernet 1
USB host ports 2
Languages supported 15

116-P-BS200/CGB, Rev. F, 2020-10-20


Fire Alarm Control Panel - BS-200

Panel Bus Connection (connector J13 and J14)


Technical specifications
Dimensions (mm) 420 x 346 x 140
Weight 9 kg (excluding batteries)
Materials Steel cabinet, ABS/PC moulded front
Mounting Surface, flush or rack mounting
Protection class IEC-529 / IP30
Operating temperature -15°C to + 55°C
Storage temperature - 40°C to + 70°C
Humidity, non-condensing Maximum 95% RH
115/230VAC
Power supply 1,6/0,8A
Frequency: 50/60Hz
Current consumption 200mA at 27VDC
Loops 2
Capacity- loop units 127 per loop
2 x 12V= 24V not included, maximum 12
Batteries
Ah
Communication Built-in TCP/IP (Ethernet) for Modbus,
Serial port

Part number Description


116-BS-200 Fire Alarm Control Panel

Stand-alone Panel Panels interconnected on the RS-485 Panel Bus

Fire Alarm Control Panel BS-200

BU-210
RS-485 Panel bus

BV-210

ESPA 444 communication protocol or


NMEA protocol for VDR systems (RS-232, RS-422/485) BS-211

Modbus RTU protocol (serial/ethernet)