RTHDE3G2G1
RTHDE3G2G1
RTHDE3G2G1
Job Information
Job01
Unit Information
Refrigeration capacity 1434 kW Cooling efficiency 0.178 kW/kW
AHRI NPLV.IP 0.108 kW/kW Refrigerant charge (HFC-134a) 318 kg
Shipping weight 7917 kg Operating weight 8761 kg
Full Load Sound Pressure-AHRI 83 dBA Acoustic Insulation
Condition
Pressure vessel code
Refrigeration isolation No refrigerant isolation valves
valves
Oil cooler Without oil cooler
Evaporator Information
Leaving fluid evap 7.00 C Flow evap 68.40 L/s
Entering fluid evap 12.00 C Fluid pressure drop evap 7693.97 mm H2O
Minimum flow evap 25.93 L/s Fouling factor evap 0.017610 m2-deg C/kW
Number of evaporator passes 4 pass Fluid freeze point evap 0.00 C
Evap fluid type Water Fluid concentration evap
Condenser Information
Entering fluid cond 32.00 C Flow cond 79.09 L/s
Leaving fluid cond 37.00 C Fluid pressure drop cond 5713.41 mm H2O
Number of cond passes 2 pass condenser Fouling factor cond 0.044025 m2-deg C/kW
Cond fluid type Water Fluid concentration cond
Condenser tube type Enhanced fin - copper Maximum flow cond 123.7 L/s
Pressure drop at min flow cond Pressure drop at max flow cond 127 kPa
Minimum flow cond
Electrical Information
Unit voltage 380. Volt 3 phase Unit hertz 50. Hertz
Total power 255.4 kW Starter type AdaptiR-2
Minimum circuit ampacity 535.69 A Maximum overcurrent protection 800.00 A
Starter expected inrush 428.55 A Motor locked rotor amps 2303.00 A
Run load amps/chiller input amps 428.55 A AFD output amps 467.86 A
This unit complies with the efficiency requirements of ASHRAE Standard 90.1-1999
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump
Water-Heating Packages Certification Program, which is based on AHRI Standard
550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in
the AHRI Directory at www.ahridirectory.org.