Bybu - xr725 - Ul Product Iq

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Design/System/Construction/Assembly Usage Disclaimer

Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation
and use of UL Certified products, equipment, system, devices, and materials.
Authorities Having Jurisdiction should be consulted before construction.
Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for
compliance with applicable requirements. The published information cannot always address every construction nuance
encountered in the field.
When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the
product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide
Information for each product category and each group of assemblies. The Guide Information includes specifics
concerning alternate materials and alternate methods of construction.
Only products which bear UL's Mark are considered Certified.

BYBU - Fire-resistance Ratings - ANSI/UL 1709


See General Information for Fire-resistance Ratings - ANSI/UL 1709

Design No. XR725


February 19, 2020

Ratings — 3/4, 1, 1-1/2, 2, 2-1/2, 3 or 4 Hr


* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions
employing the UL or cUL Certification (such as Canada), respectively.
1. Steel Column — Min size of column W8x10.

2. Spray-Applied Fire-Resistive Materials* — See table below for appropriate thickness. Prepared by mixing with water
according to instructions on each bag of mixture and spraying in one or more coats, as necessary, onto the metal lath
surfaces, which must be clean and free of dirt, loose scale and oil. As an alternate to spraying, may be machine mixed and
trowel applied. Min avg density of 47 pcf (753 kg/m3), with min individual value of 43 pcf (689 kg/m3). For method of
density determination, see Design Information Section, Sprayed Material. Type M-II/P investigated for UL 2431
Classification Category I-A and Exterior Environmental Purpose.
Min Required Thickness (inch) for Hourly Rating Period (min)

W/D 45 60 90 120 150 180 240

0.33 5/8 3/4 15/16 1-1/8 1-1/4 1-7/16 1-13/16

0.43 5/8 3/4 15/16 1-1/8 1-1/4 1-7/16 1-13/16

0.57 5/8 3/4 15/16 1-1/8 1-1/4 1-7/16 1-13/16

0.68 1/2 9/16 3/4 15/16 1-1/8 1-5/16 1-11/16

0.75 1/2 9/16 3/4 7/8 1-1/16 1-3/16 1-1/2

0.84 1/2 9/16 3/4 7/8 1-1/16 1-1/8 1-7/16

0.90 1/2 9/16 3/4 7/8 1-1/16 1-1/8 1-7/16

1.00 7/16 9/16 3/4 7/8 1-1/16 1-1/8 1-7/16

1.10 3/8 9/16 3/4 7/8 1-1/16 1-1/8 1-7/16

1.20 5/16 1/2 3/4 7/8 1-1/16 1-1/8 1-7/16


1.30 5/16 1/2 3/4 7/8 1-1/16 1-1/8 1-7/16

1.40 1/4 7/16 3/4 7/8 1-1/16 1-1/8 1-7/16

1.50 1/4 3/8 11/16 7/8 1-1/16 1-1/8 1-7/16

1.60 1/4 3/8 5/8 7/8 1-1/16 1-1/8 1-7/16

1.63 1/4 3/8 5/8 3/4 15/16 1-1/16 1-3/8

1.70 1/4 5/16 5/8 3/4 15/16 1-1/16 1-3/8

1.80 1/4 5/16 9/16 3/4 15/16 1-1/16 1-3/8

1.90 1/4 5/16 1/2 3/4 15/16 1-1/16 1-3/8

2.00 1/4 1/4 1/2 11/16 15/16 1-1/16 1-3/8

2.10 1/4 1/4 7/16 11/16 7/8 1-1/16 1-3/8

2.20 1/4 1/4 7/16 5/8 13/16 1-1/16 1-3/8

2.30 1/4 1/4 7/16 5/8 13/16 1 1-3/8

2.40 1/4 1/4 3/8 9/16 3/4 15/16 1-5/16

2.50 1/4 1/4 3/8 9/16 3/4 7/8 1-1/4

2.55 1/4 1/4 3/8 9/16 11/16 7/8 1-1/4

Min Required Thickness (mm) for Hourly Rating Period (min)

HP/A 45 60 90 120 150 180 240

406 16 20 24 29 32 37 47

312 16 20 24 29 32 37 47

235 16 20 24 29 32 37 47

197 13 15 20 24 29 34 43

179 13 15 20 23 27 31 39

160 13 15 20 23 27 29 37

149 13 15 20 23 27 29 37

134 12 15 20 23 27 29 37

122 10 15 20 23 27 29 37

112 8 13 20 23 27 29 37

103 8 13 20 23 27 29 37

96 7 12 20 23 27 29 37

89 7 10 18 23 27 29 37

84 7 10 16 23 27 29 37

82 7 10 16 20 24 27 35

79 7 8 16 20 24 27 35
74 7 8 15 20 24 27 35

71 7 8 13 20 24 27 35

67 7 7 13 18 24 27 35

64 7 7 12 18 23 27 35

61 7 7 12 16 21 27 35

58 7 7 12 16 21 26 35

56 7 7 10 15 20 24 34

54 7 7 10 15 20 23 32

53 7 7 10 15 18 23 32

BERLIN CO LTD — Type M-II/P investigated for Exterior Use, and additionally evaluated for acid and solvent spray exposure.

ISOLATEK INTERNATIONAL — Type M-II/P investigated for Exterior Use, and additionally evaluated for acid and solvent spray
exposure.

GREENTECH ASIA PACIFIC SDN BDH — Type M-II/P investigated for Exterior Use, and additionally evaluated for acid and solvent
spray exposure.

GREENTECH THERMAL INSULATION PRODUCTS MFG CO L L C — Type M-II/P investigated for Exterior Use, and additionally
evaluated for acid and solvent spray exposure.

NEWKEM PRODUCTS CORP — Type M-II/P investigated for Exterior Use, and additionally evaluated for acid and solvent spray
exposure.

PERLITE ITALIANA SRL — Type M-II/P investigated for Exterior Use, and additionally evaluated for acid and solvent spray exposure.

3. Metal Lath — Expanded steel lath, weighing 3.4 lb per sq yd. Lath wrapped around entire column surface with minimum
1 in overlap. Secured with power actuated fasteners located at the center of webs and flanges, spaced 18 in OC.

3A. Metal Lath — For boxed type protection. Min 3.4 lb per sq yd expanded steel. Lath lapped minimum 1 in. at vertical
joint on column flange and secured with power actuated fasteners, located at the center of the flanges, spaced 18 in OC.

4. Corner Bead — (Optional, Not Shown) — No. 25 MSG galv expanded steel corner bead with minimum 2 in. legs may be
used in conjunction with column cage. When used, placed over each corner of column cage and attached to column with
powder actuated fasteners and washers or attached to metal lath with tie wire spaced 18 in. O.C.

* Indicates such products shall bear the UL or cUL Certification Mark for
jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
Last Updated on 2020-02-19

The appearance of a company's name or product in this database does not in itself assure that products so identified have been
manufactured under UL Solutions' Follow - Up Service. Only those products bearing the UL Mark should be considered to be Certified and
covered under UL Solutions' Follow - Up Service. Always look for the Mark on the product.

UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1. The Guide Information,
Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner,
without any manipulation of the data (or drawings). 2. The statement "Reprinted from Product iQ with permission from UL Solutions" must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "©2024
UL LLC."