Ckt no.

P AT AF LOAD DESCRIPTION VA VOLT AMPERE SIZE OF WIRE CONDUIT


1 2 15 50 13 LIGHTING OUTLET 1300 230 5.59 2-3.5 sqmm THNN Cu 20mm PVC

2 2 15 50 13 LIGHTING OUTLET 1300 230 5.59 2-3.5 sqmm THNN Cu 20mm PVC
3 2 15 50 15 LIGHTING OUTLET 1500 230 6.45 2-3.5 sqmm THNN Cu 20mm PVC

4 2 15 50 15 LIGHTING OUTLET 1500 230 6.45 2-3.5 sqmm THNN Cu 20mm PVC

5 2 15 50 15 LIGHTING OUTLET 1500 230 6.45 2-3.5 sqmm THNN Cu 20mm PVC

6 2 30 50 1 REFRIGERATOR 1800 230 7.83 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 25mm PVC

7 2 20 50 1 REFRIGERATOR 1800 230 7.83 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 25mm PVC

8 2 30 50 1 RANGE 1800 230 7.83 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 25mm PVC

9 2 30 50 8 CONVENIENCE OUTLET 1440 230 6.26 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 20mm PVC

10 2 20 50 8 CONVENIENCE OUTLET 1440 230 6.26 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 20mm PVC

11 2 20 50 8 CONVENIENCE OUTLET 1440 230 6.26 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 20mm PVC

12 2 20 50 8 CONVENIENCE OUTLET 1440 230 6.26 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 20mm PVC

13 2 30 50 1 1.0 HP ACU OUTLET 1840 230 8.00 2-3.5 sqmm THNN Cu + 1-3.5 sqmm THNN Grnd. 25mm PVC

14 2 30 50 1 SPARE 1000 230 4.35 STUB-IN 20mm PVC

21100 91.41

E LOAD SCHEDULE
2

FROM EXISTING
POWER SOURCE

GENERAL ELECTRICAL NOTES LO LO REF R CO CO SPARE


1. ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THESE PLANS AND SPECIFICATIONS. 2 4 6 8 10 12 14
THE APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE RULES AND REGULATION
OF THE LOCAL ENFORCING AUTHORITY, AND THE REQUIREMENTS OF THE LOCAL POWER AND TELEPHONE COMPANIES.
THE ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
15A 15A 30A 30A 20A 20A 30A
2. SERVICE FROM THE ELECTRIC POWER COMPANY SHALL BE 220V, 2 PHASE, 60HZ. ALL INSTALLATION SHALL HE CONCEALED
FROM VIEW BY INSTALLING CONDUCTORS PVC CONDUIT, POWER AND LIGHTING DISTRIBUTION EMBEDDED IN CONCRETE
125 AT
SHALL BE IN PVC MOLDFLEX CONDUITS.
15A 15A 15A 30A 20A 20A 30A
3. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THNN" UNLESS OTHERWISE INDICATED IN THE
MINIMUM SIZE FOR POWER AND LIGHTING SHALL BE 3.5 MM2 WIRE.

4. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR CONNECTION TO
THE POWER SUPPLY.
ELECTRIC METER
M 1 3 5 7
LO LO LO REF CO CO ACU
9 11 13

5. ALL RECEPTACLES SHALL BE OF THE GROUNDING TYPE.

6. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANELBOARDS, LIGHTING FIXTURES AND ALL NON-CURRENT CARRYING
METAL PARTS BE PROPERLY GROUNDED IN ACCORDANCE WITH THE PHILIPPINE ELECTRICAL CODE.

7. ALL THE PANELBOARDS SHALL BE PROVIDED WITH GROUNDING BUS. CIRCUIT BREAKERS SHALL BE BOLT-ON TYPE AND OF
THE THERMAL-MAGNETIC TYPE, COMMON TRIP WITH THE RATINGS AND NUMBER OF POLES INDICATED IN THE DRAWINGS

8. THE MOUNTING HEIGHTS OF WIRING DEVICES SHALL BE AS FOLLOWS:


A. LIGHT SWITCHES 1.4M ABOVE FLOOR FINISH
B. CONVENIENCE OUTLETS 0.3 ABOVE FLOOR FINISH OR AS REQUIRED
C. TELEPHONE OUTLETS 0.3 ABOVE FLOOR FINISH OR AS REQUIRED 2 2
2 - 38 mm THNN CU2 WIRE + 1 - 14.0 mm THW
D. PANELBOARDS & CABINETS 1.4 ABOVE FLOOR FINISH AT CENTER OR AS REQUIRED. GROUND IN 32 mm RSC

9. ALL MOUNTING HEIGHTS SHALL BE SUBJECT TO ARCHITECTS APPROVAL PRIOR TO INSTALLATION

10. WHENEVER NECESSARY FULL BOXES SHALL BE PROVIDED EVEN IF NOT INDICATED IN THE PLANS.

11. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT AND IMMEDIATE SUPERVISION OF A DULY QUALIFIED
LICENSED ELECTRICAL ENGINEER. E RISER DIAGRAM
2

THIS DRAWING ACTING AS AN PROJECT TITLE & LOCATION: NAME AND SECTION: SHEET CONTENT: SHEET NO:
INSTRUMENT OF SERVICE IS THE
EXCLUSIVE PROPERTY OF THE
ARCHITECT AND AS SUCH MUST
NOT BE REPRODUCED OR
HASLEY ANNE R. GALANG, ANGEL G. GUIAO, JOSE C FLORES

E2
ELECTRICAL
COPIED IN PART OR IN WHOLE
WITHOUT THEIR PERMISSION.
PROPOSED TWO (2) STOREY LOAD SCHEDULE, ELECTRICAL NOTES, RISER DIAGRAM
ALL DRAWINGS ARE TO BE PRC REG NO: TIN NO: INSTRUCTOR:
RETURNED WHEN NO LONGER IN
USE. PTR NO: PLACED ISSUED:
RESIDENCE
REPUBLIC ACT 545 DATE ISSUED:
AR JONIE S. DAVID