03.ceiling Cassette (60Hz, R22)
03.ceiling Cassette (60Hz, R22)
(60Hz)
LT60 2004-B1
General Description
Thank you very much for your special patronage of LG air conditioners.
LG’s "Ceiling Cassette" is a indoor unit which is installed for the significant purpose. The ceiling cassette is
used for the commercial purposes. It can be installed in various places such as restaurants, hotels, offices and
meeting rooms.
This unit has nice outlook and is equipped with many special features. It has four louver for the air circulation in
all directions which in turn can maintain even and wide cooling. In other side it has facility for high elevation pip-
ing(30m), built in drain pump (drain throw 70cm),high ceiling operation, auto change over and others for facili-
tating its working. Noise level of the unit is very low.
In installation field unit is installed in fall ceiling. It has wide capacity range from 1~5RT.
A lot of information regarding the design & installation of this system is provided in this publication. This new
products series contains data on the same pattern.
Please utilize all the information for conducting your business efficiently.
Make sure the specification, dimension or others technical data are same as provided in enginering data book
before you start the project.
LG Electronics Inc.
Air Conditioning Division
TABLE OF CONTENTS
Table of contents Page
4 Ceiling Cassette(60Hz)
2. Model Number Nomenclature
L T - E 1 8 2 0 C L
Options
L : Basic A : Plasma Air Purifying
Model Type
C : Cooling Only A : Cooling Only + Gold Fin
H : Heat Pump B : Heat Pump + Gold Fin
Development Sequence
Chassis Type
C : C Chassis E : E Chassis D : D Chassis
Development Sequence
Function
A : Basic C : Plasma Air Purifying
Panel Look
L : Basic Panel Look
Chassis Type
Model Type
C : Cooling Only H : Heat Pump
Jet Cool :
-In this mode quick and fast cooling is done. Cold and
high velocity air is supplied to the room till the indoor
temperature reaches 18°C.
Tele Control :
- It provides you ease of control.Air conditioner can
be switched on/off by the telephone. It saves time &
energy.
ON OFF ON OFF
Dust
electrode
Dust particles
Plasma Air Purifier : Pre-filter Ionizer
discharge
Dusts Collection
+
- It not only removes microscopic contaminants & +6.5KV +
discharge Purified
Polluted +
dust, but also removes house mites, pollen, and pet Air
+
fresh Air
+
fur helps to prevent allergic diseases like asthma.It
Generating dusts aluminum coated
Odour
provides odor free, dust free and allergy free air. plasma Odor molecule electrode(-)
(3.25KV discharge)
1 2 ........ 16
Group Control :
- It enables to control up to 16 units with the help of
one wired remote controller.All the units will follow
same setting of temperature & other sub functions.
........
6 Ceiling Cassette(60Hz)
3. Features & Benefits
Central Control :
- It enables to control 16 x 8 = 128 units with the help Main M M M M M M
of 8 controllers. All units can be put on and off from PCB 1 2 16 17 18 128
one Central Room. For Setting Temperature, Fan
Speed and other sub functions, access the LCD Sub Sub Sub Sub Sub Sub
wired remote controller of each unit. 1 2 16 17 18 128
On Off
Set no. Time 01 03 05 07 09 11 13 15 17 19 21 23
Plasma
Set/Clr
Auto Changeover :
- While starting the unit, it first senses the indoor temperature & starts the unit either in the cooling or in heating
mode, depending upon the indoor temperature. Range of operation is Setting Temp.± 2°C.
Defrost / Deicing :
- In the heating mode, it prevents the ice formation on the outdoor unit. The heating cycle is reversed to the
cooling cycle to defrost the evaporator pipe of the outdoor unit. While defrost cycle, the compressor is on and
indoor fan, outdoor fan and 4-way valve are off.
8 Ceiling Cassette(60Hz)
3. Features & Benefits
5~6W
Others LG
CHILD LOCK
-Display
Vane 3 Open Vane 3 Close Open Close Open Close Vane 1 Vane 3
Time Time
Vane 4
Space Control:
Vanes angle can be controlled by pair, considering its
installation environment.
- For example direct drafts can be annoying, leading
to discomfort and reduced productivity vane control
helps to eliminate this problem.
- Easily controlled by wired remote control.
- Air Flow can be controlled easily regarding any
space environment.
10 Ceiling Cassette(60Hz)
4. List of Functions
Ceiling Cassette
Function
LT-C1220AA LT-E1820CL/CA LT-E1820HL/HA LT-C182ELA(C)0 LT-H182ELA(C)0
Air Discharge outlet 1 4 4 4 4
Airflow Direction control (left & right) - - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - - O - O
Auto Elevation Grille - - - - -
Auto Operation O O O O O
Auto Restart Operation O O O O O
Auto Swing O O O O O
Central Control Accessory Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - - -
Child Lock Function O O O O O
Cooling & Fan Operation O O - O -
Coolling, Heating & Fan Operation - - O - O
Defrost / Deicing - - O - O
Deodorizing Filter - - - - -
Drain Pump O O O O O
E.S.P. Control - - - - -
Electric Heater - - - - -
Energy Saving Gold Fin Optional Optional Optional Optional Optional
Environment Friendly Refrigerant - - - - -
Fire Alarm Function - - - - -
Forced Operation O O O O O
Group Control O O O O O
High Ceiling Operation O O O O O
Hot Start - - O - O
Jet Cool O O O O O
Low Ambient Control Optional Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O O
Restart Delay (3-minutes) O O O O O
Self Diagnosis O O O O O
Sleep Mode - - - - -
Soft Dry Operation O O O O O
Space Control - - - O O
Swirl Swing - - - O O
Tele Control Accessory Accessory Accessory Accessory Accessory
Temperature Control O O O O O
Test Function O O O O O
Time Delay Safety Function O O O O O
Timer (weekly) O O O O O
Timer (24 hr On/Off) O O O O O
Two Thermistor Control O O O O O
Wired LCD Remote Controller O O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory Accessory
Zero Standby Power O O O O O
Zone Control - - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
Ceiling Cassette
Function
LT-E2420CL/CA LT-E2420HL/HA LT-C242ELA(C)0 LT-H242ELA(C)0 LT-C302FLA(C)0 LT-H302FLA(C)0
Air Discharge outlet 4 4 4 4 4 4
Airflow Direction control (left & right) - - - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/3 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - O - O O O
Auto Elevation Grille - - - - - -
Auto Operation O O O O O O
Auto Restart Operation O O O O O O
Auto Swing O O O O O O
Central Control Accessory Accessory Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - - - -
Child Lock Function O O O O O O
Cooling & Fan Operation O - O - O -
Coolling, Heating & Fan Operation - O - O - O
Defrost / Deicing - O - O - O
Deodorizing Filter - - - - - -
Drain Pump O O O O O O
E.S.P. Control - - - - - -
Electric Heater - - - - - -
Energy Saving Gold Fin Optional Optional Optional Optional Optional Optional
Environment Friendly Refrigerant - - - - - -
Fire Alarm Function - - - - - -
Forced Operation O O O O O O
Group Control O O O O O O
High Ceiling Operation O O O O O O
Hot Start - O - O O O
Jet Cool O O O O O O
Low Ambient Control Optional Optional Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O O O
Restart Delay (3-minutes) O O O O O O
Self Diagnosis O O O O O O
Sleep Mode - - - - - -
Soft Dry Operation O O O O O O
Space Control - - O O O O
Swirl Swing - - O O O O
Tele Control Accessory Accessory Accessory Accessory Accessory Accessory
Temperature Control O O O O O O
Test Function O O O O O O
Time Delay Safety Function O O O O O O
Timer (weekly) O O O O O O
Timer (24 hr On/Off) O O O O O O
Two Thermistor Control O O O O O O
Wired LCD Remote Controller O O O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory Accessory Accessory
Zero Standby Power O O O O O O
Zone Control - - - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
12 Ceiling Cassette(60Hz)
4. List of Functions
Ceiling Cassette
Function
LT-C362DLA(C)0 LT-H362DLA(C)0 LT-C362DLA(C)1 LT-H362DLA(C)1
Air Discharge outlet 4 4 4 4
Airflow Direction control (left & right) - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - O - O
Auto Elevation Grille - - Optional Optional
Auto Operation O O O O
Auto Restart Operation O O O O
Auto Swing O O O O
Central Control Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - -
Child Lock Function O O O O
Cooling & Fan Operation O - O -
Coolling, Heating & Fan Operation - O - O
Defrost / Deicing - O - O
Deodorizing Filter - - - -
Drain Pump O O O O
E.S.P. Control - - - -
Electric Heater - - - -
Energy Saving Gold Fin Optional Optional - -
Environment Friendly Refrigerant - - - -
Fire Alarm Function - - - -
Forced Operation O O O O
Group Control O O O O
High Ceiling Operation O O O O
Hot Start - O - O
Jet Cool O O O O
Low Ambient Control Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O
Restart Delay (3-minutes) O O O O
Self Diagnosis O O O O
Sleep Mode - - - -
Soft Dry Operation O O O O
Space Control - - O O
Swirl Swing - - O O
Tele Control Accessory Accessory Accessory Accessory
Temperature Control O O O O
Test Function O O O O
Time Delay Safety Function O O O O
Timer (weekly) O O O O
Timer (24 hr On/Off) O O O O
Two Thermistor Control O O O O
Wired LCD Remote Controller O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory
Zero Standby Power O O O O
Zone Control - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
Ceiling Cassette
Function
LT-D4220CL/CA LT-D4220HL/HA LT-C422DLA(C)0 LT-H422DLA(C)0 LT-D4820CL/CA LT-D4820HL/HA
Air Discharge outlet 4 4 4 4 4 4
Airflow Direction control (left & right) - - - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/3 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - O - O - O
Auto Elevation Grille - - - - - -
Auto Operation O O O O O O
Auto Restart Operation O O O O O O
Auto Swing O O O O O O
Central Control Accessory Accessory Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - - - -
Child Lock Function O O O O O O
Cooling & Fan Operation O - O - O -
Coolling, Heating & Fan Operation - O - O - O
Defrost / Deicing - O - O - O
Deodorizing Filter - - - - - -
Drain Pump O O O O O O
E.S.P. Control - - - - - -
Electric Heater - - - - - -
Energy Saving Gold Fin Optional Optional Optional Optional Optional Optional
Environment Friendly Refrigerant - - - - - -
Fire Alarm Function - - - - - -
Forced Operation O O O O O O
Group Control O O O O O O
High Ceiling Operation O O O O O O
Hot Start - O - O - O
Jet Cool O O O O O O
Low Ambient Control Optional Optional Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O O O
Restart Delay (3-minutes) O O O O O O
Self Diagnosis O O O O O O
Sleep Mode - - - - - -
Soft Dry Operation O O O O O O
Space Control - - O O - -
Swirl Swing - - O O - -
Tele Control Accessory Accessory Accessory Accessory Accessory Accessory
Temperature Control O O O O O O
Test Function O O O O O O
Time Delay Safety Function O O O O O O
Timer (weekly) O O O O O O
Timer (24 hr On/Off) O O O O O O
Two Thermistor Control O O O O O O
Wired LCD Remote Controller O O O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory Accessory Accessory
Zero Standby Power O O O O O O
Zone Control - - - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
14 Ceiling Cassette(60Hz)
4. List of Functions
Ceiling Cassette
Function
LT-C482DLA(C)0 LT-H482DLA(C)0 LT-C48BDLA(C)0 LT-H48BDLA(C)0 LT-C48BDLA(C)1 LT-H48BDLA(C)1
Air Discharge outlet 4 4 4 4 4 4
Airflow Direction control (left & right) - - - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/3 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - O - O - O
Auto Elevation Grille - - - - - -
Auto Operation O O O O O O
Auto Restart Operation O O O O O O
Auto Swing O O O O O O
Central Control Accessory Accessory Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - - - -
Child Lock Function O O O O O O
Cooling & Fan Operation O - O - O -
Coolling, Heating & Fan Operation - O - O - O
Defrost / Deicing - O - O - O
Deodorizing Filter - - - - - -
Drain Pump O O O O O O
E.S.P. Control - - - - - -
Electric Heater - - - - - -
Energy Saving Gold Fin Optional Optional Optional Optional Optional Optional
Environment Friendly Refrigerant - - - - - -
Fire Alarm Function - - - - - -
Forced Operation O O O O O O
Group Control O O O O O O
High Ceiling Operation O O O O O O
Hot Start - O - O - O
Jet Cool O O O O O O
Low Ambient Control Optional Optional Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O O O
Restart Delay (3-minutes) O O O O O O
Self Diagnosis O O O O O O
Sleep Mode - - - - - -
Soft Dry Operation O O O O O O
Space Control O O - - O O
Swirl Swing O O - - O O
Tele Control Accessory Accessory Accessory Accessory Accessory Accessory
Temperature Control O O O O O O
Test Function O O O O O O
Time Delay Safety Function O O O O O O
Timer (weekly) O O O O O O
Timer (24 hr On/Off) O O O O O O
Two Thermistor Control O O O O O O
Wired LCD Remote Controller O O O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory Accessory Accessory
Zero Standby Power O O O O O O
Zone Control - - - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
Ceiling Cassette
Function
LT-D6020CL/CA LT-D6020HL/HA LT-C602DLA(C)0 LT-H602DLA(C)0
Air Discharge outlet 4 4 4 4
Airflow Direction control (left & right) - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - O - O
Auto Elevation Grille - - - -
Auto Operation O O O O
Auto Restart Operation O O O O
Auto Swing O O O O
Central Control Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - -
Child Lock Function O O O O
Cooling & Fan Operation O - O -
Coolling, Heating & Fan Operation - O - O
Defrost / Deicing - O - O
Deodorizing Filter - - - -
Drain Pump O O O O
E.S.P. Control - - - -
Electric Heater - - - -
Energy Saving Gold Fin Optional Optional Optional Optional
Environment Friendly Refrigerant - - - -
Fire Alarm Function - - - -
Forced Operation O O O O
Group Control O O O O
High Ceiling Operation O O O O
Hot Start - O - O
Jet Cool O O O O
Low Ambient Control Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O
Restart Delay (3-minutes) O O O O
Self Diagnosis O O O O
Sleep Mode - - - -
Soft Dry Operation O O O O
Space Control - - O O
Swirl Swing - - O O
Tele Control Accessory Accessory Accessory Accessory
Temperature Control O O O O
Test Function O O O O
Time Delay Safety Function O O O O
Timer (weekly) O O O O
Timer (24 hr On/Off) O O O O
Two Thermistor Control O O O O
Wired LCD Remote Controller O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory
Zero Standby Power O O O O
Zone Control - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
16 Ceiling Cassette(60Hz)
4. List of Functions
Ceiling Cassette
Function
LT-C60BDLA(C)0 LT-H60BDLA(C)0 LT-C60BDLA(C)1 LT-H60BDLA(C)1
Air Discharge outlet 4 4 4 4
Airflow Direction control (left & right) - - - -
Airflow Direction control (up & down) Auto Auto Auto Auto
Airflow Steps(Fan / Cool /Heat) 3/4/- 3/4/3 3/4/- 3/4/3
Auto Changeover - O - O
Auto Elevation Grille - - - -
Auto Operation O O O O
Auto Restart Operation O O O O
Auto Swing O O O O
Central Control Accessory Accessory Accessory Accessory
CHAOS wind (Auto wind) - - - -
Child Lock Function O O O O
Cooling & Fan Operation O - O -
Coolling, Heating & Fan Operation - O - O
Defrost / Deicing - O - O
Deodorizing Filter - - - -
Drain Pump O O O O
E.S.P. Control - - - -
Electric Heater - - - -
Energy Saving Gold Fin Optional Optional Optional Optional
Environment Friendly Refrigerant - - - -
Fire Alarm Function - - - -
Forced Operation O O O O
Group Control O O O O
High Ceiling Operation O O O O
Hot Start - O - O
Jet Cool O O O O
Low Ambient Control Optional Optional Optional Optional
Plasma Air Purifier Optional Optional Optional Optional
Prefilter(Washable / Anti-fungus) O O O O
Restart Delay (3-minutes) O O O O
Self Diagnosis O O O O
Sleep Mode - - - -
Soft Dry Operation O O O O
Space Control - - O O
Swirl Swing - - O O
Tele Control Accessory Accessory Accessory Accessory
Temperature Control O O O O
Test Function O O O O
Time Delay Safety Function O O O O
Timer (weekly) O O O O
Timer (24 hr On/Off) O O O O
Two Thermistor Control O O O O
Wired LCD Remote Controller O O O O
Wireless Remote Controller Accessory Accessory Accessory Accessory
Zero Standby Power O O O O
Zone Control - - - -
Notes :
• O : Basic
• Optional : Factory-Installed
• Accessory : Field-Installed
• - : Not available on this system
Power Factor % 98 98 98 98
kcal/h W(W/W) 3.4(3.95) 2.3(2.68) 2.3(2.68) 2.39(2.77)
E.E.R Cooling
Btu/h W 13.5 9.14 9.14 9.47
W/W(kcal/h W) - - - 2.77(2.39)
C.O.P Heating
Btu/h W - - - 9.47
Setting temperature range(cool/heat) °C 18~30 18~30 18~30 18~30/16~30
Dehumidification Rate l/h 1.5 1.9 1.9 1.9
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 700(24.7), R22 1,050(37.03),R22 1,050(37.03),R22 1,910(67.37), R22
Output W 19 22.4 22.4 22.4
Model AMR-023B7 IC-9630LGAC IC-9630LGAC IC-9630LGAC
No. of Poles 4 6 6 6
Indoor fan motor
Input W 50 90 90 90
Running Current A 0.56 0.38 0.38 0.38
Capacitor µF/Vac 0.9 / 400 2.5 / 440 2.5 / 440 2.5 / 440
Type Cross Flow Fan Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/102(4.0) 1/13.0(330) 1/13.0(330) 1/13.0(330)
Cooling(H/M/L) rpm 1000 / 900 / 800 720 / 670 / 620 720 / 670 / 620 720 / 670 / 620
Indoor Fan RPM
Indoor
Output W 22.4 60 60 60
Model IC-9625LGOD IC-1640LGFB IC-1640LGFB IC-1640LGFB
No. of Poles 6 6 6 6
Outdoor fan motor
Input W 77 165 165 165
Running Current A 0.3 0.72 0.72 0.72
Capacitor µF/Vac 1.5 / 370 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 1/15.7(400) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge Side Discharge
Speed rpm 700 800 800 800
Air Circulation Outdoor CMM(CFM) 25(883) 50(1766) 50(1766) 50(1766)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 46 55 55 55
Liquid inch(mm) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35)
SVC Valve
Gas inch(mm) 1 / 2 (12.7) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88)
Dimensions (W*H*D) Outdoor inch(mm) 30.3*21.2*9.6(770*540*245) 34.2*25.8*12.6(870*655*320) 34.2*25.8*12.6(870*655*320) 34.2*25.8*12.6(870*655*320)
Net Weight Outdoor kg(lbs) 31 (68.3) 62(136.6) 62(136.6) 62(136.6)
Power supply Cable(With Earth Cable) No.* mm2 3 * 2.5 3 * 2.5 3 * 2.5 3 * 2.5
Conncecting Cable(With Earth Cable) No.* mm2 4 * 0.75 4 * 0.75 4 * 0.75 5 * 0.75
Liquid Side inch(mm) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35)
Connecting Tube Gas Side inch(mm) 1 / 2 (12.7) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88)
(Ø Socket Flare) Length, std m 5 7.5 7.5 7.5
Other
18 Ceiling Cassette(60Hz)
5. Specifications
Power Factor % 98 95 95 95
kcal/h W(W/W) 2.39(2.77) 2.41(2.81) 2.41(2.81) 2.41(2.81)
E.E.R Cooling
Btu/h W 9.47 9.6 9.6 9.6
W/W(kcal/h W) 2.77(2.39) - - 2.76(2.37)
C.O.P Heating
Btu/h W 9.47 - - 9.41
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/- 18~30/16~30
Dehumidification Rate l/h 1.9 3.3 3.3 3.3
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 1,910(67.37), R22 1,950(68.78),R22 1,950(68.78),R22 1,830(64.55),R22
Output W 22.4 25 25 25
Model IC-9630LGAC IC-9630LGAD IC-9630LGAD IC-9630LGAD
No. of Poles 6 6 6 6
Indoor fan motor
Input W 90 100 100 100
Running Current A 0.38 0.41 0.41 0.41
Capacitor µF/Vac 2.5 / 440 2.5 / 440 2.5 / 440 2.5 / 440
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/13.0(330) 1/13.0(330) 1/13.0(330) 1/13.0(330)
Cooling(H/M/L) rpm 720 / 670 / 620 800 / 750 / 700 800 / 750 / 700 800 / 750 / 700
Indoor Fan RPM
Indoor
Output W 60 90 90 90
Model IC-1640LGFB AMR071B9 AMR071B9 AMR071B9
No. of Poles 6 6 6 6
Outdoor fan motor
Input W 165 168 168 168
Running Current A 0.72 0.72 0.72 0.72
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge Side Discharge
Speed rpm 800 900 900 900
Air Circulation Outdoor CMM(CFM) 50(1766) 52(1836) 52(1836) 52(1836)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 55 57 57 57
Liquid inch(mm) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35)
SVC Valve
Gas inch(mm) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88)
Dimensions (W*H*D) Outdoor inch(mm) 34.2*25.8*12.6(870*655*320) 34.2*25.8*12.6(870*655*320) 34.2*25.8*12.6(870*655*320) 34.2*25.8*12.6(870*655*320)
Net Weight Outdoor kg(lbs) 62(136.6) 62(136.6) 62(136.6) 62(136.6)
Power supply Cable(With Earth Cable) No.* mm2 3 * 2.5 3 * 2.5 3 * 2.5 3 * 2.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 0.75 4 * 0.75 4 * 0.75 5 * 0.75
Liquid Side inch(mm) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35)
Connecting Tube Gas Side inch(mm) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88)
(Ø Socket Flare) Length, std m 7.5 7.5 7.5 7.5
Other
Power Factor % 95 98 98
kcal/h W(W/W) 2.41(2.81) 2.54(2.95) 2.54(2.95)
E.E.R Cooling
Btu/h W 9.6 10.07 10.07
W/W(kcal/h W) 2.76(2.37) - 2.87(2.47)
C.O.P Heating
Btu/h W 9.41 - 9.8
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/16~30
Dehumidification Rate l/h 3.3 3.5 3.5
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 1,830(64.55),R22 1750(61.7), R22 1750(61.7), R22
Output W 25 51 51
Model IC-9630LGAD IC-9635LGPA IC-9640LGPT
No. of Poles 6 6 6
Indoor fan motor
Input W 100 180 180
Running Current A 0.41 0.85 0.85
Capacitor µF/Vac 2.5 / 440 4/440 4/440
Type Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/13.0(330) 1/382(15) 1/382(15)
Cooling(H/M/L) rpm 800 / 750 / 700 660/610/560 660/590/530
Indoor Fan RPM
Indoor
Output W 90 120 90
Model AMR071B9 IC-1640LGGF IC-1640LGGE
No. of Poles 6 6 6
Outdoor fan motor
Input W 168 218 193
Running Current A 0.72 0.65 0.65
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge
Speed rpm 900 1040 980
Air Circulation Outdoor CMM(CFM) 52(1836) 58(2,048) 58(2,048)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 57 58 58
Liquid inch(mm) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35)
SVC Valve
Gas inch(mm) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88)
Dimensions (W*H*D) Outdoor inch(mm) 34.2*25.8*12.6(870*655*320) 34.2*31.5*12.6(870*800*320) 34.2*31.5*12.6(870*800*320)
Net Weight Outdoor kg(lbs) 62(136.6) 66 (145.5) 66 (145.5)
Power supply Cable(With Earth Cable) No.* mm2 3 * 2.5 3 * 2.5 3 * 2.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 0.75 4 * 0.75 5 * 0.75
Liquid Side inch(mm) 1 / 4 (6.35) 1 / 4 (6.35) 1 / 4 (6.35)
Connecting Tube Gas Side inch(mm) 5 / 8 (15.88) 5 / 8 (15.88) 5 / 8 (15.88)
(Ø Socket Flare) Length, std m 7.5 5 5
Other
20 Ceiling Cassette(60Hz)
5. Specifications
Power Factor % 95 95 95
kcal/h W(W/W) 2.56(2.97) 2.56(2.97) 2.56(2.97)
E.E.R Cooling
Btu/h W 10.14 10.14 10.14
W/W(kcal/h W) - - 3.52(3.02)
C.O.P Heating
Btu/h W - - 12
Setting temperature range(cool/heat) °C 18~30/- 18~30/- 18~30/16~30
Dehumidification Rate l/h 4.5 4.5 4.5
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 1,950(68.78), R22 1,950(68.78), R22 1,950(68.78), R22
Output W 56.1 56.1 56.1
Model IC-14640LGPR IC-14640LGPR IC-14640LGPR
No. of Poles 6 6 6
Indoor fan motor
Input W 190 190 190
Running Current A 0.88 0.88 0.88
Capacitor µF/Vac 6 / 400 6 / 400 6 / 400
Type Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/460(18.1) 1/460(18.1) 1/460(18.1)
Cooling(H/M/L) rpm 560 / 520 /480 560 / 520 /480 560 / 520 /480
Indoor Fan RPM
Indoor
Power Factor % 95 93 93 93
kcal/h W(W/W) 2.56(2.97) 2.18(2.54) 2.18(2.54) 2.18(2.54)
E.E.R Cooling
Btu/h W 10.14 8.66 8.66 8.66
W/W(kcal/h W) 3.52(3.02) - - 2.97(2.55)
C.O.P Heating
Btu/h W 12 - - 10.12
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/- 18~30/16~30
Dehumidification Rate l/h 4.5 5 5 5
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 1,950(68.78), R22 4,240(149.6),R22 4,240(149.6),R22 4,240(149.6),R22
Output W 56.1 56.1 56.1 56.1
Model IC-14640LGPR IC-14640LGPR IC-14640LGPR IC-14640LGPR
No. of Poles 6 6 6 6
Indoor fan motor
Input W 190 190 190 190
Running Current A 0.88 0.88 0.88 0.88
Capacitor µF/Vac 6 / 400 6 / 400 6 / 400 6 / 400
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/460(18.1) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Cooling(H/M/L) rpm 560 / 520 /480 570 / 530 / 490 570 / 530 / 490 570 / 530 / 490
Indoor Fan RPM
Indoor
Output W 125 90 90 90
Model ARE306B02 AMR071B9 AMR071B9 AMR071B9
No. of Poles 6 6 6 6
Outdoor fan motor
Input W 198 168 168 168
Running Current A 0.9 0.72 0.72 0.72
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 1/20.7(526) 2/18.1(460) 2/18.1(460) 2/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge Side Discharge
Speed rpm 780 900*2 900*2 900*2
Air Circulation Outdoor CMM(CFM) 58(2048) 105(3,708) 105(3,708) 105(3,708)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 55 60 60 60
Liquid inch(mm) 1 / 4 (6.35) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52)
SVC Valve
Gas inch(mm) 5 / 8 (15.88) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
Dimensions (W*H*D) Outdoor inch(mm) 34.2*31.5*12.6(870*800*320) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370)
Net Weight Outdoor kg(lbs) 66(145.5) 93(205.0) 93(205.0) 93(205.0)
Power supply Cable(With Earth Cable) No.* mm2 3 * 2.5 3*3 3*3 3*3
Conncecting Cable(With Earth Cable) No.* mm2 5 * 0.75 4 * 1.25 4 * 1.25 5 * 1.25
Liquid Side inch(mm) 1 / 4 (6.35) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52)
Connecting Tube Gas Side inch(mm) 5 / 8 (15.88) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
(Ø Socket Flare) Length, std m 7.5 7.5 7.5 7.5
Other
22 Ceiling Cassette(60Hz)
5. Specifications
Power Factor % 93 98 98 98
kcal/h W(W/W) 2.18(2.54) 2.42(2.81) 2.42(2.81) 2.42(2.81)
E.E.R Cooling
Btu/h W 8.66 9.6 9.6 9.6
W/W(kcal/h W) 2.97(2.55) - - 3.13(2.69)
C.O.P Heating
Btu/h W 10.12 - - 10.67
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/- 18~30/16~30
Dehumidification Rate l/h 5 5.5 5.5 5.5
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 4,240(149.6),R22 4,300(151.7),R22 4,300(151.7),R22 4,300(151.7),R22
Output W 56.1 58.5 58.5 58.5
Model IC-14640LGPR IC-14640LGPK IC-14640LGPK IC-14640LGPK
No. of Poles 6 6 6 6
Indoor fan motor
Input W 190 240 240 240
Running Current A 0.88 1.1 1.1 1.1
Capacitor µF/Vac 6 / 400 6 / 400 6 / 400 6 / 400
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Cooling(H/M/L) rpm 570 / 530 / 490 600 / 555 / 520 600 / 555 / 520 600 / 555 / 520
Indoor Fan RPM
Indoor
Output W 90 90 90 90
Model AMR071B9 AMR071B9 AMR071B9 AMR071B9
No. of Poles 6 6 6 6
Outdoor fan motor
Input W 168 168 168 168
Running Current A 0.72 0.72 0.72 0.72
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 2/18.1(460) 2/18.1(460) 2/18.1(460) 2/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge Side Discharge
Speed rpm 900*2 900*2 900*2 900*2
Air Circulation Outdoor CMM(CFM) 105(3,708) 105(3,708) 105(3,708) 105(3,708)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 60 62 62 62
Liquid inch(mm) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52)
SVC Valve
Gas inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
Dimensions (W*H*D) Outdoor inch(mm) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370)
Net Weight Outdoor kg(lbs) 93(205.0) 93(205.0) 93(205.0) 93(205.0)
Power supply Cable(With Earth Cable) No.* mm2 3*3 3 * 3.5 3 * 3.5 3 * 3.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 1.25 4 * 1.25 4 * 1.25 5 * 1.25
Liquid Side inch(mm) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52)
Connecting Tube Gas Side inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
(Ø Socket Flare) Length, std m 7.5 7.5 7.5 7.5
Other
Power Factor % 98 93 93 98
kcal/h W(W/W) 2.42(2.81) 2.42(2.81) 2.42(2.81) 2.42(2.81)
E.E.R Cooling
Btu/h W 9.6 9.6 9.6 9.6
W/W(kcal/h W) 3.13(2.69) - - 3.03(2.60)
C.O.P Heating
Btu/h W 10.67 - - 10.32
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/- 18~30/16~30
Dehumidification Rate l/h 5.5 5.5 5.5 5.5
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 4,300(151.7),R22 4,600(162.3),R22 4,600(162.3),R22 4,600(162.3),R22
Output W 58.5 58.5 58.5 58.5
Model IC-14640LGPK IC-14640LGPK IC-14640LGPK IC-14640LGPK
No. of Poles 6 6 6 6
Indoor fan motor
Input W 240 240 240 240
Running Current A 1.1 1.1 1.1 1.1
Capacitor µF/Vac 6 / 400 6 / 400 6 / 400 6 / 400
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Cooling(H/M/L) rpm 600 / 555 / 520 600 / 555 / 520 600 / 555 / 520 600 / 555 / 520
Indoor Fan RPM
Indoor
Output W 90 90 90 90
Model AMR071B9 AMR071B9 AMR071B9 AMR071B9
No. of Poles 6 6 6 6
Outdoor fan motor
Input W 168 168 168 168
Running Current A 0.72 0.82 0.82 0.82
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 2/18.1(460) 2/18.1(460) 2/18.1(460) 2/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge Side Discharge
Speed rpm 900*2 900 900 900
Air Circulation Outdoor CMM(CFM) 105(3,708) 105(3708) 105(3708) 105(3708)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 62 62 62 62
Liquid inch(mm) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52)
SVC Valve
Gas inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
Dimensions (W*H*D) Outdoor inch(mm) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370)
Net Weight Outdoor kg(lbs) 93(205.0) 93(205.0) 93(205.0) 93(205.0)
Power supply Cable(With Earth Cable) No.* mm2 3 * 3.5 4 * 3.5 4 * 3.5 4 * 3.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 1.25 4 * 1.25 4 * 1.25 5 * 1.25
Liquid Side inch(mm) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52) 3 / 8 (9.52)
Connecting Tube Gas Side inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
(Ø Socket Flare) Length, std m 7.5 7.5 7.5 7.5
Other
24 Ceiling Cassette(60Hz)
5. Specifications
Power Factor % 98 90 90 90
kcal/h W(W/W) 2.42(2.81) 2.42(2.82) 2.42(2.82) 2.42(2.82)
E.E.R Cooling
Btu/h W 9.6 9.6 9.6 9.6
W/W(kcal/h W) 3.03(2.60) - - 3.2(2.75)
C.O.P Heating
Btu/h W 10.32 - - 10.91
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/- 18~30/16~30
Dehumidification Rate l/h 5.5 6.3 6.3 6.3
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 4,600(162.3),R22 5,185(182.9),R22 5,185(182.9),R22 5,185(182.9),R22
Output W 58.5 94.1 94.1 94.1
Model IC-14640LGPK IC-14640LGPQ IC-14640LGPQ IC-14640LGPQ
No. of Poles 6 6 6 6
Indoor fan motor
Input W 240 260 260 260
Running Current A 1.1 1.21 1.21 1.21
Capacitor µF/Vac 6 / 400 6 / 400 6 / 400 6 / 400
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Cooling(H/M/L) rpm 600 / 555 / 520 720 / 650 / 570 720 / 650 / 570 720 / 650 / 570
Indoor Fan RPM
Indoor
Output W 90 90 90 90
Model AMR071B9 AMR071B9 AMR071B9 AMR071B9
No. of Poles 6 6 6 6
Outdoor fan motor
Input W 168 168 168 168
Running Current A 0.82 0.72 0.72 0.72
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 2/18.1(460) 2 / 18.1(460) 2 / 18.1(460) 2 / 18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge Side Discharge
Speed rpm 900 900*2 900*2 900*2
Air Circulation Outdoor CMM(CFM) 105(3708) 105(3708) 105(3708) 105(3708)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 62 62 62 62
Liquid inch(mm) 3 / 8 (9.52) 1 / 2 (12.7) 1 / 2 (12.7) 1 / 2 (12.7)
SVC Valve
Gas inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
Dimensions (W*H*D) Outdoor inch(mm) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370)
Net Weight Outdoor kg(lbs) 93(205.0) 93(205.0) 93(205.0) 93(205.0)
Power supply Cable(With Earth Cable) No.* mm2 4 * 3.5 3 * 3.5 3 * 3.5 3 * 3.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 1.25 4 * 1.25 4 * 1.25 5 * 1.25
Liquid Side inch(mm) 1 / 2 (12.7) 1 / 2 (12.7) 1 / 2 (12.7) 1 / 2 (12.7)
Connecting Tube Gas Side inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
(Ø Socket Flare) Length, std m 7.5 7.5 7.5 7.5
Other
Power Factor % 90 92 92
kcal/h W(W/W) 2.42(2.82) 2.56(2.98) 2.56(2.98)
E.E.R Cooling
Btu/h W 9.6 10.17 10.17
W/W(kcal/h W) 3.2(2.75) - -
C.O.P Heating
Btu/h W 10.91 - -
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/- 18~30/-
Dehumidification Rate l/h 6.3 6.3 6.3
Refrigerant Control Capillary Tube Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 5,185(182.9),R22 4,700(165.8),R22 4,700(165.8),R22
Output W 94.1 94.1 94.1
Model IC-14640LGPQ IC-14640LGPQ IC-14640LGPQ
No. of Poles 6 6 6
Indoor fan motor
Input W 260 260 260
Running Current A 1.21 1.21 1.21
Capacitor µF/Vac 6 / 400 6 / 400 6 / 400
Type Turbo Fan Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460) 1/18.1(460)
Cooling(H/M/L) rpm 720 / 650 / 570 680 / 630 / 580 680 / 630 / 580
Indoor Fan RPM
Indoor
Output W 90 90 90
Model AMR071B9 AMR071B9 AMR071B9
No. of Poles 6 6 6
Outdoor fan motor
Input W 168 168 168
Running Current A 0.72 0.82 0.82
Capacitor µF/Vac 6 / 370 6 / 370 6 / 370
Type Propeller Propeller Propeller
No. Used/diameter EA/inch(mm) 2 / 18.1(460) 2/18.1(460) 2/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge Side Discharge
Speed rpm 900*2 900 900
Air Circulation Outdoor CMM(CFM) 105(3708) 105(3708) 105(3708)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 62 62 62
Liquid inch(mm) 1 / 2 (12.7) 1 / 2 (12.7) 1 / 2 (12.7)
SVC Valve
Gas inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
Dimensions (W*H*D) Outdoor inch(mm) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370)
Net Weight Outdoor kg(lbs) 93(205.0) 93(205.0) 93(205.0)
Power supply Cable(With Earth Cable) No.* mm2 3 * 3.5 4 * 3.5 4 * 3.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 1.25 4 * 1.25 4 * 1.25
Liquid Side inch(mm) 1 / 2 (12.7) 1 / 2 (12.7) 1 / 2 (12.7)
Connecting Tube Gas Side inch(mm) 3 / 4 (19.05) 3 / 4 (19.05) 3 / 4 (19.05)
(Ø Socket Flare) Length, std m 7.5 7.5 7.5
Other
26 Ceiling Cassette(60Hz)
5. Specifications
Power Factor % 92 92
kcal/h W(W/W) 2.56(2.98) 2.56(2.98)
E.E.R Cooling
Btu/h W 10.17 10.17
W/W(kcal/h W) 3.14(2.70) 3.14(2.70)
C.O.P Heating
Btu/h W 10.72 10.72
Setting temperature range(cool/heat) °C 18~30/16~30 18~30/16~30
Dehumidification Rate l/h 6.3 6.3
Refrigerant Control Capillary Tube Capillary Tube
Refrigerant charge g(oz), type 4,700(165.8),R22 4,700(165.8),R22
Output W 94.1 94.1
Model IC-14640LGPQ IC-14640LGPQ
No. of Poles 6 6
Indoor fan motor
Input W 260 260
Running Current A 1.21 1.21
Capacitor µF/Vac 6 / 400 6 / 400
Type Turbo Fan Turbo Fan
Indoor Fan
No. Used / Diameter EA/inch(mm) 1/18.1(460) 1/18.1(460)
Cooling(H/M/L) rpm 680 / 630 / 580 680 / 630 / 580
Indoor Fan RPM
Indoor
Output W 90 90
Model AMR071B9 AMR071B9
No. of Poles 6 6
Outdoor fan motor
Input W 168 168
Running Current A 0.82 0.82
Capacitor µF/Vac 6 / 370 6 / 370
Type Propeller Propeller
No. Used/diameter EA/inch(mm) 2/18.1(460) 2/18.1(460)
Outdoor Fan
Discharge Side/Top Side Discharge Side Discharge
Speed rpm 900 900
Air Circulation Outdoor CMM(CFM) 105(3708) 105(3708)
Noise Level(Sound Press,1m) Outdoor dB(A)±3 62 62
Liquid inch(mm) 1 / 2 (12.7) 1 / 2 (12.7)
SVC Valve
Gas inch(mm) 3 / 4 (19.05) 3 / 4 (19.05)
Dimensions (W*H*D) Outdoor inch(mm) 35.4*48.2*14.6(900*1225*370) 35.4*48.2*14.6(900*1225*370)
Net Weight Outdoor kg(lbs) 93(205.0) 93(205.0)
Power supply Cable(With Earth Cable) No.* mm2 4 * 3.5 4 * 3.5
Conncecting Cable(With Earth Cable) No.* mm2 5 * 1.25 5 * 1.25
Liquid Side inch(mm) 1 / 2 (12.7) 1 / 2 (12.7)
Connecting Tube Gas Side inch(mm) 3 / 4 (19.05) 3 / 4 (19.05)
(Ø Socket Flare) Length, std m 7.5 7.5
Other
30.8
1 7 846
3 2
50
328.4
390
42.7
91.6
130
164
155
Ø55
37
97.7
116.3
141.8
180
1050
694.5
5
480
28 Ceiling Cassette(60Hz)
6. Dimensional Drawings
269
75
Unit:mm
670 570
450
5
570
521
670
40
6 4
1
30
2
110 110
269
90
90
190.5
30
160
120.4
52
(unit : mm)
269
75
Unit:mm
670 570
5
450
570
521
670
6 40
4
1
30
2
110 110
269
90
90
190.5
29
160
120.4
52
(unit : mm)
30 Ceiling Cassette(60Hz)
6. Dimensional Drawings
66
292
66
850 Unit:mm
5
744
658
850
572
744
6 70
4
1
2
117
110 110
29
292
90
90
150
212
192
54
(unit : mm)
45 785(Hanging bolt) 45
5
Unit:mm
840
678
950
785
840
6
4
30
40
1
2
30
110 110
290
210.5
52 180
90
90
140
(unit : mm)
32 Ceiling Cassette(60Hz)
6. Dimensional Drawings
45 785(Hanging bolt) 45
5
Unit:mm
840
678
950
785
840
4
29
40
1
2
30
110 110
290
210.5
52 180
90
90
140
(unit : mm)
W L2
L1
D
L3
H
Gas side
(3-way valve)
L5
Liquid side
L4
(2-way valve)
W mm 770
H mm 540
D mm 245
L1 mm 287
L2 mm 64
L3 mm 518
L4 mm 10
L5 mm 100
34 Ceiling Cassette(60Hz)
6. Dimensional Drawings
W
L3
L1
D
L2
L4
H
Liquid side
2-way valve
L7 L6 L8 L9
L5
Model No.
LT-C302F, LT-H302F
LT-E18/2420
Dim LT-C362D, LT-H362D
W mm 870 870
H mm 655 800
D mm 320 320
L1 mm 370 370
L2 mm 25 25
L3 mm 340 340
L4 mm 630 775
L5 mm 25 25
L6 mm 546 546
L7 mm 162 162
L8 mm 162 162
L9 mm 54 54
L10 mm 74.5 74.5
L11 mm 79 79
L3 W
L1
D
L2
H
L4
Liquid side
3-way valve
L10 L11
Gas side
3-way valve
L9
L5
L7 L6 L8
W mm 900
H mm 1,225
D mm 370
L1 mm 460
L2 mm 45
L3 mm 410
L4 mm 1,135
L5 mm 90
L6 mm 550
L7 mm 175
L8 mm 175
L9 mm 112
L10 mm 120
L11 mm 83
36 Ceiling Cassette(60Hz)
7. Wiring Diagrams
ROOM PIPE
SENSOR SENSOR FLOAT S/W
GN/YL
FAN COMP
CN-ROOM CN-PIPE CN-FLOAT
CAPACITOR MOTOR C S R
CN-CC
BR YL MAIN PCB ASSY
BR
OLP
BK CN-MOTOR
INDOOR
CN-STEP/M
RD
RD
BR
YL
BL
BL
MOTOR OR
GN/YL
STEP
MOTOR
PTC
CN-D/PUMP
BL
BL
RD
RD
BR
BL
YL
BL
REMOTE
DRAIN CONTROL CAPACITOR
CN-REMO
PUMP
F C H
GN/YL
FUSE T3.15A
DISPLAY PCB ASSY
BL
BR
CN-DISP
CN-POWER BL BL
TB
BL
(OPTIONAL)
DOOR S/W
WH
RD
BK
4 8 1 POWER
RELAY
CLEANER
RD 2 6 0
H.V. B
BR
AIR
BK
BR BL
BL
RD
GN/YL
RD
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
BL CAPACITOR YL
TEMP.
BR R
INDOOR DRAIN STEP
MOTOR PUMP MOTOR RD H C F OR FAN
YL COMP S MOTOR
BK
OR
BK
BL
BL
C
BR
BL
FUSE T3.15A
3(L) 4(N)
BR
PIPE
THERMISTOR POWER 4 8 1
BL
RELAY 2 6 0
TO OUTDOOR UNIT
GN/YL
COMP
BR FUSE 5A
BL
RD
BL FUSE 5A
5
BR
BL
BL
RD
BK
REMOTE
GN/YL
GN/YL
CN - DISP CONTROL
7
WH
RD
(OPTION)
BK
DOOR S/W
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB 1(L) 2(N) 3(L) 4(N) 5 6 7 8
AIR
BLOCK
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A30086Z
3854A20031Q
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
BL CAPACITOR YL
R
GN/YL
THERMISTOR
BR
COMP S MOTOR
TEMP.
INDOOR DRAIN STEP STEP STEP STEP C
BK
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR
YL
BR
BL
OR
BK
BL
FUSE T3.15A
POWER 4 8 1
3 (L ) 4 (N )
BL BL WH WH PIPE
THERMISTOR RELAY 2 6 0
TO OUTDOOR UNIT
COMP
BR FUSE 5A
BL
BL FUSE 5A
BR
BL
5
BR
6
BL
RD
BK
REMOTE
CN - DISP
GN/YL
GN/YL
CONTROL
7
WH
RD
(OPTION)
BK
DOOR S/W
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
1(L) 2(N) 3(L) 4(N) 5 6 7 8
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20031Q
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
BL CAPACITOR YL
R
RD H C F OR FAN
COMP S
THERMISTOR
BR BK MOTOR
C
TEMP.
PUMP MOTOR
BL
YL
OR
BK
BL
BL
POWER 4 8 1
FUSE T3.15A
3(L) 4(N)
BR
RELAY 2 6 0 REVERSING
PIPE
BL THERMISTOR VALVE
RD
TO OUTDOOR UNIT
GN/YL
BR FUSE 5A
OUT FAN
BL
COMP
4 WAY
BL FUSE 5A
BR
BL
RD TB2
5
BR
BL
BK
BK
FLOAT S/W
BK
6
GN/YL
GN/YL
REMOTE
YL CN - DISP CONTROL
7
WH
RD
(OPTIONAL EXTRA)
BK
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20072A 3854A20031N
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
38 Ceiling Cassette(60Hz)
7. Wiring Diagrams
BL CAPACITOR YL
R
RD H C F OR FAN
COMP S MOTOR
C
BK
GN/YL
BR
THERMISTOR
BL
BR
TEMP.
INDOOR DRAIN STEP STEP STEP STEP
MOTOR PUMP
YL
MOTOR MOTOR MOTOR MOTOR
POWER 4 8 1
OR
BK
RELAY
BL
2 6 0 REVERSING
FUSE T3.15A
3(L) 4(N)
BL BL WH WH
VALVE
PIPE
RD
THERMISTOR
TO OUTDOOR UNIT
BR FUSE 5A
BL
BL FUSE 5A
BR
BL
COMP
TB2
BR
5
BL
BK
BK
FLOAT S/W
6
GN/YL
GN/YL
REMOTE
CN - DISP CONTROL
7
WH
RD
(OPTION)
BK
TERMINAL 5 7
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20031N
THERMISTOR
BR
TEMP.
BL
BL
MOTOR OR
RD H C
COMP S HOUSING
3(L) 4(N)
BR FUSE T3.15A BR
C
BL BK
PIPE
BL THERMISTOR
TO OUTDOOR UNIT
POWER 4 8 1 pipe TH
GN/YL D.P
RELAY 2 6 0
OUT FAN
REVERSING
COMP
RD
VALVE NO NC NO NC
L1 TNS
RD
L2
5
BR FUSE 5A
BL
BL FUSE 5A
FLOAT S/W L3 L4
BR
BL
YL
6
WH
BL
TB
GN/YL
REMOTE
GN/YL
CN - DISP CONTROL BK
7
WH
RD
BK
BL
DOOR S/W
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20126K 3854A20077V
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
YL
BL CAPACITOR FAN
GN/YL
THERMISTOR
RD H C
BR COMP S
TEMP.
INDOOR DRAIN STEP STEP STEP STEP BR HOUSING
MOTOR PUMP C
YL
MOTOR MOTOR MOTOR MOTOR BL BK
OR
BK
BL
FUSE T3.15A
4 8 1
3(L) 4(N)
POWER pipe TH
BL BL WH WH PIPE D.P
THERMISTOR
RELAY 2 6 0 REVERSING
RD
VALVE NO NC NO NC
TNS
TO OUTDOOR UNIT
L1
COMP
L2
BR FUSE 5A
BL
BL FUSE 5A
L3 L4
BR
BL
5
FLOAT S/W WH
BL
TB
6
GN/YL
GN/YL
REMOTE
BK
CN - DISP CONTROL
7
BL
WH
RD
(OPTION)
BK
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20077V
BL
R
RD H C YL
COMP S FAN
GN/YL
C BR MOTOR OR
THERMISTOR
BL
BR
TEMP.
4 8 1 POWER
BK
BL
FUSE T3.15A
BK 2 6 0 RELAY
3(L) 4(N)
RD
BL BL WH WH PIPE 63H
THERMISTOR
BK BK
TO OUTDOOR UNIT
COMP
BR FUSE 5A
BL
5
BL FUSE 5A
BR
FLOAT S/W
BL
6
BL
REMOTE
GN/YL
CN - DISP CONTROL
7
GN/YL
WH
RD
(OPTION)
BK
DOOR S/W
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
1(L) 2(N) 3(L) 4(N) 5 6 7 8
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20307A
3854A20125F
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
40 Ceiling Cassette(60Hz)
7. Wiring Diagrams
BL
R
GN/YL
RD H C YL
COMP S FAN
THERMISTOR
C BR MOTOR OR
BR BL
TEMP.
INDOOR DRAIN STEP STEP STEP STEP
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR
YL
SV
BK OR
OR
BK
BL
4 8 1 POWER
FUSE T3.15A
3(L) 4(N)
BL BL WH WH
BK 2 6 0 RELAY
PIPE
RD
63H PIPE TH
THERMISTOR D.P
BK BK
TO OUTDOOR UNIT
NO NC NO NC
20 TNS
L1
SV
COMP
L2
BR FUSE 5A
BL
BL FUSE 5A
BR
5
L3 L4
BR
BL
FLOAT S/W
WH
BL
6
TB
GN/YL
GN/YL
REMOTE BK
CN - DISP CONTROL
7
WH
RD
(OPTION)
BK
BL
DOOR S/W
TERMINAL
1(L) 2(N) 3(L) 4(N) 5 6 7 8
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
TERMINAL
POWER BLOCK
TO INDOOR UNIT
INPUT
3854A20126V
3854A20125E
Notes:
COMP COMPRESSOR BL BLUE BK BLACK
BR BROWN OR ORANGE RD RED
WH WHITE YL YELLOW GN/YL GREEN/YELLOW
F1
BK BK
BK
GN/YL
WH
THERMISTOR
WH TB
GN/YL
WH
BR
TEMP.
BL
BL
A1
FUSE T3.15A T1 T2
BR
1
PIPE
THERMISTOR 1Ø, 220V, 60Hz BKBK
BL BK BK
2
POWER SUPPLY
TO OUTDOOR UNIT
OR BK
RD
SV
COMP
3
CAPACITOR BL
F C H
To the Indoor unit
4
2 BL
S RD
GN/YL REMOTE YL OR BK R C 3
CN - DISP CONTROL 4
WH
RD
BK
CM 5
FMo GN/YL
DOOR S/W
TERMINAL 6
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
3854A20072P
P/NO : 3854A20203M
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
F1
BK BK
BK
WH
WH TB
GN/YL
WH
BK
WH
TM 1 2 3 L1 L2
52C A2
L N 63H
GN/YL
THERMISTOR
BR A1
TEMP.
T1 T2
INDOOR DRAIN STEP STEP STEP STEP
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR
YL
1Ø, 220V, 60Hz
OR
BK
BL
BK BKBK BK
FUSE T3.15A POWER SUPPLY
3 (L ) 4 (N )
BL BL WH WH OR BK
PIPE
THERMISTOR SV
TO OUTDOOR UNIT
CAPACITOR BL
F C H
COMP
BK BR
FLOAT S/W 1
BL RD BR WH BL
2
6
S RD
REMOTE YL OR BK R C 3
CN - DISP CONTROL
7
4
WH
RD
(OPTION)
BK
CM 5
DOOR S/W
CLEANER
RD
BK
DISPLAY PCB 6
AIR
BLOCK
GN/YL TMo
P/NO : 3854A20203M
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
F1 D.P C TH
BK BK
GN/YL
NO NC NO NC
BK TNS
BK
OR
BR WH WH
INDOOR DRAIN STEP
MOTOR PUMP MOTOR WH
YL BK
GN/YL
TB1 52F1
OR
BK
BL
BL
1 2
WH
BR FUSE T3.15A TM 1 2 3 L1 L2 BK 3 4
OR BL
1
A2
PIPE L N WH 5 6
63H 52C
BL THERMISTOR 7 8
A1 TB2
2
T1 T2
TO OUTDOOR UNIT
BL
RD
4 WAY
COMP
3
FLOAT S/W BK BK BK
5
F C H BK BL
GN/YL REMOTE WH
CN - DISP CONTROL
(OPTIONAL EXTRA) CAPACITOR
To the Indoor unit
WH
RD
BK
BK BR
YL BL RD BR 1
DOOR S/W
TERMINAL WH BL
H.V. ASSY
CLEANER
RD
S 2
BK
DISPLAY PCB
AIR
BLOCK BK BK R C RD
3
TEMP. OR BK BK
4
THERMISTOR CM BK BK
20SV
5
FMo SV GN/YL
BK BK 6
GN/YL Tmo
3854A20072G
3854A20203L
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
42 Ceiling Cassette(60Hz)
7. Wiring Diagrams
F1 D.P C TH
BK BK
NO NC NO NC
BK TNS
BK
OR
WH WH
WH
BK
GN/YL
GN/YL
TB1 52F1
INDOOR WIRING DIAGRAM
THERMISTOR
1 2
BR WH
TEMP.
INDOOR DRAIN STEP STEP STEP STEP TM 1 2 3 L1 L2 BK 3 4
YL
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR A2 OR BL
L N WH 5 6
63H 52C
OR
BK
BL
7 8
FUSE T3.15A A1 TB2
3(L) 4(N)
T1 T2
BL BL WH WH PIPE BL
THERMISTOR
1Ø, 220V, 60Hz
TO OUTDOOR UNIT
OR
POWER SUPPLY
COMP
BK BK BK
5
FLOAT S/W BL
F C H BK
6
WH
REMOTE
CN - DISP CAPACITOR
BK BR
WH
RD
(OPTION)
BK
YL BL RD BR 1
WH BL
DOOR S/W
TERMINAL 2
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB S
AIR
BLOCK BK BK R C RD
3
OR BK BK
4
CM BK BK 5
FMo SV 20SV GN/YL
BK BK 6
GN/YL Tmo
3854A20203L
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
BR
GN/YL
THERMISTOR
BR
TEMP.
WH
INDOOR DRAIN STEP
MOTOR PUMP MOTOR WH
YL 1 3 5 31
TM L N 52C A
OR
BK
BL
BL
B
BR FUSE T3.15A 2 4 6 32
1
1Ø,220V,60Hz
PIPE POWER SUPPLY BK
BL THERMISTOR
2
OR BK
TO OUTDOOR UNIT
BK
RD
COMP
3
F1
BR BR WH
4
Co Co
WH
ONLY LT-D xxx2CL FLOAT S/W WH Cr WH
To the indoor unit
PTCR BK BK
1
5
BK RD WH
BK
YL BK YL BK 2
GN/YL REMOTE BL
CN - DISP CONTROL BL
3
OR OR
T2 T1 4
WH
RD
BK
T3
FMo1 FMo2 5
DOOR S/W
CLEANER
RD
BK
DISPLAY PCB CM
AIR
3854A20072P
3854A20072Y
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
BR
WH
WH
GN/YL
THERMISTOR
N A
BR
TEMP.
INDOOR DRAIN STEP STEP STEP STEP B
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR 2 4 6 32
YL
1Ø,220V,60Hz
OR
BK
BL
POWER SUPPLY BK
FUSE T3.15A
3(L) 4(N)
BL BL WH WH OR BK
PIPE
THERMISTOR BK
TO OUTDOOR UNIT
F1
BR BR WH
COMP
Co Co
WH
5
WH Cr WH
BK WH
YL BK YL BK 2
REMOTE BL
CN - DISP CONTROL 3
7
OR OR BL
T2 T1 4
WH
RD
(OPTION)
BK
T3
DOOR S/W
CLEANER
RD
49FMo 49FMo GN/YL
BK
DISPLAY PCB 6
AIR
BLOCK
CM Tmo
GN/YL GN/YL
3854A20072Y
BK
BK
BR D.P C TH
GN/YL
TNS
OR NO NC
WH
BR WH
INDOOR DRAIN STEP BK
MOTOR PUMP MOTOR WH 52F1
YL
WH 1 2
OR
BK
BL
BL
3 4
TM L N 1 3 5 31
BR FUSE T3.15A 52C A
T/B1 5 6
1
RD 7 8
PIPE B
BL THERMISTOR 2 2 2 32
1Ø,220V,60Hz T/B2
2
POWER SUPPLY
TO OUTDOOR UNIT
63H2
RD WH WH
RD
4 WAY
COMP
3
BR BR BK BK
BK YL
4
Co Co
F1
FLOAT S/W WH
YL YL
5
BK BL
GN/YL REMOTE WH Cr WH
CN - DISP
To the indoor unit
WH
CONTROL YL BK YL BK PTCR BK BK
(OPTIONAL EXTRA) RD 1
WH
RD
BK
BK WH
OR OR
2
DOOR S/W
TERMINAL BL
H.V. ASSY
CLEANER
RD
FMo1 FMo2 3
BK
DISPLAY PCB
AIR
3854A20072G 3854A20072X
Notes:
63H2 HIGH PRESSURE SWITCH FOR HEATING C TH THERMISTOR FOR PIPE TEMP. 20SV REVERSING COIL
52C MAGNETIC CONTACTOR Tmo TERMINAL BLOCK TM MAIN TERMINAL BLOCK
52F1 RELAY FOR FMo Cr RUN CAPACITOR FOR CM CM COMPRESSOR
Co RUN CAPACITOR FOR FMo FMo OUTDOOR FAN MOTOR F1 FUSE (250V, 5A)
D.P DEICER PCB RD RED BL BLUE
WH WHITE YL YELLOW OR ORANGE
BK BLACK BR BROWN CN CONNECTOR
GN/YL GREEN/YELLOW FIELD WIRING
44 Ceiling Cassette(60Hz)
7. Wiring Diagrams
BK
BK
BR D.P C TH
TNS
OR NO NC
WH
WH
BK
GN/YL
THERMISTOR
WH 1 2
BR
TEMP.
INDOOR DRAIN STEP STEP STEP STEP TM L N
3 4
MOTOR PUMP 1 3 5 31
YL
MOTOR MOTOR MOTOR MOTOR 52C A
T/B1 5 6
RD 7 8
OR
BK
BL
B
FUSE T3.15A 2 2 2 32
3(L) 4(N)
1Ø,220V,60Hz T/B2
BL BL WH WH PIPE POWER SUPPLY
THERMISTOR 63H2
RD WH WH
TO OUTDOOR UNIT
BR BR BK BK
COMP
YL
Co Co
F1
WH
5
FLOAT S/W YL YL
BK
6
BL
WH Cr WH
BK RD
WH
RD
(OPTION)
BK
OR OR WH
2
DOOR S/W
TERMINAL BL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB FMo1 FMo2 3
AIR
3854A20072X
63H2 HIGH PRESSURE SWITCH FOR HEATING C TH THERMISTOR FOR PIPE TEMP. 20SV REVERSING COIL
52C MAGNETIC CONTACTOR Tmo TERMINAL BLOCK TM MAIN TERMINAL BLOCK
52F1 RELAY FOR FMo Cr RUN CAPACITOR FOR CM CM COMPRESSOR
Co RUN CAPACITOR FOR FMo FMo OUTDOOR FAN MOTOR F1 FUSE (250V, 5A)
D.P DEICER PCB RD RED BL BLUE
WH WHITE YL YELLOW OR ORANGE
BK BLACK BR BROWN CN CONNECTOR
GN/YL GREEN/YELLOW FIELD WIRING
BK
BK
GN/YL
BR
THERMISTOR
BR
TEMP.
BL
BL
1 3 5 31
TM L N 52C A
BR FUSE T3.15A
1
B
2 4 6 32
PIPE
1Ø,220V,60Hz
BL THERMISTOR POWER SUPPLY BK
2
TO OUTDOOR UNIT
BK
OR BK
RD
COMP
3
BK
F1
BR BR WH
4
BK
ONLY LT-D xxx2CL FLOAT S/W Co Co
WH
Cr WH
5
WH
To the indoor unit
PTCR BK BK
REMOTE BK RD CH 1
GN/YL BK WH
CN - DISP CONTROL YL BK YL BK 2
BL
WH
3
RD
BK
OR OR BL
T2 T1 4
DOOR S/W
TERMINAL T3
H.V. ASSY
CLEANER
RD
FMo1 FMo2 5
BK
DISPLAY PCB
AIR
3854A20072P
P/NO : 3854A90008M
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
BK
BK
BR
WH
GN/YL
THERMISTOR
BR 1 3 5 31
TM L 52C
TEMP.
N A
INDOOR DRAIN STEP STEP STEP STEP
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR
YL
B
OR
BK
BL
2 4 6 32
FUSE T3.15A 1Ø,220V,60Hz
3 (L ) 4 (N )
POWER SUPPLY BK
BL BL WH WH PIPE
THERMISTOR BK
OR BK
TO OUTDOOR UNIT
BK
COMP
F1
BR BR WH
BK
5
FLOAT S/W Co Co
WH
6
WH Cr WH
BK WH
2
WH
RD
(OPTION)
BK
YL BK YL BK BL
3
DOOR S/W
TERMINAL
H.V. ASSY
CLEANER
RD
OR OR BL
BK
DISPLAY PCB T2 T1 4
AIR
BLOCK
T3
FMo1 FMo2 5
49FMo 49FMo GN/YL
6
CM Tmo
GN/YL GN/YL
P/NO : 3854A90008M
Notes:
52C MAGNETIC CONTACTOR Co RUN CAPACITOR FOR FMo
TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
F1 FUSE (250V,10A) TMo TERMINAL BLOCK
CM COMPRESSOR RD RED
BL BLUE WH WHITE
BK BLACK YL YELLOW
OR ORANGE GN/YL GREEN/YELLOW
BR
INDOOR DRAIN STEP
YL
MOTOR PUMP MOTOR
OR
BK
BL
BL
BR FUSE T3.15A
1
PIPE
BL THERMISTOR
2
TO OUTDOOR UNIT
RD
4 WAY
COMP
3
BK
4
FLOAT S/W
5
GN/YL REMOTE
CN - DISP CONTROL
(OPTIONAL EXTRA)
WH
RD
BK
DOOR S/W
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
TEMP.
THERMISTOR
3854A20072G
3854A90008D
Notes:
63H2 HIGH PRESSURE SWITCH FOR HEATING C TH THERMISTOR FOR PIPE TEMP. 20SV REVERSING COIL
52C MAGNETIC CONTACTOR Tmo TERMINAL BLOCK TM MAIN TERMINAL BLOCK
52F1 RELAY FOR FMo Cr RUN CAPACITOR FOR CM CM COMPRESSOR
Co RUN CAPACITOR FOR FMo FMo OUTDOOR FAN MOTOR F1 FUSE (250V, 5A)
D.P DEICER PCB RD RED BL BLUE
WH WHITE YL YELLOW OR ORANGE
BK BLACK BR BROWN CN CONNECTOR
GN/YL GREEN/YELLOW FIELD WIRING
46 Ceiling Cassette(60Hz)
7. Wiring Diagrams
GN/YL
INDOOR WIRING DIAGRAM
THERMISTOR
BR
TEMP.
INDOOR DRAIN STEP STEP STEP STEP
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR
YL
OR
BK
BL
FUSE T3.15A
3 ( L) 4 ( N)
BL BL WH WH PIPE
THERMISTOR
TO OUTDOOR UNIT
COMP
5
FLOAT S/W
6
REMOTE
CN - DISP CONTROL
7
WH
RD
(OPTION)
BK
DOOR S/W
TERMINAL
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB
AIR
BLOCK
3854A90008D
Notes:
63H2 HIGH PRESSURE SWITCH FOR HEATING C TH THERMISTOR FOR PIPE TEMP. 20SV REVERSING COIL
52C MAGNETIC CONTACTOR Tmo TERMINAL BLOCK TM MAIN TERMINAL BLOCK
52F1 RELAY FOR FMo Cr RUN CAPACITOR FOR CM CM COMPRESSOR
Co RUN CAPACITOR FOR FMo FMo OUTDOOR FAN MOTOR F1 FUSE (250V, 5A)
D.P DEICER PCB RD RED BL BLUE
WH WHITE YL YELLOW OR ORANGE
BK BLACK BR BROWN CN CONNECTOR
GN/YL GREEN/YELLOW FIELD WIRING
BK F1
GN/YL
BK
THERMISTOR
BR
TEMP.
WH
INDOOR DRAIN STEP RD
MOTOR PUMP MOTOR
YL WH F1 WH
OR
BK
BL
BL
FUSE T3.15A TM R S T N 1 3 5 31
BR 52C
1
A
PIPE
BL THERMISTOR B
2
POWER SUPPLY 2 4 6 32
TO OUTDOOR UNIT
OR
RD
COMP
3
BK
RD
4
BK WH BK
ONLY LT-D xxx2CL FLOAT S/W 63H2
Co Co
5
BK
GN/YL REMOTE WH
CN - DISP CONTROL
To the indoor unit
BK RD
WH
RD
BK
YL BK YL BK BK BK 1(L)
DOOR S/W
TERMINAL WH 2(N)
H.V. ASSY
CLEANER
RD OR OR
RD
BK
DISPLAY PCB
AIR
CM TMo
GN/YL
3854A20072P
3854A20119P
Notes:
63H2 HIGH PRESSURE SWITCH FOR COOLING TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
49FMo INTERNAL T.P FOR FMo SV SOLENOID COIL F1 FUSE (250V 5A)
CM COMPRESSOR Co RUN CAPACITOR FOR FMo TMo TERMINAL BLOCK
52C MAGNECTIC CONTACTOR BL BLUE RD RED
BK BLACK WH WHITE OR ORANGE
YL YELLOW GN/YL GREEN/YELLOW
BK F1
BK
WH
RD
GN/YL
THERMISTOR
BR
TEMP.
INDOOR DRAIN STEP STEP STEP STEP
MOTOR PUMP MOTOR MOTOR MOTOR MOTOR TM R S T N 1 3 5 31
YL 52C A
OR
BK
BL
FUSE T3.15A
B
3(L) 4(N)
BK
COMP
RD
5
BK WH BK
FLOAT S/W
63H2
6
Co Co
REMOTE BK
CN - DISP CONTROL
7
WH
WH
RD
(OPTION)
BK
TERMINAL BK RD
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB YL BK YL BK 1(L)
AIR
BLOCK BK BK
OR OR WH 2(N)
RD
FMo FMo SV U V 3
49FMo 49FMo
W
(T1) (T2) 4
(T3)
5
CM TMo
GN/YL
3854A20119P
Notes:
63H2 HIGH PRESSURE SWITCH FOR COOLING TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
49FMo INTERNAL T.P FOR FMo SV SOLENOID COIL F1 FUSE (250V 5A)
CM COMPRESSOR Co RUN CAPACITOR FOR FMo TMo TERMINAL BLOCK
52C MAGNECTIC CONTACTOR BL BLUE RD RED
BK BLACK WH WHITE OR ORANGE
YL YELLOW GN/YL GREEN/YELLOW
BK F1
BK D.P C TH
BK BK NO NC NO NC
GN/YL
TNS
WH
RD WH
BR F1
WH WH
INDOOR DRAIN STEP
MOTOR PUMP MOTOR OR 52F1
YL BK
1 2
TM R S T N OR
OR
1 3 5 31
BK
52C
BL
BL
A OR 3 4
B
PIPE POWER SUPPLY 2 4 6 32 7 8
BL THERMISTOR T/B2
2
TO OUTDOOR UNIT
BK
RD BL
RD RD
4 WAY
COMP
WH
3
WH BK
BK BK
BK 63H2 BK
4
Co Co
FLOAT S/W
5
BK RD
GN/YL REMOTE YL BK YL BK 1( L)
CN - DISP CONTROL
BK BK
WH
(OPTIONAL EXTRA) OR OR WH 2 ( N)
WH
RD
BK
RD
FMo FMo SV U V 3
DOOR S/W
CLEANER
RD W (T1) (T2) BK BL 4
BK
DISPLAY PCB
AIR
BLOCK (T3) 5
20SV
TEMP. BK BL
THERMISTOR CM TMo
GN/YL
3854A20072G 3854A20119N
Notes:
63H2 HIGH PRESSURE SWITCH FOR COOLING 52C MAGNECTIC CONTACTOR Co RUN CAPACITOR FOR FMo
C TH THERMISTOR FOR PIPE TEMP. TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
49FMo INTERNAL T.P FOR FMo 52F1 RELAY FOR FMo F1 FUSE (250V 5A)
20SV REVERSING COIL D.P DEICER PCB TMo TERMINAL BLOCK
CM COMPRESSOR SV SOLENOID COIL BL BLUE
RD RED BK BLACK WH WHITE
OR ORANGE YE YELLOW GN/YL GREEN/YELLOW
48 Ceiling Cassette(60Hz)
7. Wiring Diagrams
BK F1
BK D.P C TH
BK BK NO NC NO NC
TNS
WH
RD WH
GN/YL
THERMISTOR
BR
OR 52F1
BK
TEMP.
INDOOR DRAIN STEP STEP STEP STEP 1 2
OR
MOTOR PUMP TM R S T N 1 3 5 31
YL
MOTOR MOTOR MOTOR MOTOR 52C A OR 3 4
OR
BK
BL
T/B1 WH 5 6
FUSE T3.15A B
3(L) 4(N)
POWER SUPPLY 2 4 6 32 7 8
BL BL WH WH PIPE T/B2
THERMISTOR
BK
TO OUTDOOR UNIT
RD BL
RD
WH
COMP
WH BK
BK BK
63H2 BK
5
FLOAT S/W Co Co
6
REMOTE
CN - DISP
BK RD
WH
RD
(OPTION)
BK
YL BK YL BK BK BK 1(L)
WH
DOOR S/W
TERMINAL OR OR WH 2(N)
H.V. ASSY
CLEANER
RD
BK
DISPLAY PCB RD
AIR
3854A20119N
Notes:
63H2 HIGH PRESSURE SWITCH FOR COOLING 52C MAGNECTIC CONTACTOR Co RUN CAPACITOR FOR FMo
C TH THERMISTOR FOR PIPE TEMP. TM MAIN TERMINAL BLOCK FMo OUTDOOR FAN MOTOR
49FMo INTERNAL T.P FOR FMo 52F1 RELAY FOR FMo F1 FUSE (250V 5A)
20SV REVERSING COIL D.P DEICER PCB TMo TERMINAL BLOCK
CM COMPRESSOR SV SOLENOID COIL BL BLUE
RD RED BK BLACK WH WHITE
OR ORANGE YE YELLOW GN/YL GREEN/YELLOW
INDOOR
COIL OUTDOOR
COIL
COMPRESSOR
GAS SIDE
Note:
: COOLING
50 Ceiling Cassette(60Hz)
8. Refrigerant Cycle Diagrams
OUTDOOR CAPI A
COIL
COMPRESSOR
INDOOR
GAS
Gas SIDE
Side ACCUM.
COIL
CAPI C
LIQUID
Liquid Side
SIDE
CAPI B
Heat Pump
REVERSING
INDOOR GAS SIDE VALVE
COIL
CAPI C1
Heating Cooling
CAPI C2
COMPRESSOR
LIQUID SIDE
CAPI B
Note: COOLING
HEATING
Based on Total Cooling Capacity, choose suitable model from the specification table.
The model with net cooling capacity of 24,000 Btu/h is selected.
The system is LT-E2420CL.
Verify the unit performance at the given conditions in accordance with step 3.
Enter cooling capacities table on page 54 at high speed and 95°F outdoor entering air temperature
with 80°F DB/67°F WB indoor entering air temperature.
Total cooling capacity = 24,000 Btu/h, Sensible capacity=18,000 Btu/h
Ex: At 30m interconnecting piping length, from coefficient of capacity change graph,
coeffienct factor is 0.915.
Total Cooling Capacity = Capacity (%) x Total Cooling Capacity = 91.5x24000 = 21,960Btu/h
100 100
Sensible Capacity = Capacity (%) x Sensible Capacity = 91.5x18,000 = 16,470Btu/h
100 100
52 Ceiling Cassette(60Hz)
10. Performance Data
54 Ceiling Cassette(60Hz)
10. Performance Data
Notes: 1. All capacites are net, evaporator fan motor heat is deducted. 2. DB=Dry Bulb Temperature(°F), WB=Wet Bulb Temperature(°F)
3. TC=Total cooling capacity(Unit:1,000Btu/h) 4. SHC=Sensible heat capacity(Unit:1,000Btu/h)
5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
56 Ceiling Cassette(60Hz)
10. Performance Data
Notes: 1. All capacites are net, evaporator fan motor heat is deducted. 2. DB=Dry Bulb Temperature(°F), WB=Wet Bulb Temperature(°F)
3. TC=Total cooling capacity(Unit:1,000Btu/h) 4. SHC=Sensible heat capacity(Unit:1,000Btu/h)
5. PI=Power Input(Comp.+ indoor fan motor+outdoor fan motor) (kW)
Notes :
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 44.6°FDB/42.8°FWB.
3. TC=Total heating capacity(Unit:1,000 Btu/h)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
58 Ceiling Cassette(60Hz)
10. Performance Data
Outdoor WB (°F)
Indoor DB
14.0 23.0 32 35.6 39.2 42.8 50 59.0
(°F)
TC PI TC PI TC PI TC PI TC PI TC PI TC PI TC PI
60.8 28.4 3.0 33.4 3.3 38.7 3.6 40.6 3.7 42.6 3.8 45.0 3.9 48.7 4.1 53.7 4.4
64.4 27.5 3.1 32.4 3.4 37.4 3.7 39.3 3.8 41.2 4.0 43.5 4.0 47.1 4.2 52.0 4.5
68 26.7 3.2 31.4 3.5 36.3 3.8 38.2 4.0 40.0 4.1 42.0 4.2 45.7 4.4 50.5 4.7
71.6 25.7 3.3 30.3 3.6 35.0 4.0 36.8 4.1 38.5 4.2 40.7 4.3 44.1 4.5 48.7 4.8
75.2 24.8 3.4 29.2 3.8 33.8 4.1 35.5 4.2 37.2 4.3 39.3 4.4 42.6 4.7 47.0 5.0
Notes :
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal capacity is 44.6°FDB/42.8°FWB.
3. TC=Total heating capacity(Unit:1,000 Btu/h)
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect
of frost on the heat exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including
capacity reduction by frost on the exchanger and defrosting operation.
Notes :
Outdoor Air 1. All capacities are net, indoor fan motor heat is deducted.
Temperature 14 21.2 24.8 28.4 32 35.6 39.2 42.8 2. Capacities are based on the following conditions.
(°FWB, RH=85%) Outdoor air : 85%RH. However, the condition on nominal capacity is
44.6°FDB/42.8°FWB.
Correction
0.95 0.95 0.89 0.87 0.87 0.89 0.91 1.00 3. TC=Total heating capacity(Unit:1,000 Btu/h)
Factor
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW)
60 Ceiling Cassette(60Hz)
11. The Coefficient of Capacity Change
Cooling
100
18K
90
Capacity(%)
42K/60K
24/48K
80
70
7.5 10 20 30 40 50 Model Additional Refrigerant
24K 30 g/m
18K
24K
90
Capacity(%)
42K/60K
80
70
7.5 10 20 30 40 50
Total Pipe Length(m)
Notes:
* Equivalent pipe length = Actual pipe length + number of bend x 0.3
* Refer to the specification for the maximum pipe length of each model.
Cooling
100
48K
36K
90 30K
Capacity(%)
60K
80
70
7.5 10 20 30 40 50 Model Additional Refrigerant
36K 40 g/m
60K 70 g/m
100
30K
60K
90 36K
Capacity(%)
48K
80
70
7.5 10 20 30 40 50
Total Pipe Length(m)
Notes:
* Equivalent pipe length = Actual pipe length + number of bend x 0.3
* Refer to the specification for the maximum pipe length of each model.
62 Ceiling Cassette(60Hz)
11. The Coefficient of Capacity Change
100
Cooling/Heating
Capacity(%)
90
80
70
7.5 8 9 10 11 12 13 14 15
Total Pipe Length(m)
Model Additional Refrigerant
12K 30 g/m
Notes:
* Equivalent pipe length = Actual pipe length + number of bend x 0.3
* Refer to the specification for the maximum pipe length of each model.
Item Range
43(109.4)
18(64.4)
Standard operation
-10(14)
10(50) 24(75.2)
Indoor air temperature °C D.B.(°F)
64 Ceiling Cassette(60Hz)
13. Air Velocity and temperature Distributions(Reference Data)
2m 2m
2.0
2.0
1.5
1m 1m
1.5
0.5 1.0
1.0
0.5
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m
22 1m 1m
24 27
24
0m 0m
5m 4m 3m 2m 1m 0m 5m 4m 3m 2m 1m 0m
2m 2.0 2.0 2m
2.0 2.0
1.5 1.5
1.5 1.5 1m
1m
1.0 1.0 1.0 1.0
0.5 0.5
0.5 0.5
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
22 22 1m 1m
24 27 27 24
24 24
0m 0m
4m 3m 2m 1m 0m 1m 2m 3m 4m 4m 3m 2m 1m 0m 1m 2m 3m 4m
Overall
Notes:
- Sound measured at 1.5m away from
the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20µPa
Ceiling
- Sound level will vary depending on a range of factors such as
1.5m the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard(KS conditions)
80 80 80
70 70 70
Sound Pressure Level (dB re 20µPa )
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
66 Ceiling Cassette(60Hz)
14. Sound Levels
80 80
80
70 70
NC-70 NC-70 70
NC-70
NC-65 NC-65
60 60
NC-65
60
NC-60 NC-60
Sound Pressure Level (dB re 20µPa )
20 NC-25 20 NC-25
NC-25
20
NC-20 NC-20
NC-20
NC-15 NC-15
10 10 NC-15
10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Octave Band Center Frequency (Hz)
LT-D4820 LT-D6020
LT-C/H482D LT-C/H602D
LT-C/H48BD LT-C/H60BD
90 90
80 80
70 70
NC-70 NC-70
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
Sound Pressure Level (dB re 20µPa )
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
20 NC-25 20 NC-25
NC-20 NC-20
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
30 or more
the unit. Ceiling Ceiling Board
Ceiling Board
• There should not be any obstacles to the air circula-
30 or less
tion.
or more
50 or 50 or
more more
330 or less
Above 250
100
• There should be easy provision of condensate drain.
• Taking into account the noise prevention criteria, Unit:cm
spot the installation location.
• Keep proper distance of the unit from ceiling, fence, Floor
20 or more
Ceiling Ceiling Board
Ceiling Board
30 or less
or more
50 or 50 or
more more
330 or less
Above 250
100
15.1.2 Outdoor Unit
• If a roof is built over the unit to prevent direct sun- Unit:cm
light or rain exposure, make sure that heat radiation
from the condenser is not restricted. Floor
• Do not place animals and plants in the path of the warm air.
• Take the air conditioner weight into account and select a place where noise and vibration are minimum.
• Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
• Rooftop Installations : If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the
roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop
mounting.
Su Su
More than nro More than nro
30cm of 30cm
of More than 50cm
(Service space)
More
More than
than More than
Fe 30cm
30cm
30cm Fe
ob nce ob nce
sta or sta or
cle cle
s More than 50cm s More than 50cm
More than 70cm More than 70cm
68 Ceiling Cassette(60Hz)
15. Installation
Level gauge
75
600 (Ceiling opening)
450 (Hanging bolt)
570 Unit size
75
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to Unit:mm
45 785(Hanging bolt) 45
66
790 (Ceiling opening)
658 (Hanging bolt)
744 Unit size
744 Unit size
NOTE:
66
90mm
(W3/8 or M10)
Nut
Flat washer for M10
(W3/8 or M10)
(accessory) Ceiling board Air Conditioner body Ceiling board
Spring washer
(M10)
Ceiling
150mm
(W3/8 or M10) from the bracket to 40mm
Nut
Flat washer for M10 Air Conditioner body
(W3/8 or M10)
(accessory) Ceiling board Ceiling board
Spring washer
(M10)
• The following parts are local purchasing. • Drill the piping hole on the wall slightly tilted to the
Hanging Bolt - W 3/8 or M10 outdoor side using a Ø 70 hole-core drill.
Nut - W 3/8 or M10
Spring Washer - M10
Wall
Plate Washer - M10
Indoor Outdoor
CAUTION
• Tighten the nut and bolt to prevent unit from
5~7mm
falling off.
70 Ceiling Cassette(60Hz)
15. Installation
15.5 Wiring Connection
1. All wiring must comply with LOCAL REGULATIONS.
2. Select a power source that is capable of supplying the current as required by the air conditioner.
3. Feed the power source to the unit via a distribution switch board designed for this purpose.
4. The terminal screws inside the control box may be loose due to vibration during transport.
Check the screws for loose connection.
(Running the air conditioner with loose connection can overload and damage electrical components.)
5. Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION.
Indoor
power cord
Control box cover
Remote
controller [Air inlet side view]
cord
Control box cover
fitting screw(2 units)
CAUTION
The power cord connected to the outdoor unit The connecting cable connected to the indoor and
should be complied with the following specifications outdoor unit should be complied with the following
(Rubber insulation, type H05RN-F approved by HAR specifications (Rubber insulation, type H05RN-F
or SAA). approved by HAR or SAA).
Capacity 1 Phase 3 Phase
18K/24K/28K/30K NORMAL
2.5mm2 -
BTU/h CROSS-SECTIONAL
GN
/YL 36K BTU/h 5.5mm 2.5mm2
2 GN
/YL AREA 0.75mm2 (18K/24K/36K)
8.5mm
7.5mm
42K/48K/60K
8.5mm 2
3.5mm 2 1.25mm2 (42K/48K/60K)
20 BTU/h 20
mm mm
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer or its service agent.
WARNING
Make sure that the screws of the terminal are free from looseness.
1. Temporarily fix two decorative panel fixing screws (hexagon M6 screw) on the unit body. (Tighten by amount 10mm in
length.)
The fixing screws (hexagon M6 screw) are included the Indoor unit box.
2. Remove the air inlet grille from the decorative panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decorative panel key hole ( ) on the screws fixed in step above, and slide the panel so that the screws
reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector and room temp. thermistor connector.
6. After tightening these screws, install the air inlet grille (including the air filter) and push middle point of inlet grille.
7. Assemble the cover display and the cover.
Key holes
Louver motor
Decorative panel
fixing screws
(Hexagon M6 screw)
Cover
Decorative panel
Cover display
Push
Inlet Grille
72 Ceiling Cassette(60Hz)
15. Installation
The decoration panel has its installation Before installing the decoration panel,
direction. always remove the paper template.
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by
amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole ( ) on the screws fixed in step above, and slide the panel so
that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).
Decoration panel
Display
Key holes
Inlet Grille
CAUTION
Install certainly the decoration Good example Bad example
Air conditioner unit
panel.
Cool air leakage causes sweating. Air conditioner Air
unit Cool air leakage
Water drops fall. (no good)
Ceiling Ceiling
board board
Decoration panel Decoration
Fit the insulator (this part) and panel
be careful for cool air leakage
Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior
Feed water Flexible drain hose and leave it provisionally until the test
(accessory)
comes to an end.
Main
drain pipe • Feed water to the flexible drain hose and
check the piping for leakage.
Drain • Be sure to check the drain pump for normal
Drain Pump port Glue the joint operating and noise when electrical wiring
Drain hose connection is complete.
Use the clip (accessory) • When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
Drain pan
Flexible drain hose
CAUTION 1/50~1/100
The supplied flexible drain hose should not be curved,
MAX 700mm
neither screwed. The curved or screwed hose may
cause a leakage of water.
After the confirmation of the above conditions, prepare the wiring as follows: Flexible drain hose
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the
circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which
the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If
they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a
overload protection device.
• Proper starting power is not given to the compressor.
74 Ceiling Cassette(60Hz)
15. Installation
R15H
OP2 OP1
R14H OP3 R19H
SW TH R11H
Position 3 2TH LO
C070
STAND
HI R03S
R04S
R01S
R02S
SW HIGH
CAUTION
You can choose the RPM(or air volume) of indoor motor according to the height of ceiling to supply the
comfortable atmosphere to consumers.
Procedure
1. Choose the selectable position in the table after measuring the height of ceiling.
Ceiling height Mode of slide switch Change of air volume Remark
more than 3.3m High Ceiling Increasing
Maunfactured in stan-
2.7~3.3m Standard -
dard mode
less than 2.7m Low Ceiling Decreasing
2. In the case of changing the height as "high" or "low", open the rear cover of the wired remote-controller.
3. Move the slide switch to the set position. Slide switch for 2 Thermistor
4. Close the rear cover and check if it works nomally. Low ceiling R15H
Lo R14H OP3
SW TH
OP2 OP1
R19H
R11H
Standard STAND
(Default) REMO
MAIN
2TH OP7
OP6
LO
C070
STAND
HI R03S
R04S
R01S
R02S
SW HIGH
CAUTION
• Be careful not to exchange the color of wires.
• The maximum length of connecting wire should be below 200m(25Ω) on connecting each units.
• Use a wire more than 0.5mm2
76 Ceiling Cassette(60Hz)
16. Function of Remote Control
78 Ceiling Cassette(60Hz)
20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355
Seoul 150-721, Korea
Phone :3777-7969 Fax:3777-5137/8
http://www.lge.com
http://biz.lgservice.com
ctronics
Ele In Approvals:
G
c.
L
EN ISO 9001
BS EN ISO 9001
M
REG I
IR
ST F ANSI/ASQC Q9001
I
O E R E D 97
S
4
9 001 A8
P/No.: 3828A20428J KS A 9001
For continual product development, LG reserves the right to change specifications without notice
©LG Electronics INC. Printed in Korea.March/2004