Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 7

TEST REPORT FOR O/C & E/F RELAY

ELECTROTEST DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24


DATE :- 05-04-2023
PVT. LTD. TESTING DATE : 03-04-2023
PANEL:- 3.3 KV HT SWBD
CLIENT :- TSL,COAL MINES FEEDER :- SHAFT CABLE Sheet No.1
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 of 2

Relay Details :- Make : SCHNEIDER Model No. : MICOM P122


Relay Current : 1A Aux Volts : 0-110 V DC
SI No : 39791870/05/22 CTR : 400/1 A

Relay Setting :- (I>) :- 0.5×In TMS :- 1.0 (Curve – IEC SI)


(I>>) :- 3.0×In Time :- 0.5 Sec (Curve - DTL)
(I>>>) :- 5.0×In Time :- 0.1 Sec (Curve - DTL)
(Ie-d>) :- 0.2×In TMS :- 0.2 (Curve – IEC SI)
(Ie-d>>) :- 0.5×In Time :- 0.5 Sec (Curve - DTL)

Test Kit Details:-


Instrument: Relay test set
Make :- METRAVI Range :- 0-200 Amps
Sl. No. :- MIPL/43/21-22 Cal. Due Date :- 12-01-2024

1) O/C Unit Test :- (I>) (IEC SI)


Setting Injected Op. Time as
Pick up Actual OP. Time
Current Current in per graph in
Phase current In Sec. LED Remarks
x In TMS in Amps Amps Sec
(Amps) X2 X5 X2 X5 X2 X5
R–Y 0.5 1.0 0.51 1.0 2.5 10.0 4.30 10.034 4.374 O/C Trip OK
Y–B 0.5 1.0 0.51 1.0 2.5 10.0 4.30 10.032 4.375 O/C Trip OK
B–R 0.5 1.0 0.51 1.0 2.5 10.0 4.30 10.033 4.373 O/C Trip OK

2) O/C Unit Test :- (I>>) (DMT)


Setting
Pick up Injected
Current Actual OP. Time
Phase Time in current in Current in LED Remarks
x In In milli-Sec.
Sec Amps Amps
(Amps)
R–Y 3.0 0.5 3.0 4.0 537 O/C Trip OK
Y–B 3.0 0.5 3.0 4.0 536 O/C Trip OK
B–R 3.0 0.5 3.0 4.0 538 O/C Trip OK

3) O/C Unit Test :- (I>>>) (DMT)


Setting
Pick up Injected Actual OP.
Current
Phase Time in current in Current in Time LED Remarks
x In
Sec Amps Amps In milli-Sec.
(Amps)
R–Y 5.0 0.1 5.0 6.0 133 O/C Trip OK
Y–B 5.0 0.1 5.0 6.0 132 O/C Trip OK
B–R 5.0 0.1 5.0 6.0 134 O/C Trip OK
TEST REPORT FOR O/C & E/F RELAY
ELECTROTEST DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24
DATE :- 05-04-2023
PVT. LTD. TESTING DATE : 03-04-2023
PANEL:- 3.3 KV HT SWBD
CLIENT :- TSL,COAL MINES FEEDER :- SHAFT CABLE Sheet
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 No.2 of 2

4) Earth Fault Unit Test :- (Ie-d>) (IEC SI)


Setting Injected Op. Time as
Pick up Actual OP. Time
Current in per graph in
Phase Current TMS current in In Sec. LED Remarks
x In Amps Sec
Amps
(Amps) X2 X5 X2 X5 X2 X5
R–N 0.2 0.2 0.2 0.4 1.0 2.0 0.86 2.036 0.868 E/F Trip OK
Y–N 0.2 0.2 0.2 0.4 1.0 2.0 0.86 2.035 0.870 E/F Trip OK
B–N 0.2 0.2 0.2 0.4 1.0 2.0 0.86 2.037 0.869 E/F Trip OK

5) Earth Fault Unit Test :- (Ie-d>>) (DMT)

Setting Pick up Injected Actual OP.


Phase Current current in Current in With 86 Time LED Remarks
Time (sec)
x In Amps Amps In mili-Sec
R–N 0.5 0.5 0.5 0.6 531 E/F Trip OK
Y–N 0.5 0.5 0.5 0.6 532 E/F Trip OK
B–N 0.5 0.5 0.5 0.6 530 E/F Trip OK

Remarks :- Test results found satisfactory, relay is fit to service.

Test Performed by: Test Witnessed by:


Name : Sonu,Vishal & Mukesh Name :MR. S. Bandopadhyay
Organization: Electrotest pvt ltd. Organization: TSL

Organisation Electrotest Pvt Ltd KINJAL TSL


Name Abhishek Singh
Designation Manager

Signature
TEST REPORT FOR ELR RELAY
ELECTROTEST DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24
DATE :- 05-04-2023
PVT. LTD. TESTING DATE : 03-04-2023
PANEL:- 3.3 KV HT SWBD
CLIENT :- TSL,COAL MINES FEEDER :- SHAFT CABLE Sheet
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 No.1 of 1

Relay Details :- Make : SCHNEIDER Model No. : MICOM P122


Relay Current : 1A Aux Volts : 0-110 V DC
SI No : 39791867/05/22 CTR : 50/1 A

Relay Setting :- (Ie>) :- 0.2×In TMS :- 0.1 (Curve – IEC SI)


(Ie>>) :- 0.5×In Time :- 50 mSec (Curve - DMT)
(Ie>>>) :- 0.8×In Time :- 0 mSec (Curve - DMT)
Test Kit Details:- Instrument: Relay test set
Make :- METRAVI Range :- 0-200 Amps
Sl. No. :- MIPL/43/21-22 Cal. Due Date :- 12-01-2024

1) ELR Unit Test :- (Ie>) (IEC SI)


Setting Injected Op. Time as
Pick up Actual OP. Time
Current Current in per graph in
Phase TMS current In Sec. LED Remarks
x In Amps Sec
in Amps
(Amps) X2 X5 X2 X5 X2 X5
CBCT 0.2 0.1 0.2 0.4 1.0 1.0 0.430 1.037 0.461 ELR Trip OK

2) ELR Unit Test :- (Ie>>) (DMT)


Setting Pick up Injected Actual OP.
Phase Current Time current in Current in With 86 Time LED Remarks
x In (milli-sec) Amps Amps In mili-Sec
CBCT 0.5 50 0.5 0.6 87 ELR Trip OK

3) ELR Unit Test :- (Ie>>>) (DMT)


Setting Pick up Injected Actual OP.
Phase Current Time current in Current in With 86 Time LED Remarks
x In (milli-sec) Amps Amps In mili-Sec
CBCT 0.8 0 0.8 0.9 37 ELR Trip OK

Remarks :- Test results found satisfactory, relay is fit to service.

Test Performed by: Test Witnessed by:


Name : Sonu,Vishal & Mukesh Name : MR. S. Bandopadhyay
Organization: Electrotest pvt ltd. Organization: TSL
Organisation Electrotest Pvt Ltd KINJAL TSL
Name Abhishek Singh
Designation Manager
Signature
TEST REPORT FOR AUXILARY RELAY
ELECTROTEST DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24
DATE :- 05-04-2023
PVT. LTD. TESTING DATE : 03-04-2023
PANEL:- 3.3 KV HT SWBD
CLIENT :- TSL,COAL MINES FEEDER :- SHAFT CABLE Sheet No.1
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 of 1

1. Relay Details:-
Name :- Master Trip/ Lock Out Relay (K86)
Make :- GE
Model No:- MVAJM15JA0754A
Sl No :- 35570430/01/22
Aux. volt :- 110-125 V DC

2. Test Condition :- Relay is connected on panel.

3. General check :- All connections tightness checked- OK.

4. Test Kit Detail :-


Instrument: Relay test set
Make :- METRAVI Range :- 0-200 Amps
Sl. No. :- MIPL/43/21-22 Cal. Due Date :- 12-01-2024

5. Relay Test :- (Operational Check) :-

Visual Inspection On Flag


Relay Operation Remarks
Relay Operation
OK OK OK OK

Remarks :- Test results found satisfactory, relay is fit to service.

Test Performed by: Test Witnessed by:


Name : Sonu,Vishal & Mukesh Name :MR. S. Bandopadhyay
Organization: Electrotest pvt ltd. Organization: TSL

Organisation Electrotest Pvt Ltd KINJAL TSL


Name Abhishek Singh
Designation Manager

Signature

TEST REPORT FOR AUXILARY RELAY


DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24
ELECTROTEST DATE :- 05-04-2023
TESTING DATE : 03-04-2023
PVT. LTD. PANEL:- 3.3 KV HT SWBD
CLIENT :- TSL,COAL MINES FEEDER :- SHAFT CABLE Sheet No.1
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 of 1

1. Relay Details:-
Name :- INTER TRIP Relay (K96)
Make :- GE
Model No:- MVAAM31C1AA0751A
Sl No :- 35570434/01/22
Aux. volt :- 110-125 V DC

2. Test Condition :- Relay is connected on panel.

3. General check :- All connections tightness checked- OK.

4. Test Kit Detail :-


Instrument: Relay test set
Make :- METRAVI Range :- 0-200 Amps
Sl. No. :- MIPL/43/21-22 Cal. Due Date :- 12-01-2024

5. Relay Test :- (Operational Check) :-

Visual Inspection On Flag


Relay Operation Remarks
Relay Operation
OK OK OK OK

Remarks :- Test results found satisfactory, relay is fit to service.

Test Performed by: Test Witnessed by:


Name : Sonu,Vishal & Mukesh Name :MR. S. Bandopadhyay
Organization: Electrotest pvt ltd. Organization: TSL

Organisation Electrotest Pvt Ltd KINJAL TSL


Name Abhishek Singh
Designation Manager

Signature

TEST REPORT FOR AUXILARY RELAY


DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24
DATE :- 05-04-2023
TESTING DATE : 03-04-2023
PANEL:- 3.3 KV HT SWBD
ELECTROTEST FEEDER :- SHAFT CABLE
CLIENT :- TSL,COAL MINES Sheet
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 No.1 of 1

1. Relay Details:-
Name :- DC FAIL Relay (K80D)
Make :- GE
Model No:- MVAAM11B1CA2531A
Sl No :- 35573833/01/22
Aux. volt :- 110-125 V DC

2. Test Condition :- Relay is connected on panel.

3. General check :- All connections tightness checked- OK.

4. Test Kit Detail :-


Instrument: Relay test set
Make :- METRAVI Range :- 0-200 Amps
Sl. No. :- MIPL/43/21-22 Cal. Due Date :- 12-01-2024

5. Relay Test :- (Operational Check) :-

Visual Inspection On Flag


Relay Operation Remarks
Relay Operation
OK OK OK OK

Remarks :- Test results found satisfactory, relay is fit to service.

Test Performed by: Test Witnessed by:


Name : Sonu,Vishal & Mukesh Name :MR. S. Bandopadhyay
Organization: Electrotest pvt ltd. Organization: TSL

Organisation Electrotest Pvt Ltd KINJAL TSL


Name Abhishek Singh
Designation Manager

Signature

TEST REPORT FOR AUXILARY RELAY


DOC. NO. :- 06/ETEST/TSL/2-PIT/2023-24
DATE :- 05-04-2023
TESTING DATE : 03-04-2023
PANEL:- 3.3 KV HT SWBD
ELECTROTEST FEEDER :- SHAFT CABLE
CLIENT :- TSL,COAL MINES Sheet
LOCATION :- SIJUA 2PIT 3.3 KV S/S PANEL NO. :- 06 No.1 of 1

1. Relay Details:-
Name :- AC FAIL Relay (K80A)
Make :- GE
Model No:- MVAAM11B1CA2533A
Sl No :- 35573813/01/22
Aux. volt :- 220-250 V AC

2. Test Condition :- Relay is connected on panel.

3. General check :- All connections tightness checked- OK.

4. Test Kit Detail :-


Instrument: Relay test set
Make :- METRAVI Range :- 0-200 Amps
Sl. No. :- MIPL/43/21-22 Cal. Due Date :- 12-01-2024

5. Relay Test :- (Operational Check) :-

Visual Inspection On Flag


Relay Operation Remarks
Relay Operation
OK OK OK OK

Remarks :- Test results found satisfactory, relay is fit to service.

Test Performed by: Test Witnessed by:


Name : Sonu,Vishal & Mukesh Name :MR. S. Bandopadhyay
Organization: Electrotest pvt ltd. Organization: TSL

Organisation Electrotest Pvt Ltd KINJAL TSL


Name Abhishek Singh
Designation Manager

Signature