NT991BNWAS Inst - Tech Manual (1012-01)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 76

NAVITRON SYSTEMS LTD

NT991 BNWAS
BRIDGE NAVIGATIONAL
WATCH ALARM SYSTEM
INSTALLATION & TECHNICAL MANUAL

Osborn House
25e Brockhampton Lane
Havant, Hants, U.K. PO9 1JT
Registered in England No. 2607869

Tel: (023) 9249 8740


FAX: (023) 9249 8783
Int. Code: +44 23
Email: [email protected]
Web: www.navitron.co.uk
1012/01
NAVITRON SYSTEMS LTD

NT991BNWAS INSTALLATION & OPERATION

- Index -

General

Section 1: Unit Dimensions and Siting.

Section 2: Standard & Optional System Cables & Connections.

Section 3: Installation Presets.

Section 4: Installation Checks & Alongside Set Up.

Section 5: Operating Instructions & Alarm Indicators.

Section 6: NT991 BNWAS Schematics & PCB Layout.


NT991BNWAS INSTALLATION & OPERATION

General: -

The Navitron NT991 Bridge Navigational Watch Alarm System (BNWAS) is a robust
and intelligent monitoring device compliant with MSC specification MSC. 128(75)
and the IMO adopted standard for BNWAS - IEC 62616. The system provides a
backup facility for the Officer of the Watch (OOW) by automatically alerting the
Master or other qualified personnel if the OOW is rendered incapable of performing
regular and consistent watch duties. The system also provides an Emergency Call
facility in order that the OOW, or other watch personnel, can call for immediate
assistance.

The NT990 BNWAS is fully expandable from the Basic equipment required for
smaller vessels to the fully comprehensive configurations appropriate for much
larger ships. Available equipment includes optional Bridge Visual Alarm, Bridge
Reset and Movement Detector Units in addition to the requisite number of 2 nd Stage
(Officer Call) and 3rd Stage (Final) Crew Call and Public Area Audible Alarm Units.
The control unit also features an integral backup officer selector switch.

The NT991 BNWAS provides analogue and serial data output facilities to interface
with Central Alarm Panels, VDRs etc.

A built it intruder alarm which utilises the Movement Detector Units is also a standard
feature of the system.

The Basic NT991 BNWAS components are shown in Fig. G1.

(i) The Control / Display Unit (NT991 BNWAS CU) featuring: -

Operating Mode selection via key switch (permanently ON, permanently


OFF or automatically engaged via the ships Heading or Track control
system).

Variable Alarm timing period adjustable via key switch from 3 to 12


minutes in 1-minute steps.

A two digit red LED display showing either actual alarm time period set or
a count down timer when the BNWAS is engaged.

Integral Backup Up Officer selector switch with LED indication of selected


officer.

Installation adjustable alarm tone type and volume.

Prominent Alarm Reset button.

Emergency Call button.

Variable red backlight illumination for night viewing.

Comprehensive LED Operational mode and Alarm status indicators


including Tamper, Power Fail and Intruder alarms.
NT991BNWAS INSTALLATION & OPERATION

(ii) Distribution Unit Type NT991 BNWAS DB

Suitable for a range of ships power supply voltage (18 – 40Vdc,


115/230Vac 50/60Hz) and equipped with 12 volt free relay contacts to
drive remote visual / audible alarms such as: -

Bridge Visual, Bridge Audible, Master Call, 1st Officer Call, 2nd Officer Call,
3rd Officer Call, 4th Officer Call, Crew Call, Intruder Alarm and BNWAS
malfunction.

Further Alarm / Status output indications are available via two serial data
ports (4800 / 38K4 baud) for VDR, Central Alarm Panel etc.

A total of 6 x Remote (bridge/bridge wing mounted) Reset Unit inputs are


also provided (2 x standard Navitron, 2 x serial data & 2 x opto isolated dc
level).

Automatic reset is also available via 2 x Movement Detector inputs.

An optional internal rechargeable battery can also be fitted to provide


power supply backup facility in the event of main power failure.

(iii) Optional Remote Alarm Reset Unit(s) (NT990 BNWAS RST)

Waterproof and illuminated, the Remote Reset units (maximum 6 units)


can be strategically installed in Wheelhouse and Bridge wing locations as
required.

(iv) Optional Bridge Visual Alarm Unit (WAS BVA)

The visual unit is typically bridge deckhead mounted and provides the first
alarm level signalling the end of the BNWAS time period selected (3 to 12
minutes). It invites bridge watch personnel to cancel by RESET operation
within 15 seconds beyond which the bridge audible alarm will commence.

(v) Optional Bridge Movement Detectors (WAS PIR)

The BNWAS reset function is signalled from dual technology


microwave/infrared Movement Detectors which will detect bridge
personnel activity up to a range of 12 metres.

Movement detection will automatically reset / restart the BNWAS timing


period.

Two Movement Detector ports are available which may be connected to a


maximum of 4 Movement Detectors.
NT991BNWAS INSTALLATION & OPERATION

(vi) Optional Officer Cabin Alarm Unit (WAS CA)

The audible Cabin Alarm Unit is also fitted with a red LED and both are
active when the subject cabin has been selected via the Control Unit
Officer Selector Switch and a 2nd Stage (Officer Call) alarm condition
exists. The Cabin Alarm Unit is not fitted with a Reset facility since alarm
reset is only permitted within the Bridge area.

(vii) Optional Masters Cabin Alarm Unit (WAS MCA)

Similar to the standard Officer Cabin Alarm Unit, a visual and audible 2 nd
Stage alarm is produced. However, this unit can be connected as the
Master’s Cabin Alarm and can function as a normal Cabin Alarm Unit or
permanently in parallel with standard Cabin Alarms. When used as a
parallel device, the captain (Master) may switch his Alarm OFF via the
integral switch if not wishing to monitor or be disturbed by other (Duty
Officer) Cabin Alarm Calls.

(viii) Optional Final Stage Alarm Switch/Dist Unit (WAS ADU)

This unit is only required on very large vessel installations (Cruise Ships
etc.) where many 3rd Stage alarms (more than 10) are required in view of
the potentially high number of corridor locations etc. throughout the vessel.

When the WAS ADU is used, the 3rd Stage alarms are supplied
(115/230Vac and/or 24Vdc) and activated via 3 separate channels
available from the Switch/Distribution Unit. Each channel will support up to
10 Alarm Units and is independently fused with additional switch unit
facilities including Power Fail and Tamper Alarm plus Alarm Test – all of
which can be isolated if required via the integral key switch.

(ix) Optional Final Stage Audible Alarms


(Types WAS AU1AC, AU2AC, AU1DC & AU2DC per Sect. 1.6)

The Audible Alarm Units are available in 4 versions to provide two


standard operating voltage levels (12-24Vdc or 230Vac) each of which can
be supplied for sound output levels of 100 or 112dB(A).

(x) Optional Uninterruptible (Emergency Battery) Power Supply

The Navitron NT991 BNWAS is equipped to warn of primary power supply


failures and automatically continue to function from the secondary / back
up supplies connected from the ships power supply system. Further back
up is available when the optional internal battery is fitted within the NT991
BNWAS Distribution Box and will support the system if all external power
supplies fail.

The Basic NT991 BNWAS configuration is shown in Fig. G1.

Optional (additional) components are shown in Fig. G2.

Comprehensive System Configuration is shown in Fig. G3.


NT991BNWAS INSTALLATION & OPERATION

FIG G1 – Basic NT991 BNWAS General System Configuration


Using Non Navitron Audible Alarms.
NT991BNWAS INSTALLATION & OPERATION

FIG G2 – Optional (Additional) NT991 BNWAS Components


Using Navitron Selectors & Alarm Units.
NT991BNWAS INSTALLATION & OPERATION

FIG G3 – Comprehensive System Configuration


NT991BNWAS INSTALLATION & OPERATION

Section 1: Unit Dimensions and Siting.

1.1 Siting the NT991 BNWAS Control Unit.

1.2 Siting the NT991 BNWAS Distribution Unit.

1.3 Siting the Remote Reset Unit (Optional).

1.4 Siting the Officer Cabin Alarm Unit(s).

1.5 Siting the Crew Call (Final Stage) Alarm Switch/Distribution Unit
(Optional).

1.6 Siting the Final Stage Audible Alarm Units.

1.7 Siting the Bridge Visual Alarm Unit (Optional).

1.8 Siting the Movement Detector(s) (Optional).

Installation Note – Radio Frequency Interference (RFI)

The NT991 BNWAS exhibits high levels of RFI rejection and minimal levels of
radiated interference by virtue of careful decoupling, suppression and screening
measures exercised as a standard Navitron Systems design function and is fully
compliant with the statutory requirements of EN60945 (IEC60945).

However, any potential risk of cross coupling should be minimised where possible by
ensuring that BNWAS components and associated cable routing is afforded the
greatest separation possible from high power transmitters, couplers and other RF
carrying cables.

1.1 The NT991 BNWAS Control Unit.


Compass Safe Distance – 0.5m, weight 1.1kg.

The NT991 BNWAS Control / Display unit is not suitable for external location and is
intended for Panel / Console mounting in an enclosed wheelhouse position which is
visible and readily accessible to the OOW.

Furthermore, the unit should be located such that the first stage (15 second) audible
alarm is audible from all operational positions on the bridge where the OOW may
reasonably be expected to be stationed.

(This function may be engineered using one or more sounding devices thus in
addition to the display unit audible alarm, volt free contacts are available in the
Distribution Unit to activate further bridge mounted alarms if required).

The Control / Display unit mounting and outline dimensions are shown in FIG 1.1.
NT991BNWAS INSTALLATION & OPERATION

1.1 The NT991 BNWAS Control Unit … (Continued).

FIG 1.1 – NT991 BNWAS Control Unit Outline and Mounting Dimensions.

1.2 Siting the NT991 BNWAS Distribution Unit.


Compass Safe Distance – 0.5m, weight 4kg.

The NT991 BNWAS Distribution Unit is not suitable for external siting and must be
mounted in an enclosed wheelhouse location.

Since all BNWAS fuses are situated in the Distribution Unit, it should be sited in an
accessible location and consideration should be given to cable routing and
associated cable gland entries.
NT991BNWAS INSTALLATION & OPERATION

1.2 Siting the NT991 BNWAS Distribution Unit … (Continued).

NOTE: If fitted, the Distribution Unit internal battery MUST NOT be mounted in a
permanently inverted position.

FIG 1.2.1 NT991 BNWAS Distribution Unit Outline Dimensions.

1.3 Siting the Remote Reset Unit(s) (If Applicable).


Compass Safe Distance – 0.5m, weight 0.15kg.

The NT990 BNWAS Reset unit is suitable for mounting in Wheelhouse and Bridge
Wing locations in positions which are visible and readily accessible to the OOW.
Outline and mounting dimensions are shown in FIG 1.3.1.

FIG 1.3.1 Reset Unit Outline Dimensions.

Two mounting holes are provided outside of the sealing gasket and are exposed
when the Remote Reset Unit lid is removed.
NT991BNWAS INSTALLATION & OPERATION

1.4 Siting the Officer Cabin Alarm Unit(s).


Compass Safe Distance – 0.1m, weight 0.5kg.

The Cabin Alarm Unit may be a standard (Type WAS CA) or Master`s Cabin
Alarm (Type WAS MCA) which are identical in size and mounting considerations.

The Master`s Cabin Alarm Unit (WAS MCA) will sound simultaneously with all
Officer Call Alarms if connected in parallel with standard Cabin Alarms unless the
Unit is switched “off”. This facility allows the Master to monitor all Duty Officer Cabin
Alarm Calls (if required) or to switch “off” the MCA if wishing to be undisturbed. Since
standard Officer Cabin Alarms are not permitted to be switched “off”, the Master`s
Cabin Alarm Unit (MCA) must only be installed in captains quarters where it is the
prerogative of the Master to switch it “off”. The MCA can also be used as a standard
CA if connected as the first “Master” alarm but the MCA ON/OFF Switch will
automatically be disabled when the MCA is the nominated Cabin Alarm. The switch
will remain operational when other Cabin Alarms are active.

The standard Officer Cabin Alarm Unit (CA) is to be used to call the chosen duty
officer (1st, 2nd, 3rd etc.) thus only the standard Cabin Alarm Unit (WAS CA) is
permitted for this purpose since it is not possible to switch these units “off”.

Both Alarm Unit Types should be mounted in a cabin location and mounting/outline
dimensions are shown in FIG 1.4.1.

FIG 1.4.1 Officer Cabin Alarm Unit(s) - Outline Dimensions.


NT991BNWAS INSTALLATION & OPERATION

1.5 Siting the Crew Call (Final Stage) Alarm Switch/Distribution Unit.
Compass Safe Distance – 0.25m, weight 2.5kg.

The 3rd Stage Switch/Distribution Unit (Type WAS ADU) is only required for very
large vessels and should be internally located in an area convenient from the
viewpoint of available power supplies (24Vdc/115/230Vac) and for cable routing to
the Final Stage Audible Alarm Units (crew areas etc.).

Outline dimensions are shown in FIG 1.5.1.

FIG 1.5.1 Final Stage Alarm Switch Unit Outline Dimensions.

1.6 Siting the Final Stage Audible Alarm Units.


Compass Safe Distance – 0.1m, weight AU1 – 0.25kg, AU2 – 0.7kg.

The Final Stage Audible Alarm Units (AU`s) are available in 100 & 112 dB(A) output
levels suitable for either DC or AC operation. The Alarm Units are available in two
case sizes reflecting the rated sound output level.

A total of 4 Alarm Types are therefore available as follows:-

(i) Type WAS AU1AC = 100 dB for AC operation.


(ii) Type WAS AU2AC = 112 dB for AC operation.
(iii) Type WAS AU1DC = 100 dB for DC operation.
(iv) Type WAS AU2DC = 112 dB for DC operation.

Unless special sealing arrangements are requested, standard enclosures are


suitable for internal mounting only – not in exposed bulkhead or deck locations –
with outline dimensions as shown in FIG 1.6.1.
NT991BNWAS INSTALLATION & OPERATION

FIG 1.6.1 Final Stage Audible Alarm Unit Outline Dimensions.

1.7 Siting the Bridge Visual First Stage Alarm Beacon.


Compass Safe Distance – 0.1m, weight 0.15kg.

The Bridge Visual Alarm Unit (Type WAS BVA) provides a highly visible but night
vision friendly (variable illumination level) indication of Watch Alarm period timeout to
invite manual “Reset”.

The visual Alarm Unit must be internally mounted within the bridge/wheelhouse area
– typically to the deckhead – and dimensions are shown in FIG. 1.7.1.

FIG 1.7.1 Visual Alarm Dimensions.


NT991BNWAS INSTALLATION & OPERATION

1.8 Siting the Movement Detector(s).


Compass Safe Distance – 0.1m, weight 0.15kg.

The Movement Detector(s) (WAS PIR) should be bridge/wheelhouse mounted at a


height of approx 2.5m above deck level, out of direct sunlight where possible and
positioned to detect persons who themselves are in a bridge location enabling them
to maintain a clear and adequate look out. The detection arc and range is approx 90
degrees and 12m respectively. (Dimensions are shown in Fig. 1.8.1).

Note:-
Mounting holes and cable entry
points are accessed by removing the
front cover and quick release PCB for
the knock out locations in the back of
the case.

FIG 1.8.1 WAS PIR Outline


Dimensions.

The movement detection range &


scope of the WAS PIR is shown in
FIG 1.8.2 in Top and Side
aspects.

The Top view (plan view of


wheelhouse area) illustrates a 90o
arc of detection which could be
increased in area if 2 x PIRs were
installed in opposite corners with
overlapping detection areas.

The Side view shows the height of


PIR vs. the wheelhouse deck area
covered.

FIG 1.8.2 WAS PIR Area of


Coverage.
NT991BNWAS INSTALLATION & OPERATION

Section 2: Standard System Cables and Connections.

The System Interconnection Cables are shown in Fig. 2.

Cable size and type are detailed in Table 2.1.

2.1 NT991 BNWAS Cable Routing and Earth Bonding.

2.2 NT991 BNWAS Distribution Unit Connections.

2.3 NT991 BNWAS “Auto” Connection to Navitron Autopilot.

2.4 NT991 BNWAS “Auto” Connection to Proprietary Equipment.

2.5 NT991 BNWAS External Alarm Connections Including Intruder Alarm


Connections.

2.6 NT991 BNWAS Power Fail Alarm Connections.

2.7 Masters (MCA) & Officer Cabin Alarm (CA) Connections.

2.8 Final (3rd) Stage Alarm Connections.

2.9 Final (3rd) Stage Alarm Connections Via Alarm Distribution Unit
NT990BNWAS ADU.

2.10 Tamper Connections.

2.11 1st Stage Bridge Visual Alarm Unit Connections.

2.12 Bridge Movement Detector Connections.

2.13 Optional NT990 BNWAS RST Remote Reset Connections.

2.14 Proprietary Equipment Reset Inputs.

2.15 Proprietary Equipment Emergency Call Input.

2.16 Internal Battery Connection.


NT991BNWAS INSTALLATION & OPERATION

FIG 2 – Standard System Interconnecting Cables.


NT991BNWAS INSTALLATION & OPERATION
2.1 NT991 BNWAS Cable Routing and Earth Bonding.

When routing interconnecting cables, consideration should be given to the remarks


concerning Radio Frequency Interference (RFI) in Section 1. For this reason any
potential risk of cross coupling should be minimised where possible by ensuring that
screened cables are employed throughout and that cable routing is afforded the best
separation possible from transmitter, couplers and other RF associated cables.

Commensurate with the use of screened cables, earth points are fitted to the BNWAS
units to provide cable screen terminations.

Cable Cable Type & Minimum Comment


No. Size
2 Core Screened. Optional 5-40Vdc Auto On/Off control input from
1 2
0.22mm 7/0.2mm. Autopilot etc.
2 Core Screened.
2 2 Optional 5-40Vdc Emergency call input.
0.22mm 7/0.2mm.
6 Core Screened.
3&4 2 Optional PIR / MW movement detectors.
0.22mm 7/0.2mm.
6 Core Screened. Optional Navitron NT990BNWASRST reset
5&6 2
0.22mm 7/0.2mm. units.
2 Core Screened. Optional 5-40Vdc Reset input from Radar,
7&8 2
0.22mm 7/0.2mm. Plotter etc.
2 Core Twisted Pair
Optional IEC61162 $xxEVE / $xxACK input from
9 Screened.
2 central alarm panel.
0.22mm 7/0.2mm.
2 Core Twisted Pair
Optional IEC61162 serial data input. Accepts
10 & 11 Screened.
2 $xxEVE Reset data from proprietary equipment.
0.22mm 7/0.2mm.
2 Core Twisted Pair
Optional IEC61162 $xxALR output to central
12 Screened.
2 alarm panel.
0.22mm 7/0.2mm.
2 Core Twisted Pair
13 Screened. IEC 61162 output to VDR.
2
0.22mm 7/0.2mm.
2 Core Screened.
14 2 Optional power monitor.
0.22mm 7/0.2mm.
2 Core Screened.
15 2 Optional intruder alarm output.
0.5mm 16/0.2mm.
2 Core Screened. Volt free contact to indicate NT991BNWAS
16 2
0.22mm 7/0.2mm. malfunction.
Main power supply to NT991BNWAS system.
2 / 3 Core Screened.
17 2 18-40Vdc or 110/220Vac. Connected via
0.75mm 24/0.2mm.
suitable isolator.
Backup 18-40Vdc power supply to
2 Core Screened.
18 2 NT991BNWAS system. Connected via suitable
0.75mm 24/0.2mm.
isolator.
4 Core Screened.
19 2 Optional bridge audio alarm output
0.5mm 16/0.2mm.
6 Core Screened. Optional Navitron NT990BNWAS BVA bridge
20 2
0.22mm 7/0.2mm. visual alarm.
4 Core Screened. Factory fitted cable to NT991BNWAS Control
21 2
0.5mm 16/0.2mm. Unit.
6 Core Screened.
22 2 Output to Master / Officer Call Alarm.
0.22mm 7/0.2mm.
23, 24, 25, 4 Core Screened. st nd rd th
2 Output to 1 , 2 , 3 & 4 Officer Call Alarms
26 0.22mm 7/0.2mm.
6 Core Screened. rd
27 2 Output to 3 stage (Crew Call) Alarms.
0.5mm 16/0.2mm.

Table 2.1 – NT991 BNWAS Interconnecting Cables.


1 ENABLE +VE (5-40Vdc)
REMOTE ENABLE 1 TAMPER + 100 YELLOW
2 ENABLE –VE
SEE SECTION TAMPER- 99 WHITE
3 IEC61162 ENABLE INPUT A SEE
2.3 OR 2.4 1 CREW 98 BLUE
4 IEC61162 ENABLE INPUT B 27 SECTION
MOTION CALL 97 LINK
SEE 2.8 OR 2.9
EMERGENCY CALL 5 EMER CALL + DETECTOR 2 BATTERY 123 +12V 96 RED
2 LINK 122 SECTION
SEE SECTION 6 EMER CALL – SEE SECTION 0V 95 BLACK
2.16
2.15 2.12
7 +12V TAMPER + 94 YELLOW
RED 4
MOTION 8 0V TAMPER - 93 WHITE
BLACK 3 SEE
DETECTOR 1 BLUE 9 MOTION DET 1 101 +12V 4TH OFFICER 92 BLUE
26
3 RED SECTION
SEE SECTION YELLOW 10 TAMPER - BLACK 102 0V CALL 91
2.7

Fig 2.2.1 NT991 BNWAS DB Connection Details.


2.12 11 TAMPER + 103 MOTION DET 2 +12V 90 RED
WHITE BLUE
NT990 0V 89 LINK
NT991BNWAS INSTALLATION & OPERATION

YELLOW 104 TAMPER –


RED 12 +12V BNWAS RST
WHITE 105 TAMPER +
NT990 BNWAS BLACK 13 0V SEE TAMPER + 88 YELLOW
RST SEE BLUE 14 RESET 1 SECTION TAMPER - 87 WHITE
106 TAMPER LOOP SEE
SECTION 5
WHITE 15 VISUAL 1 2.13 107 TAMPER LOOP 3RD OFFICER 86 BLUE
25 SECTION
2.13 YELLOW 16 TAMPER - CALL 85
2.7
GREEN 17 TAMPER + 6 RED 108 +12V +12V 84 RED
BLACK 0V 83 LINK
109 0V
18 0V BLUE 110 RESET 2
19 +12V WHITE 111 VISUAL 2 TAMPER + 82 YELLOW
EXT RESET
20 EXT RESET 1 + (5-40VDC) YELLOW 112 TAMPER- TAMPER - 81 WHITE
SEE SEE

BRIDGE
7 2ND OFFICER BLUE
2.3 2.2 NT991 BNWAS Distribution Unit Connections.

80

TAMPER +
TAMPER –
EXT RESET 1 –

AUDIO
SECTION 21 GREEN 113 TAMPER + 24 SECTION
5 CALL 79
2.14 22 EXT RESET 2 + (5-40VDC) 2.7
8 +12V 78 RED
23 EXT RESET 2 – 114 TAMPER LOOP

+12V
5 0V 77 LINK
115 TAMPER LOOP

0V
24 IEC61162 INPUT 1 A
9

116
117
118
119
120
121
25 IEC61162 INPUT 1 B TAMPER + 76 YELLOW
5 TAMPER - 75 WHITE
26 IEC61162 INPUT 2 A SEE
10 27 IEC61162 INPUT 2 B 1ST OFFICER 74 BLUE
23 SECTION

2.5
SEE
SECTION
SERIAL CALL 73
28 IEC61162 INPUT 3 A 2.7
INTERFACES 11 +12V 72 RED
29 IEC61162 INPUT 3 B
SEE SECTION 0V 71 LINK
30 IEC61162 OUTPUT 1 B
3.1.6 to 3.1.9

50 +VE BACKUP 18-40VDC


MALFUNCTION
12 31 IEC61162 OUTPUT 1 A
32 ISO GND 1 TAMPER + 70 YELLOW

48 +VE MAIN 18-40VDC

51 -VE SHIP’S SUPPLY


49 -VE SHIP’S SUPPLY
INTRUDER
33 IEC61162 OUTPUT 2 B TAMPER - 69 WHITE
34 IEC61162 OUTPUT 2 A MASTER 68 RED SEE

ALARM

ALARM
13

BRIDGE
VISUAL
35 ISO GND 2 CALL 67 LINK 22 SECTION
OFFICER 66 BLUE 2.7

LED DRIVE

TAMPER +
TAMPER -
46 NEUTRAL
SEE 36 N.C. CALL 65

CLOCK
47 EARTH
37 COM POWER +12V 64 GREEN

DATA
SECTION 14

+12V

+12V
40 COM

43 COM

45 LIVE
MONITOR

41 N.O.

44 N.O.
39 N.C.

42 N.C.
2.6 38 N.O. 0V 63 LINK

0V

0V
52
53
54
55
56
57
58

59
60
61
62
1
2
3
4

NT991BNWAS CU
RED
LINK
BLACK
BLUE

WHITE
YELLOW

CONTROL UNIT
21
3m HALOGEN
FREE LOW
FACTORY FITTED

SMOKE CABLE
15

OR
16

17

17

18

SECTION 2.11
BVA SEE
NT990BNWAS
SUPPLY
(18 – 40Vdc)
SHIP’S BACKUP
SUPPLY
SHIP’S MAIN

(18 – 40Vdc)

20
SUPPLY
SHIP’S MAIN

(115 / 230Vac)
SEE
SECTION
2.5
NT991BNWAS INSTALLATION & OPERATION

2.3 NT991 BNWAS “AUTO” Connection to Navitron Autopilot System.

If used in conjunction with a Navitron Autopilot, the NT991 BNWAS may be configured to
turn on automatically (AUTO operating mode) when the Autopilot is engaged provided
the NT991 BNWAS operating mode has been selected for “AUTO”. Control can be via
analogue voltage level (Sect. 2.3.1) or serial data detection (Sect. 2.3.2).

2.3.1 Analogue “AUTO” Detection / Connections.

The Distribution Unit is equipped with an opto-isolated input port (4 – 40Vdc input voltage
range) which is available for connection to Navitron Autopilot models as shown in FIG
2.3.1 but may only be used in the absence of serial data connection (see 2.3.2).

41 Blue Navitron Autopilot Types


NT921G / NT951G
42 Red NT990G / NT991G

NT991BNWAS 35 Blue Navitron Autopilot Types


DISTRIBUTION UNIT NT921 / NT921MK2
37 Red
+VE 1 Red
ENABLE
INPUT 7 Blue Navitron Autopilot Types
-VE 2 Blue NT920 / NT920G /
10 Red NT925G

33 Blue Navitron Autopilot Types


NT888G
36 Red
Note: DIL switches SW5/2 and SW5/3
located in the distribution unit must be set to
OFF for all Navitron Autopilot types. 19 Blue Navitron Autopilot Types
NT999G
21 Red

FIG 2.3.1 – NT991 BNWAS “AUTO” Analogue Voltage Detection


from Navitron Autopilots.

2.3.2 Serial Data (NMEA 0183) “AUTO” Detection / Connections.

The Distribution Unit is equipped with a serial data input port to detect Navitron Autopilot
status (OFF/ON) via NMEA “HTD” sentence transmission as shown in FIG 2.3.2.

NB. SW5/1 in the Distribution Unit (FIG 3.0) must be set for 4800 baud (SW5/1 OFF)
and SW5/2 must be set to ON.

NT991BNWAS 36 B Blue Navitron Autopilot Types


DISTRIBUTION UNIT NT951G / NT991G
37 A Red
IEC61162 A 3 Red
ENABLE 98 B Blue Navitron Autopilot Types
INPUT NT888G
B 4 Blue
A Red
99

89 B Blue Navitron Autopilot Types


NT999G
90 A Red

FIG 2.4.2 – NT991 BNWAS “AUTO” Serial Data Detection


from Navitron Autopilots.
NT991BNWAS INSTALLATION & OPERATION

2.4 NT991 BNWAS “AUTO” Connection to Proprietary Equipment.

If automatic activation of the BNWAS is required when other equipment (proprietary


Autopilot system etc.) is made active, this can be achieved by BNWAS detection of
analogue voltage level or serial data received from controlling equipment as shown in
FIG 2.4.1 or 2.4.2 as appropriate.

2.4.1 Analogue Auto Detection from Proprietary Equipment.

The Distribution Unit is equipped with an opto-isolated input port which is polarity
conscious and will respond to an analogue signal voltage level from 4 – 40Vdc as a
remote ‘ON’ command provided the BNWAS operating mode selected is ‘AUTO’.
Note: SW5/2 must be set ‘OFF’. If the
proprietary equipment ‘ON’ condition
corresponds to a HIGH signal level (+ve
NT991BNWAS
DISTRIBUTION UNIT
logic) SW5/3 in the BNWAS DB must be PROPRIETARY EQUIPMENT
set to ‘ON’.
+VE 1 +VE Remote “ON”
ENABLE command to
INPUT BNWAS
-VE 2 -VE (4-40Vdc)

FIG 2.4.1.1 – ‘AUTO’ ON Analogue Voltage Connection to Proprietary Equipment.


Note: SW5/2 must be set ‘OFF’. If
NT991BNWAS the proprietary equipment ‘ON’
DISTRIBUTION UNIT
condition corresponds to a ‘CLOSED‘
+VE 1 contact SW5/3 in the BNWAS DB
ENABLE must be set to ‘ON’. PROPRIETARY EQUIPMENT
INPUT -VE 2
Remote “ON” volt
+12V 7 free contact to
BNWAS
0V 8

FIG 2.4.1.2 – ‘AUTO’ ON Volt Free Contact Connection to Proprietary Equipment.

2.4.2 Serial Data (NMEA) Auto Detection from Proprietary Equipment.

Suitable IEC61162 sentences (i.e. $ - -HTD etc) which contain ON/OFF status fields can
be accepted by the BNWAS from proprietary equipment for remotely controlled BNWAS
ON/OFF functions provided the BNWAS operating mode is set to ‘AUTO’.

Note: SW5/2 in the BNWAS Dist. Unit must be set ‘ON’ when NMEA data is used for
‘AUTO’ activation. SW5/1 located in the BNWAS Distribution Unit must be set to ‘OFF’
for 4800 baud and ‘ON’ for 38400. baud sentences.
NT991BNWAS
PROPRIETARY EQUIPMENT
DISTRIBUTION UNIT
3 A
IEC61162 A
IEC61162
ENABLE
OUTPUT
INPUT B
4
B

FIG 2.4.2 – NT991 BNWAS ‘AUTO’ ON Serial Data Connection


to Proprietary Equipment.
NT991BNWAS INSTALLATION & OPERATION

2.5 NT991 BNWAS External Alarm Connections.

The BNWAS is equipped with 10 independent relay operated normally open (N/O)
contacts. These close to provide switchlines to the appropriate visual/audible alarm
which, dependent on type, may be bridge or remotely located.

NT991BNWAS DISTRIBUTION UNIT


ALARM TERMINALS

N.C.
42
SYSTEM SYSTEM MALFUNCTION ALARM CONTACT
MALFUNCTION 43 TO CENTRAL ALARM PANEL ETC. IF
ALARM REQUIRED.
44
N.O.

BRIDGE 55 POWER SUPPLY


VISUAL
56 BRIDGE VISUAL ALARM (BRIDGE VIEWABLE ONLY)

118 POWER SUPPLY


BRIDGE
AUDIO
119 BRIDGE AUDIO (BRIDGE AUDIBLE ONLY)

OFFICER 65 POWER SUPPLY


CALL (ALL)
66 OFFICER CALL (MASTER CABIN)

MASTER 67 POWER SUPPLY


CALL
68 MASTER CALL (MASTER CABIN)

1ST OFFICER 73 POWER SUPPLY


CALL
74 1ST OFFICER CALL

2ND OFFICER 79 POWER SUPPLY


CALL
80 2ND OFFICER CALL

3RD OFFICER 85 POWER SUPPLY


CALL
86 3RD OFFICER CALL

4TH OFFICER 91 POWER SUPPLY


CALL
92 4TH OFFICER CALL

97 POWER SUPPLY
CREW CALL
98 CREW CALL (CREW QUARTERS ETC.

All Alarm contacts are rated 1A @ 30Vdc/220VAC.


NT991BNWAS INSTALLATION & OPERATION

2.5 NT991 BNWAS External Alarm Connections…(Continued).

Intruder Alarm Changeover Contacts.

NT991BNWAS DISTRIBUTION UNIT Intruder alarm contact changes state if the


intruder alarm is active and an intruder is
N.C. detected.
39
INTRUDER
ALARM 40 Note: the volt free contacts may be
TERMINALS connected in parallel with any other
41
N.O. contact pair to sound the appropriate alarm
(master, 1st officer etc.) or alternatively can
be used to activate a dedicated alarm.

2.6 NT991 BNWAS Power Fail Alarm Connections.

NT991BNWAS DISTRIBUTION UNIT

N.C. A power supply monitoring relay


36 provides a single pole closing or
POWER opening contact in the event of
MONITOR 37
complete power supply failure.
TERMINALS
38
N.O.
Contacts rated 1A @ 30Vdc/220VAC

2.7 Master (MCA) & Officer Cabin Alarm (CA) Connections.

Cables 22 to 26 provide alarm switchlines between the bridge mounted Distribution Unit
and the appropriate Officer Cabin Alarm Unit which may be a Masters Cabin Alarm
Monitor Unit (5 core cable) or a standard Officer Cabin Alarm Unit (4 core cable).

FIG 2.7.1 - NT990 BNWAS Officer Cabin Alarm Unit Connections.


NT991BNWAS INSTALLATION & OPERATION

2.8 Final (3RD) Stage Alarm Connections.

The Final (3rd) Stage Alarm Distribution Unit (BNWAS ADU) is required if more than 10 x
final stage audible alarm units are to be connected or if the final stage alarms are
required to be A.C. types, see Section 2.9 for ADU connections. If less than 10 x d.c final
stage audible alarms are required these are connected directly to NT991BNWAS DB
cable 27 as shown below.

Fig 2.8.1 100dB(A) D.C. Alarm Fig 2.8.2 112dB(A) D.C. Alarm

Multiple 3rd stage alarm units (10 max) are connected as shown in Fig 2.8.3

ALARM UNIT 1 ALARM UNIT ALARM UNIT


2, 3, 4 etc. LAST

1 2 3 + - 1 2 3 + - 1 2 3 + -
RED

RED

RED
BLUE

BLUE

BLUE
WHITE

WHITE

WHITE
YELLOW

YELLOW

YELLOW

YELLOW

YELLOW

Cable 27 from
NT991BNWAS
DB

Fig 2.8.3 Multiple Alarm Unit Connections to NT991BNWAS DB

2.9 Final (3RD) Stage Alarm Distribution Unit (ADU) Connections (Optional).

Cable 27 from the Distribution Box (DB1 or DB2) provides the 3 rd (Final) Stage Alarm
switchline which is routed to the Final Stage Alarm Units via the 3 rd Stage Alarm
Distribution Unit when more than 10 3rd stage alarms required or if A.C. type alarms are
necessary.

NT990BNWAS ADU connections are shown in Fig 2.9.


NT991BNWAS INSTALLATION & OPERATION

FIG 2.9 - Final Stage Alarm Distribution Unit (ADU) Connections.

2.9.1 Final Stage 100dB(A) Audible Alarm Unit Cables and Connections.

FIG 2.9.1 - DC or AC 100dB(A) Audible Alarm Unit Connections.


NT991BNWAS INSTALLATION & OPERATION

2.9.2 Final Stage 112dB(A) Audible Alarm Unit Cables and Connections.

FIG 2.9.2 - DC or AC 112dB(A) Audible Alarm Connections.

2.9.3 Final (3rd) Stage Alarm Distribution Unit (ADU) Tamper Connections.

The Final Stage Switch Unit will support 3 independent alarm output channels, each of
which may support up to 10 audible Alarm Units (30 Final Stage Alarm Units).

ADU Terminals Audible Alarm Unit Terminals

(Alarm Channel 1) (Alarm Unit No. 1a, 1b, 1c, 1d etc.)


Term 16 = Tamper OUT To 3 way Tamper Terminal Block
Term 17 = Tamper IN (Nos. 1-3) as shown in FIG 2.9.3

(Alarm Channel 2) # (Alarm Unit No. 2a, 2b, 2c, 2d etc.)


Term 21 = Tamper OUT To 3 way Tamper Terminal Block
Term 22 = Tamper IN (Nos. 1-3) as shown in FIG 2.9.3

(Alarm Channel 3) # (Alarm Unit No. 3a, 3b, 3c, 3d etc.)


Term 26 = Tamper OUT To 3 way Tamper Terminal Block
Term 27 = Tamper IN (Nos. 1-3) as shown in FIG 2.9.3

NOTE: As all Tamper Loop terminals must provide series continuity, if less than 3 ADU
alarm channels are used, the vacant Tamper terminals must provide continuity via
jumper links as shown in FIG 2.9.3:-
NT991BNWAS INSTALLATION & OPERATION

FIG 2.9.3 – Final Stage Audible Alarm Unit Tamper Connections.

2.9.4 Optional External Dimmer Connections.

The Final (3rd) Stage Switch Unit is fitted with an independent dimmer control but may be
converted by jumper link adjustment to accept control from an external dimmer
potentiometer. Connections and associated jumper link positions are shown below:-

FIG 2.9.4 – Final (3rd) Stage ADU Optional External Dimmer Control.
NT991BNWAS INSTALLATION & OPERATION

2.10 Tamper Connections.

The integrity of the BNWAS is protected by anti tamper measures to warn of cover / lid
removal or severed cables involving Distribution Unit, Remote Reset Unit(s) Alarm Units,
Movement Detectors, Officer Alarm Selector Switch, Officer Cabin Alarm Units, Final (3 rd)
Stage Alarm Distribution Unit(s) and Final Stage Audible Alarm Units.

The Tamper Loop series circuit is based on lid removal microswitch detection of break in
continuity of the 5Vdc current limited supply derived from various dedicated Tamper
terminals within the DB. The Distribution Unit Tamper circuit is shown in FIG 2.10.
Unused Tamper Terminals must be linked to complete the Tamper Loop.
NT991BNWAS DISTRIBUTION UNIT
+5V

TO
MONITOR 113 NT990BNWAS
CIRCUIT RST RESET 2
INTERNAL 112 TAMPER
TAMPER
SWITCH
17 NT990BNWAS
RST RESET 1
16 TAMPER
NOTE: Terminals 106
106, 107, 114 & 115 105 WAS/PIR MOTION
have no connection DETECTOR 2
107 104 TAMPER
in the NT991BNWAS
DB and are provided
to allow tamper 114 11 WAS/PIR MOTION
connection to DETECTOR 1
multiple units to be 115 10 TAMPER
looped in and out.
100
CREW CALL
99 TAMPER

94 TH
4 OFFICER
93 TAMPER

88 RD
3 OFFICER
87 TAMPER

82 ND
2 OFFICER
81 TAMPER

76 ST
1 OFFICER
75 TAMPER

70
MASTER / OFFICER
69 TAMPER

121
BRIDGE AUDIO
120 TAMPER

58
BRIDGE VISUAL
57 TAMPER
0V

FIG 2.10 – Distribution Unit Tamper Circuit.


NT991BNWAS INSTALLATION & OPERATION

2.11 1st Stage Bridge Visual Alarm Unit Connections.

Cable 20 from the BNWAS Distribution Unit (DB) is connected to the visual alarm as
shown.

FIG 2.11 – Visual alarm Unit Connections.

2.12 BNWAS Bridge Located Movement Detector (WAS PIR) Connections.

Two Movement Detector Units may be used and are connected to the BNWAS cable(s) 3
& 4.

The Detector covers are “clickfit” and secured with a screw at the bottom, the PCB
mounted terminals are exposed when the cover is removed for connection as shown in
FIG 2.12.

Cable 3 NT991BNWAS / DB Cable 4 NT991BNWAS / DB

FIG 2.12 – BNWAS Movement Detector (WAS PIR) Connections.


NT991BNWAS INSTALLATION & OPERATION

2.13 NT990 BNWAS Reset Unit Connections.

Up to 6 NT990BNWAS RST reset units can be connected to the Distribution Unit,


see Figs 2.13.1 to 2.13.6 below for connection details:-
NT990BNWAS
NT991BNWAS DB DISTRIBUTION UNIT RESET UNIT

+12V 12 RED RED 1


NOTE: Link unused +12V
NT991BNWAS DB 0V 13 BLACK BLACK 2
0V
tamper terminals 112
RESET 1 14 BLUE WHITE 3
& 113 (any other VISUAL 1
unused tamper VISUAL 1 WHITE Cable 5
15 BLUE 4
terminals must also be RESET 1
TAMPER 16 YELLOW YELLOW
linked, Section 2.10). 5 TAMPER
TAMPER 17 GREEN GREEN 6 TAMPER

FIG 2.13.1 – Single Reset Unit Connection to Distribution Unit.

NT991BNWAS
DISTRIBUTION UNIT NT990BNWAS RESET UNIT 1

+12V 12 RED RED 1 +12V


0V 13 BLACK BLACK 2 0V

RESET 1 14 BLUE WHITE 3 VISUAL

VISUAL 1 WHITE Cable 5


15 BLUE 4 RESET
TAMPER 16 YELLOW YELLOW TAMPER
5
TAMPER 17 GREEN GREEN TAMPER
6

+12V 108 RED NT990BNWAS RESET UNIT 2

109 RED 1 +12V


0V BLACK
BLACK 2 0V
RESET 2 110 BLUE

VISUAL 2 111 WHITE WHITE 3 VISUAL

TAMPER 112 YELLOW BLUE 4 RESET


Cable 6
TAMPER 113 GREEN YELLOW 5 TAMPER

GREEN 6 TAMPER

Fig 2.13.2 Dual NT990BNWAS RST Reset Unit Connections.


NT991BNWAS INSTALLATION & OPERATION

2.13 NT990BNWAS RST Reset Unit Connections to Distribution Unit… (Continued).


Cable 5A
NT991BNWAS NT990BNWAS NT990BNWAS
DISTRIBUTION UNIT RESET UNIT 1 RESET UNIT 2

+12V 12 RED RED 1 +12V RED 1 +12V

0V 13 BLACK BLACK 2 0V BLACK 2 0V


RESET 1 14 BLUE WHITE 3 VISUAL WHITE 3 VISUAL

VISUAL 1 15 WHITE BLUE 4 RESET BLUE 4 RESET

TAMPER - 16 YELLOW YELLOW TAMPER YELLOW TAMPER


5 5
TAMPER + 17 GREEN GREEN TAMPER GREEN TAMPER
6 6
GREEN Cable 5B
TAMPER LOOP 114
YELLOW
NT990BNWAS
+12V 108 RED Cable 6 RESET UNIT 3

0V 109 BLACK
RED 1 +12V
RESET 2 110 BLUE 2
BLACK 0V
VISUAL 2 111 WHITE
WHITE 3 VISUAL
TAMPER - 112 YELLOW
BLUE 4 RESET
TAMPER + 113 GREEN
YELLOW 5 TAMPER

TAMPER LOOP 115 GREEN 6 TAMPER

Fig 2.13.3 Triple NT990BNWAS RST Reset Unit Connections.

Cable 5A
NT991BNWAS NT990BNWAS NT990BNWAS
DISTRIBUTION UNIT RESET UNIT 1 RESET UNIT 2

+12V 12 RED RED 1 +12V RED 1 +12V

0V 13 BLACK BLACK 2 0V BLACK 2 0V


RESET 1 14 BLUE WHITE 3 VISUAL WHITE 3 VISUAL

VISUAL 1 15 WHITE BLUE 4 RESET BLUE 4 RESET

TAMPER - 16 YELLOW YELLOW TAMPER YELLOW TAMPER


5 5
TAMPER + 17 GREEN GREEN TAMPER GREEN TAMPER
6 6
GREEN
TAMPER LOOP 114 Cable 5B
YELLOW

Cable 6A
NT990BNWAS NT990BNWAS
+12V 108 RED RESET UNIT 3 RESET UNIT 4

0V 109 BLACK
RED 1 +12V RED 1 +12V
RESET 2 110 BLUE 2 2
BLACK 0V BLACK 0V
VISUAL 2 111 WHITE
WHITE 3 VISUAL WHITE 3 VISUAL
TAMPER - 112 YELLOW
BLUE 4 RESET BLUE 4 RESET
TAMPER + 113 GREEN
YELLOW 5 TAMPER YELLOW 5 TAMPER
GREEN GREEN TAMPER GREEN TAMPER
TAMPER LOOP 115 6 6
YELLOW
Cable 6B

Fig 2.13.4 Quad NT990BNWAS RST Reset Unit Connections.


NT991BNWAS INSTALLATION & OPERATION

2.14 Proprietary Equipment Reset Inputs.

The NT991BNWAS DB is equipped with two analogue input ports to accept d.c. or
volt free contact RESET signals from proprietary equipment conveniently located
bridge / wheelhouse work stations as required. The inputs are opto isolated to
eliminate common mode problems and will operate over an applied signal voltage
range of 4-40Vdc.

The inputs will only respond to a signal demand each time the related remote
switch is operated thus a permanently closed switch contact will not produce a
permanent Reset condition. Connection details are shown in Fig 2.14.1 and 2.14.2.

NT991BNWAS
DISTRIBUTION UNIT PROPRIETARY EQUIPMENT

+VE 20 +VE Remote


RESET 1 “RESET”
-VE 21 -VE command to
BNWAS
PROPRIETARY EQUIPMENT (4-40Vdc)

+VE 22 +VE Remote


RESET 2 “RESET”
-VE 23 -VE command to
BNWAS
(4-40Vdc)

Fig 2.14.1 Proprietary Reset (Signal Voltage Type) Connections.

NT991BNWAS PROPRIETARY EQUIPMENT


DISTRIBUTION UNIT
Remote “RESET”
0V 18 volt free contact
to BNWAS
+12V 19

+VE
RESET 1 20
-VE PROPRIETARY EQUIPMENT
21
Remote “RESET”
volt free contact
+VE to BNWAS
22
RESET 2
-VE
23

Fig 2.14.2 Proprietary Reset (Volt Free Contact Type) Connections.

2.15 Proprietary Equipment Emergency Call Input.

The NT991BNWAS DB is equipped with an analogue input port to accept a d.c.


signal or volt free contact from proprietary equipment to summon the backup officer
to the bridge. The input is opto isolated to eliminate common mode problems and
will operate over an applied signal voltage range of 4-40Vdc.
NT991BNWAS INSTALLATION & OPERATION

2.15 Proprietary Equipment Emergency Call Input... (Continued).

The inputs will only respond to a signal demand each time the related remote
switch is operated thus a permanently closed switch contact will not produce a
permanent emergency call condition. The input can be configured via distribution
unit DIL switch SW4/4 (see Section 3.1.4 for details) to trigger on either the
presence (positive logic) or absence (negative logic) of a voltage signal. Connection
details are shown in Fig 2.15.1, 2.15.2 & 2.15.3.

NT991BNWAS DISTRIBUTION UNIT


PROPRIETARY EQUIPMENT

+VE 5 +VE Remote “Emergency


EMERGENCY Call” command to
CALL -VE -VE BNWAS (4-40Vdc)
6
-
VE

Fig 2.15.1 Proprietary Emergency Call (Signal Voltage Type) Connections.

PROPRIETARY EQUIPMENT
NT991BNWAS DISTRIBUTION UNIT
Remote “Emergency
Call” normally open
+VE 5 volt free contact
EMERGENCY to BNWAS
CALL -VE 6

NOTE: Set DIL 7 PROPRIETARY EQUIPMENT


+12V
switch SW4/4
OFF. 8 Remote “Emergency
0V
Call” normally open
volt free contact
to BNWAS

Fig 2.15.2 Proprietary Emergency Call (N.O. Volt Free Contact Type) Connections.

PROPRIETARY EQUIPMENT
NT991BNWAS DISTRIBUTION UNIT
Remote “Emergency
Call” normally closed
+VE 5 volt free contact
EMERGENCY to BNWAS
CALL -VE 6

NOTE: Set DIL 7 PROPRIETARY EQUIPMENT


+12V
switch SW4/4
ON. Remote “Emergency
0V 8
Call” normally closed
volt free contact
to BNWAS

Fig 2.15.3 Proprietary Emergency Call (N.C. Volt Free Contact Type) Connections.

2.16 Internal Battery Connection.

The optional internal battery is connected to the system by linking terminals 122 &
123. (See Fig. 2.2.1).

The battery must only be connected to the system once all wiring has been
completed.
NT991BNWAS INSTALLATION & OPERATION

Section 3: The NT991 BNWAS Installation Presets.

3.0 - Distribution Unit Location of Switches & Links

3.1 BNWAS Distribution Unit DIL Switch Presets.

1. DIL Switch SW1. Baud Rate (Data 1 In/Out) Movement Detect


Function & Serial Data Format.

2. DIL Switch SW2. Baud Rate (Data 2 In/Out) Reset, VDR &
Emergency Call.

3. DIL Switch SW3. Baud Rate (Data 3 In), Internal Battery


Monitor, External Backup Power Monitor, Max Officer Select
Number.

4. DIL Switch SW4. Extended Officer Call Response Time,


Combined Officer Call Response Time, Emergency Call Input
Setup.

5. DIL Switch SW5. Remote BNWAS ‘AUTO’ Enable (IEC61162


Data), Remote BNWAS ‘AUTO’ Enable (Analogue Voltage
Signal), Intruder Alarm Enable.

6. Central Alarm Panel Serial Data Interface.

7. Proprietary Equipment Alarm & Reset Serial Interfaces.

8. IEC 62616 Dedicated $BNALR Output.

9. Serial Communication Summary.

3.2 BNWAS Distribution Unit Selector Switches & Links.

115V/230VAC Power Supply Selector (All BNWAS Configurations).

3.3 BNWAS Control / Display Unit Presets.

Tone Selection / Volume Adjustment.

3.4 115V/230VAC Power Supply Selector


(3RD Stage ADU Switch Unit – Expanded Systems).

3.5 Officer Cabin Alarm Volume and Tone Selection.

3.6 Final Stage Alarms (100dB(A)) Tone Selection.

3.7 Final Stage Alarms (112dB(A)) Tone Selection.


NT991BNWAS INSTALLATION & OPERATION

Installation Introduction.

MSC.128(75) & IEC 62616 define that the BNWAS shall provide visual and
audible alarm stages at fixed intervals geared to the period (3 to 12 minutes)
selected by the Master/OOW.

The Bridge Visual Alarm (BNWAS Main Unit & optional BVA) intensity is
adjustable via the BNWAS Control Unit illumination key. The 1st Stage Bridge
Audible Alarm must be installation adjustable for tone and volume to ensure
its effectiveness against background noise and/or other bridge alarm
functions, this is facilitated by installation adjustable presets.

This also applies to the tone & volume and presets that are also incorporated
in Navitron Officer Cabin and Final Stage Alarm Units.

In some cases (larger vessels etc.) it may be necessary to extend the


response time to the ‘Officer Call’ alarm stage (normally 90 seconds) to a
maximum of 3 minutes whereas in vessels other than passenger vessels, the
Officer and Crew Call alarms may be combined to sound in all locations at the
same time.

Accordingly, BNWAS presets for alarm time extension, backup power supply,
internal battery monitoring and serial alarm data adjustments are available in
the Distribution Unit.

An AC power supply selector switch (115/230VAC) is located in the Final


Stage Switch Unit (WAS ADU in expanded systems only) and must be set as
appropriate.
NT991BNWAS INSTALLATION & OPERATION

3.0 - Distribution Unit Location of Switches & Links

DIL Switch DIL Switch DIL Switch DIL Switch


DIL Switch SW3 SW4
SW2 SW5
SW1
LED5

SW6 Main supply input


voltage selection 115 /230Vac

FIG 3.0 - NT991BNWAS Distribution Unit Location Installation Switches


NT991BNWAS INSTALLATION & OPERATION

3.1 BNWAS Distribution Unit DIL Switch Presets.

The Distribution Unit has a total of five 4-way DIL switches (see Fig 3.0 for
switch location).

Switches SW1, SW2 & SW3 allow various Serial Data format adjustments to
be made between proprietary bridge work stations (Resets from Radar,
ECDIS etc.) dialogue with Central Alarm Panel, VDR, Emergency Call Alarm
(immediate or 30 seconds delayed) and Movement Detector function (AND`d
or OR`d).

AND = Both Movement Detectors detecting movement (within 10 seconds of


each other) to reset timing period.

OR = Only one or other of the Movement Detectors detecting movement to


reset.

Switches SW4 & SW5 allow the following to be adjusted: 3 rd stage delay time,
auto enable type / polarity , emergency call polarity and intruder alarm enable.

Refer to Fig. 3.0 for location of the switches.

3.1.1 SW1 Parameters (Serial Data Input/Output No.1).

Switch SW1
Pole Function OFF ON
1 Baud Rate Serial input/output 1. 4800 Baud 38K4 Baud
(Central Alarm Panel)
2 Movement detector function. OR’d AND’d
3 Serial output 1 mode. Central Alarm VDR mode
Panel mode
4 Function of receipt $xxACK ACK reset ACK reset
sentence from Central Alarm Panel disable enable

(See 3.1.6 to 3.1.8 for Central Alarm Panel, proprietary Reset equipment and
dedicated BNWAS Alarm (ALR) & VDR Serial Data Sentence formats).

3.1.2 SW2 Parameters (Serial Data Input / Output No. 2).

Switch SW2
Pole Function OFF ON
1 Baud Rate Serial input/output 2. 4800 Baud 38K4 Baud
(VDR)
2 ALR to “Emergency call” alarm time ALR alarm ALR 30 sec
immediate delay
3 VDR “Heart Beat” Output Disabled Enabled
4 Not Used

(See 3.1.6 to 3.1.8 for Central Alarm Panel, proprietary Reset equipment and
dedicated BNWAS Alarm (ALR) & VDR Serial Data Sentence formats).
NT991BNWAS INSTALLATION & OPERATION

3.1.3 SW3 Parameters (Serial Data Input No. 3).

Switch SW3
Pole Function OFF ON
1 Baud Rate Serial input 3. 4800 Baud 38K4 Baud
2 Internal Battery Monitor Enable Disabled Enabled
3 External Backup Power Monitor Disabled Enabled
4 Max Officer Number Calibration Set max
number

(See 3.1.6 to 3.1.8 for Central Alarm Panel, proprietary Reset equipment and
dedicated BNWAS Alarm (ALR) & VDR Serial Data Sentence formats).

3.1.4 SW4 Parameters.

Switch SW4
Pole Function OFF ON
1 +60 Seconds 3rd Stage Delay Add 0 Add 60sec
2 +30 Seconds 3rd Stage Delay Add 0 Add 30 sec
3 Combine 2nd & 3rd Stage (3rd Stage Disabled Enabled
Delay =0)
4 Emergency Call D.C input polarity Positive Negative

3.1.5 SW5 Parameters.

Switch SW5
Pole Function OFF ON
1 Baud Rate Auto Enable Serial 4800 Baud 38K4 Baud
Input.
2 Auto Enable Mode D.C. Voltage Serial Data
Control Control
3 Auto Enable D.C. Input Polarity Negative Positive
4 Intruder Alarm Enable Disabled Enabled
NT991BNWAS INSTALLATION & OPERATION

3.1.6 Central Alarm Panel Serial Data Interface.

The NT991 BNWAS provides an IEC61162 compliant ALR and ACK data
interface for alarm status information exchange between the BNWAS and
central alarm panel.

The NT991 BNWAS will transmit the following sentences on Channel 1 Output
(Terminals 30 & 31) to the Central Alarm Panel provided SW1/3 is set “OFF”
(See 3.1.1) if the relevant alarm condition occurs:-

Alarm Sentence transmitted.


Bridge Visual $BNALR,,000,a,b,BNWAS Bridge Visual*hh
Bridge Audible (Stage 1) $BNALR,,000,a,b,BNWAS Bridge Audible*hh
Officer Call (Stage 2) $BNALR,,000,a,b,BNWAS Officer Call*hh
Crew Call (Stage 3) $BNALR,,000,a,b,BNWAS Crew Call*hh
Tamper $BNALR,,001,a,b,BNWAS Tamper*hh
Main Power Fail $BNALR,,002,a,b,BNWAS Main Fail*hh
Backup Power Fail $BNALR,,003,a,b,BNWAS Backup Fail*hh
System Fail $BNALR,,004,a,b,BNWAS System Fail*hh
Intruder Alarm $BNALR,,010,a,b,BNWAS Intruder*hh

Where “a” in the sentence defined above is “A” if the alarm is active and “V” if
it is inactive.

Where “b” in the sentence defined above is “A” if the alarm has been
acknowledged by the central alarm panel and “V” if it is unacknowledged.

An alarm sentence is transmitted on change of state of any alarm. Once


triggered, an alarm sentence will continue to be transmitted until it is inactive
and has been acknowledged by the central alarm panel (via the $xxACK
sentence to Channel 1 input terminals 24 & 25).

If no change of state of alarms occurs an alarm list will be transmitted every


60 seconds. If there are no active or unacknowledged alarms then the “No-
alerts” message ($BNALR,,,V,V,*hh) is sent every 60 seconds.

If Switch 1 pole 4 is ON then receipt of the $xxACK sentence is assumed to


be a result of operator activity at the central alarm panel and will automatically
reset the BNWAS.

If the BNWAS receives an active un-acknowledged $xxALR sentence from the


central alarm panel the BNWAS will generate an “Emergency Call” alarm and
therefore summon backup officer assistance. If switch 2 pole 2 is on there will
be a 30 second delay before the “Emergency Call” alarm is activated. If an
inactive $xxALR sentence is received by the BNWAS during the 30 second
delay period, the alarm demand will be cancelled and no “Emergency Call”
alarm will be generated.
NT991BNWAS INSTALLATION & OPERATION

3.1.7 Proprietary Equipment Alarm & Reset Serial Interfaces.

The BNWAS alarms will be reset on receipt of the $xxEVE,,BNWAS,Operator


activity*hh(CR)(LF) sentence on serial data inputs 1, 2 or 3 (Terminals 24/25,
26/27 or 28/29).

If an active un-acknowledged $xxALR sentence is received on serial input 2


the BNWAS will generate an “Emergency Call” alarm and therefore summon
backup officer assistance. If switch 2 pole 2 is on there will be a 30 second
delay before the “Emergency Call” alarm is activated. If an inactive $xxALR
sentence is received by the BNWAS during the 30 second delay period, the
demand will be cancelled and no “Emergency Call” alarm will be generated.

3.1.8 IEC 62616 Dedicated $BNALR Output.

The NT991 BNWAS provides an IEC62616 compliant $BNALR data output for
VDR use on Channel 2 (terminals 33 & 34) and will transmit the following
baud rate adjustable sentences (SW2/1) if the relevant alarm condition or
BNWAS status change occurs:-

NOTE: If Channel 2 VDR heartbeat output is enabled (SW2/3 set to ON) then
the last transmitted sentence is repeated at 60 second intervals.

$BNALR,,xxx,a,b,c----c*hh

Where:-
xxx: Designation of source of alarm or source of reset command.

000 – Normal 007 – IEC61162 Reset Source


001 – Tamper Alarm 008 – DC Reset Source
002 – Main Power Fail Alarm 009 – Motion Detector Reset Source
003 – Backup Power Fail Alarm
004 – System Fail Alarm
005 – CU Reset Source
006 – NT990 BNWAS RST Reset Source

a: A = Dormant period exceeded, V = Dormant period not


exceeded

b: A = Alarm acknowledged, V = Alarm unacknowledged

c - - c: BNWAS mode: c1; c2; c3


c1 = AUT or MAN or OFF
c2 = Dormant period in min, (03 – 12)
c3 = Alarm stage: 1, 2 or 3.

Example: $BNALR,,000,A,V,C1=AUT;C2=03;C3=1*hh

NOTE: This data is also available from Channel 1 output when SW1/3 is set
to VDR mode (See 3.1.1).
NT991BNWAS INSTALLATION & OPERATION

3.1.8 IEC 62616 Dedicated $BNALR Output … (Continued).

In addition to the IEC62616 compliant $BNALR data output defined above the
following sentence is also transmitted on Channel 2.

Alarm Sentence transmitted.


Intruder $BNALR,,010,a,b,BNWAS Intruder*hh

3.1.9 Summary Block Diagram of Serial Communication Input / Output


Functions.

In simplified terms, in addition to the Auto Mode Enable serial input the DB is
a three channel serial data device which allows the BNWAS to interface with
ships Central Alarm Panel, VDR, Radar and ECDIS etc. work stations and to
accept via additional serial data inputs, Remote Reset instruction from bridge
located Reset Units.

In addition to the serial data inputs, analogue inputs allow reset from
Movement Detectors (PIR) and two further 5-40Vdc isolated inputs.

A third isolated 5-40Vdc analogue input is available for Emergency Call use.

Channel 1, 2 & 3 input / output sentence types are shown in Fig. 3.1.9.

NT991BNWAS DB CENTRAL
$BNALR*, $BNACK ALARM
(Terminals 30, 31, 32) CH1 TX PANEL
$xxALR*, $xxACK, $xxEVE
(Terminals 24, 25) CH1 RX

$BNALR**, $BNACK
(Terminals 33, 34, 35) CH2 TX ECDIS
$xxALR, $xxEVE
(Terminals 26, 27) CH2 RX

VDR

(Terminals 28, 29) CH3 RX


$xxEVE (Operator activity
reset)
RADAR ETC.

* CH1 - $BNALR output sentence structure is set by DIL switch SW1/3, see Sections 3.16 & 3.18.

* CH2 - $ BNALR output sentence structure is defined in Section 3.18

FIG 3.1.9 – NT991 BNWAS Input / Output Sentence Types.


NT991BNWAS INSTALLATION & OPERATION

3.1.9 IEC 62616 Serial Data (IEC 61162 Format) … (Continued).

Channel 1 Transmit - $BNALR – Selectable for Central Alarm Panel


(Section 3.1.6) or VDR (Section 3.1.8) use. Central
Alarm Mode requires $BNALR sentences to be
acknowledged by the $xxACK sentence.

$BNACK - Sent on receipt of $xxALR from


proprietary equipment such as Central Alarm Panel
etc.

Channel 1 Receive - $xxALR – If received as an active and


unacknowledged sentence, an Officer Call Alarm will
be generated either immediately or after 30 second
delay (DIL Switch SW2/2).

$xxACK – Acknowledges a $BNALR sentence if in


Central Alarm Panel Mode or resets the BNWAS
Alarms on receipt of $xxACK per DIL Switch SW1/4
setting.

$xxEVE – Signals operator activity to the BNWAS to


generate an alarm reset condition.

Channel 2 Transmit - $BNALR – VDR Mode only (Section 3.1.8) to send


status data to proprietary equipment.

$BNACK – Acknowledgement sent on receipt of


$xxALR from proprietary equipment.

Channel 2 Receive - $xxALR – If received as an active and


unacknowledged sentence, an Officer Call Alarm will
be generated either immediately or after 30 seconds
delay (DIL Switch SW2/2).

$xxEVE – Signals operator activity to the BNWAS to


generate an alarm reset condition.

Channel 3 Receive - $xxEVE – Signals operator activity to the BNWAS to


generate an alarm reset condition.
NT991BNWAS INSTALLATION & OPERATION

3.2 (i) 115 (110V) VAC / 230 (220V) VAC Power Supply Selector Switch.

This switch (SW6) is located in the BNWAS Distribution Unit and must be set
as appropriate to the ships Power supply voltage. (See Fig. 3.0 for Switch
Location).

3.3 BNWAS Control / Display Unit Presets.

A 5 way DIL switch and a rotary volume preset are mounted on the back of
the Control / Display unit sounder and are accessible by temporary removal of
the blanking plug on the rear of the Control / Display unit, Fig 3.3

Blanking plug
Fig 3.3 Location of
Rear view of
Control Unit Presets.
NT991BNWAS
CU

There are 28 tone combinations available for selection as required which are
defined by the DIL switch settings as shown in Table 3.3.1 where switch
positions 1, 2,3,4 and 5 all ‘ON’ relates to code 11111 etc and all switches in
‘OPEN’ position equates to 00000.
nd
N° Tone 2 Tone Code Description
12345
1 Alternating tones 800/970Hz @ 2Hz 14 11111 BS5839 Part 1 1988
2 Sweeping 800/970Hz @ 7Hz 14 11110 Fast sweep (LF) BS5839 part 1 1988
3 Sweeping 800/900Hz @ 1Hz 14 11101 Medium sweep (LF) BS5839 Part 1 1988
4 Continuous at 2850Hz 14 11100
5 Sweeping 2400-2850Hz @ 7Hz 4 11011 Fast sweep
6 Sweeping 2400-2850Hz @ 1Hz 4 11010
7 Slow Whoop 14 11001 Slow whoop
8 Sweep 1200-500Hz @ 1Hz 14 11000 Din tone
9 Alternating tones 2400/2850 @ 2Hz 4 10111
10 Intermittent tone at 2850Hz @ 1Hz 14 10110 Back-up alarm (LF) BS5839 Part 1 1988
11 Alternating tone at 2850Hz @ 1Hz 14 10101 BS5839 Part 1 1988
12 Intermittent tone @ 2850Hz @ 1Hz 4 10100 Back-up alarm (HF)
13 970Hz @ ¼ S on / 1S off 14 10011 BS5839 Part 1 1988
14 Continuous @ 970Hz 14 10010 BS5839 Part 1 1988
15 554Hz for 100ms and 440Hz for 400ms 14 10001 French Fire sound
16 Intermittent 660Hz 150mS On/150mS Off 16 10000 Swedish Alarm Tone
17 Intermittent 660Hz 1.8S On/1.8S Off 17 01111 Swedish Alarm Tone
18 Intermittent 660Hz for 6.5S On/13S Off 18 01110 Swedish Alarm Tone
19 Continuous 660Hz 19 01101 Swedish Alarm Tone
20 Alternating 554/440Hz @ 1Hz 20 01100 Swedish Alarm Tone
21 Intermittent 660Hz @ 1Hz 21 01011 Swedish Alarm Tone
22 Intermittent 2850Hz 150mS On/100mS Off 14 01010 Pelican Crossing
23 Sweep 800-970Hz @ 50Hz 14 01001 Low Frequency Buzz BS5839 Part 1 1988
24 Sweep 2400-2850Hz @ 50Hz 4 01000 High Frequency Buzz
25 Intermittent 970Hz 500mS On/500mS Off 25 00111 ISO 8201 Low Frequency BS5839 Part 1 1988
26 Intermittent 2850Hz 500mS On/500mS Off 26 00110 ISO 8201 High Frequency
27 Continuous @ 4kHz 27 00101
28 Alternating tones 800/970 @ 2Hz 10 00100 FP1063.1 - telecoms

FIG 3.3.1 - Bridge Audible Alarm Tone Selection.


NT991BNWAS INSTALLATION & OPERATION

3.4 115V/230VAC Power Supply Selector (Final Stage Switch Unit).

When an expanded system incorporating the Navitron NT990 BNWAS 3 rd


Stage Audible Alarm Switch Unit is installed, the supply to the Switch Unit
should be independent from the Main BNWAS Distribution Unit to provide
maximum back up power fail alarm coverage. The supplies may be 24Vdc or
115Vac or 230Vac to suit the required 3rd (Final) Stage Audible Alarm Units.

The required supply voltage level and type (AC or DC) must be set using the
two PCB mounted selector switches within the 3rd Stage Switch Unit as
shown.

3.5 Officer Cabin Alarm Volume and Tone Selection.

Both the Masters Alarm monitor Cabin Unit and standard Officer Cabin Alarm
Unit types are equipped with audible Sounder Units which are installation
selectable for volume and a total of 28 different tones.

A 5 way DIL switch and a rotary volume preset are mounted on the back of
the Officer Cabin Alarm Unit sounder and are accessible when the Front
Cover is removed. (See FIG 3.5.1).

FIG 3.5.1 – Officer Cabin Alarm Unit


Volume & Tone Selection.
NT991BNWAS INSTALLATION & OPERATION

3.5 Officer Cabin Alarm Volume and Tone Selection … (Continued).

The 28 tone combinations available (for selection as required) are defined by


the DIL switch settings as shown in Table 3.5.2 where switch positions 1,
2,3,4 and 5 all ‘ON’ relates to code 11111 etc and all switches in ‘OPEN’
position equates to 00000.
nd
N° Tone 2 Tone Code Description
12345
1 Alternating tones 800/970Hz @ 2Hz 14 11111 BS5839 Part 1 1988
2 Sweeping 800/970Hz @ 7Hz 14 11110 Fast sweep (LF) BS5839 part 1 1988
3 Sweeping 800/900Hz @ 1Hz 14 11101 Medium sweep (LF) BS5839 Part 1 1988
4 Continuous at 2850Hz 14 11100
5 Sweeping 2400-2850Hz @ 7Hz 4 11011 Fast sweep
6 Sweeping 2400-2850Hz @ 1Hz 4 11010
7 Slow Whoop 14 11001 Slow whoop
8 Sweep 1200-500Hz @ 1Hz 14 11000 Din tone
9 Alternating tones 2400/2850 @ 2Hz 4 10111
10 Intermittent tone at 2850Hz @ 1Hz 14 10110 Back-up alarm (LF) BS5839 Part 1 1988
11 Alternating tone at 2850Hz @ 1Hz 14 10101 BS5839 Part 1 1988
12 Intermittent tone @ 2850Hz @ 1Hz 4 10100 Back-up alarm (HF)
13 970Hz @ ¼ S on / 1S off 14 10011 BS5839 Part 1 1988
14 Continuous @ 970Hz 14 10010 BS5839 Part 1 1988
15 554Hz for 100ms and 440Hz for 400ms 14 10001 French Fire sound
16 Intermittent 660Hz 150mS On/150mS Off 16 10000 Swedish Alarm Tone
17 Intermittent 660Hz 1.8S On/1.8S Off 17 01111 Swedish Alarm Tone
18 Intermittent 660Hz for 6.5S On/13S Off 18 01110 Swedish Alarm Tone
19 Continuous 660Hz 19 01101 Swedish Alarm Tone
20 Alternating 554/440Hz @ 1Hz 20 01100 Swedish Alarm Tone
21 Intermittent 660Hz @ 1Hz 21 01011 Swedish Alarm Tone
22 Intermittent 2850Hz 150mS On/100mS Off 14 01010 Pelican Crossing
23 Sweep 800-970Hz @ 50Hz 14 01001 Low Frequency Buzz BS5839 Part 1 1988
24 Sweep 2400-2850Hz @ 50Hz 4 01000 High Frequency Buzz
25 Intermittent 970Hz 500mS On/500mS Off 25 00111 ISO 8201 Low Frequency BS5839 Part 1 1988
26 Intermittent 2850Hz 500mS On/500mS Off 26 00110 ISO 8201 High Frequency
27 Continuous @ 4kHz 27 00101
28 Alternating tones 800/970 @ 2Hz 10 00100 FP1063.1 - telecoms

FIG 3.5.2 - Officer Cabin Audible Alarm Tone Selection.


NT991BNWAS INSTALLATION & OPERATION

3.6 Final Stage Alarms (100dB(A)) Tone Selection.

The 100dB(A) Final Stage Audible Alarm Units provide 10 installation


selectable tones via PCB mounted pin links which are exposed when the
Front Cover of the Unit is removed. Volume is also adjustable via preset VR1.

FIG 3.6.1 – Final Stage (100dB(A)) Tone Selection.


nd
N° Tone 2 Tone Code Description

1 800/1000Hz @ 0.25 sec Alternating Tone 8 99 dB(A) @ 1m


2 500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop Tone 1 100 dB(A) @ 1m
3 1200/500 Hz @ 1 Hz – DIN / PFEER P.T.A.P. Tone 8 99 dB(A) @ 1m
4 544 Hz (100mS)/440 Hz (400mS) – NF S 32-01 Tone 9 97 dB(A) @ 1m
5 Bell Tone 1 95 dB(A) @ 1m
6 800/1000 Hz @ 7 Hz Sweeping Tone 8 99 dB(A) @ 1m
7 500-1200 Hz 3.75 sec /0.25 sec Australian Evac Tone 10 100 dB(A) @ 1m
8 1000 Hz Continuous – PFEER Toxic Gas - 100 dB(A) @ 1m
9 554 Hz Continuous - 97 dB(A) @ 1m
10 420 Hz @ 0.625 sec Australian Alert - 97 dB(A) @ 1m

DC Version
N° Tone Code Description

1 800/1000Hz @ 0.25 sec Alternating 99 dB(A) @ 1m

2 500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop 100 dB(A) @ 1m

3 1200/500 Hz @ 1 Hz – DIN / PFEER P.T.A.P. 99 dB(A) @ 1m

4 544 Hz (100mS)/440 Hz (400mS) – NF S 32-01 97 dB(A) @ 1m

5 1000 Hz Continuous – PFEER Toxic Gas 100 dB(A) @ 1m

6 Bell 95 dB(A) @ 1m

7 800/1000 Hz @ 7 Hz Sweeping 99 dB(A) @ 1m

8 2400/2900 Hz @ 50 Hz Sweeping 100 dB(A) @ 1m

9 420 Hz @ 0.25 sec Australian Alert 97 dB(A) @ 1m

10 500-1200 Hz 3.75 sec /0.25 sec Australian Evac 100 dB(A) @ 1m

AC Version
FIG 3.6.2 – Final Stage 100dB(A) Tone Types.
NT991BNWAS INSTALLATION & OPERATION

3.7 Final Stage Alarms (112dB(A)) Tone Selection.

The 112dB(A) audible Alarm Unit provides a total of 32 different tones for
selection as required. Volume adjustment is also installation adjustable.

A 6 way DIL switch and a rotary volume preset are mounted on the back of
the Alarm Unit sounder and are accessible when the Front Cover is removed.
(See FIG 3.7.1).

FIG 3.7.1 - Final Stage (112dB(A)) Tone Selection.


nd rd
N° Tone 2 Tone (S2) 3 Tone (S3) Code Description
123456
1 340 Hz Continuous Tone 2 Tone 5 000000 102 dB(A) @ 1m
2 800/1000 Hz @ 0.25 sec Alternating Tone 17 Tone 5 100000 106 dB(A) @ 1m
3 500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop Tone 2 Tone 5 010000 106 dB(A) @ 1m
4 800/1000 Hz @ 1 Hz Sweeping Tone 6 Tone 5 110000 106 dB(A) @ 1m
5 2400 Hz Continuous Tone 3 Tone 20 001000 112 dB(A) @ 1m
6 2400/2900 Hz @ 7 Hz Sweeping Tone 7 Tone 5 101000 108 dB(A) @ 1m
7 2400/2900 Hz @ 1 Hz Sweeping Tone 10 Tone 5 011000 108 dB(A) @ 1m
8 500/1200/500 Hz @ 0.3 Hz Sweeping Tone 2 Tone 5 111000 106 dB(A) @ 1m
9 1200/500 Hz @1 Hz – DIN PFEER P.T.A.P. Tone 15 Tone 2 000100 106 dB(A) @ 1m
10 2400/2900 Hz @ 2 Hz Alternating Tone 7 Tone 5 100100 110 dB(A) @ 1m
11 1000 Hz @ 1 Hz Intermittent Tone 2 Tone 5 010100 106 dB(A) @ 1m
12 800/1000 Hz @ 0.875 Hz Alternating Tone 4 Tone 5 110100 106 dB(A) @ 1m
13 2400 Hz @ 1 Hz Intermittent Tone 15 Tone 5 001100 112 dB(A) @ 1m
14 800 Hz 0.25 sec on, 1 sec off Intermittent Tone 4 Tone 5 101100 108 dB(A) @ 1m
15 800 Hz Continuous Tone 2 Tone 5 011100 108 dB(A) @ 1m
16 660 Hz 150 mS on, 150 mS off Intermittent Tone 18 Tone 5 111100 104 dB(A) @ 1m
17 544 Hz (100 mS)/440 Hz (400 mS) – NF S 32-001 Tone 2 Tone 27 000010 104 dB(A) @ 1m
18 660 Hz 1.8 sec on, 1.8 sec off Intermittent Tone 2 Tone 5 100001 104 dB(A) @ 1m
19 1.4 KHz-1.6 KHz 1s, 1.6 KHz-1.4 KHz 0.5s – NFC 48-265 Tone 2 Tone 5 010010 106 dB(A) @ 1m
20 660 Hz Continuous Tone 2 Tone 5 110010 104 dB(A) @ 1m
21 554 Hz/440 Hz @ 1 Hz Alternating Tone 2 Tone 5 001010 104 dB(A) @ 1m
22 554 Hz @ 0.875 sec Intermittent Tone 2 Tone 5 101010 104 dB(A) @ 1m
23 800 Hz @ 2 Hz Intermittent Tone 6 Tone 5 011010 108 dB(A) @ 1m
24 800/1000 Hz @ 50 Hz Sweeping Tone 29 Tone 5 111010 108 dB(A) @ 1m
25 2400/2900 Hz @ 50 Hz Sweeping Tone 29 Tone 5 000110 108 dB(A) @ 1m
26 Bell Tone 2 Tone 15 100110 100 dB(A) @ 1m
27 554 Hz Continuous Tone 26 Tone 5 010110 104dB(A) @ 1m
28 440 Hz Continuous Tone 2 Tone 5 110110 103 dB(A) @ 1m
29 800/1000 Hz @ 7 Hz Sweeping Tone 7 Tone 8 001110 105 dB(A) @ 1m
30 300 Hz Continuous Tone 2 Tone 5 101110 100 dB(A) @ 1m
31 660/1200 Hz @ 1 Hz Sweeping Tone 26 Tone 5 011110 105 dB(A) @ 1m
32 Two Tone Chime Tone 26 Tone 15 111111 103 dB(A) @ 1m

FIG 3.7.2 – Final Stage 112dB(A) Tone Types.


NT991BNWAS INSTALLATION & OPERATION

Section 4: Installation Checks and Alongside Set Up.

It is assumed that all cable routing and associated connections have been
completed in accordance with Section 2.

4.1 Check 115V/230VAC selector switch setting in Distribution Unit (if


appropriate) to ensure correct switch (SW1) setting. See Section 3.2.

4.2 If appropriate – check 115/230Vac and AC/DC Selector Switch settings in


Final (3rd) Stage Switch Unit are correctly set. See Section 3.4.

4.3 Check that all earth braids & earthing arrangements / earth stud connections
are complete.

4.4 Ensure all covers are at least temporarily in place to prevent unnecessary
‘Tamper’ alarms during set up.

4.5 Check that the BNWAS Control / Display Unit blanking plug is removed to
permit tone / volume adjustments. See Section 3.3.

4.6 Ensure DIL Switch SW5/4 (Intruder Alarm Enable) is set to “OFF”. Use the
key switch to select the Control / Display Unit ‘ SET’ position.

4.7 Switch on the Power supply isolators.


(The Control panel display segments and all alarm LED’s except ‘Computer
Fail’ will illuminate for a 1 second self test period).

4.8 With the key switch in the ‘SET’ position, use the ‘TIME’ keypad to select the
required alarm interval (3 – 12 minutes) as confirmed by the Control Unit 2
digit display.

4.9 Use the ‘MODE’ keypad to select the ‘ON’ operating mode as confirmed by
the ‘WORK MODE ON’ LED.

4.10 The maximum number of officers must now be set to match the number of 2 nd
stage alarms connected to the NT991BNWAS Distribution Unit. This prevents
the users from selecting a backup officer output that is unused and has no
alarm associated with it.

Set Distribution Unit DIL switch SW3/4 to “ON”. With the key switch in the
“SET” position repeatedly press the “SELECT ON CALL OFFICER” triangular
keypad until the required highest available officer LED is flashing. Press the
“CONFIRM ON CALL OFFICER” triangular keypad to confirm the selection.
This setting can now be programmed by setting DIL switch SW3/4 in the
Distribution Unit to “OFF”.
NT991BNWAS INSTALLATION & OPERATION

Section 4: Installation Checks and Alongside Set Up … (Continued).

4.11 Continue with the installation calibration by setting the “MASTER” officer as
the current on call officer as follows:- Repeatedly press the “SELECT ON
CALL OFFICER” triangular keypad until the “MASTER” officer LED is
flashing. Press the “CONFIRM ON CALL OFFICER” triangular keypad to
confirm the selection (if the selection is not confirmed within 6 seconds the
system will revert to the previous officer selection).

4.12 Use the key switch to select ‘RUN’. The BNWAS will begin to time the alarm
period selected, the time display will show a count down time (in minutes) with
a flashing right hand decimal point to indicate that the timer is active, in the
last 59 seconds the display will show a count down in seconds.

4.13 Check Bridge Visual Alarm at end of timing period. If serial interfaces have
been connected check VDR & Central Alarm Panel receive correct messages.
(15 seconds visual alarm before Bridge Audible).

4.14 Check Bridge Audible Alarm following Bridge Visual Alarm period.
(15 seconds audible alarm and visual indication before Officer Call Alarm).

4.15 Check Officer Call Alarm and visual indication following Bridge Audible
Alarm period (90 seconds is default setting before Crew Call Alarm – See
also 4.22 & 4.24).

4.16 Whilst waiting for the 3rd Stage Crew Call alarm check all available officer call
alarms as follows:- For each available officer press the “SELECT ON CALL
OFFICER” triangular keypad until the required officer LED is flashing. Press
the “CONFIRM ON CALL OFFICER” triangular keypad to confirm the
selection (if the selection is not confirmed within 6 seconds the system will
revert to the previous officer selection). When confirmed the selected officer
cabin alarm should be sounding.

4.17a) Check Crew Call visual indication following Officer Call Alarm timeout
period.

4.17b) If appropriate – check Final (3rd) Stage Switch Unit (ADU) key switch is
set to the ON position and that the ALARM ACTIVE LED is illuminated.

4.17c) If appropriate – check that the integral audible Final Stage Switch Unit
audible Alarm is active accompanied by the main (external) Final
Stage audible Alarm(s) and corresponding CHAN 1, CHAN 2, CHAN 3
GREEN LEDs as appropriate.

4.18 Check that operation of the ‘RESET’ button (including any/all remote Reset
units and Movement Detectors) cancels any alarm stage and that a new
timing period commences. (See also Section 4.29).

Operation of all remaining reset facilities including movement detectors are


checked in Section 4.29.
NT991BNWAS INSTALLATION & OPERATION

Section 4: Installation Checks and Alongside Set Up … (Continued).

4.19 Check that operation of the ‘EMERGENCY CALL’ button immediately sounds
the Officer Call accompanied by Officer Call visual indication and
subsequently (after Officer Call timeout period) the ‘Crew Call’ Alarm.

4.20 To avoid unnecessary disturbance, temporarily disable (disconnect) the


Master Officer and Crew Call alarms at the BNWAS Distribution Unit.
(Terminal Nos. 68 and 98 – see FIG 2.2.1) Select the “MASTER” officer using
the control unit keypads..

4.21a) Allow the BNWAS to run and adjust the tone and volume of the Bridge
Audible Alarm. (Section 3.3 / Table 3.3.1 refer).

4.21b) Reconnect Terminal No. 68 of the BNWAS Distribution Unit (FIG 2.2.1) and
adjust tone and volume settings of the Officer Cabin Alarm Units (Section
3.5). Select each available officer in turn using the control unit key pads.

4.21c) Reconnect Terminal No. 98 of the BNWAS Distribution Unit (FIG 2.2.1)
and, if appropriate, adjust tone and volume settings of the Final Stage
Switch Unit (integral) and Final Stage external alarms per Sect. 3.6
(100dB(A)) & 3.7 (112dB(A)).

4.22 Refer to Section 3.1.4 (Fig 3.0) and set the required Officer response
timeout period using SW4 position 1, 2 and 3 in the Distribution Unit.
(Time between Officer Call and Crew Call Alarm adjustable from 90 to 180
seconds or combine Officer and Crew Call Alarms).

4.23 If external backup power is connected check and ensure that SW3 position 3
is set to ‘ON’ (backup power supply monitor).

4.24 If the BNWAS is to be activated by remote proprietary equipment in the


‘AUTO’ mode, refer to Sections 2.3 or 2.4 as appropriate and set SW5
positions 2 and 3 accordingly.

4.25 Check ‘Tamper’ Alarm response to displaced covers before finally securing all
covers and replacing the control Unit calibration insert.

(Tamper response should immediately sound the Officer Call Alarm


accompanied by Officer Call and Tamper visual indications which can only be
reset by key switch operation (Run – Set – Run) or by 15 second continuous
operation of the RESET button).
NT991BNWAS INSTALLATION & OPERATION

Section 4: Installation Checks and Alongside Set Up … (Continued).

4.26a) If the internal battery is fitted connect it to the system by fitting a link
between terminals 122 & 123 in the distribution unit. Enable the internal
battery monitor by setting DIL switch SW3 pole 2 to ON.

4.26b) Check Power Fail Alarm response(s) to temporarily disconnected power


supplies.

Disconnect main supply for “MAIN POWER” Fail indication. Reconnect


main power supply.

Disconnect backup DC supplies for “2ND POWER” Fail indication.

If internal battery fitted check BNWAS system continues to operate with


both main and backup supplies turned off. MAIN and 2ND power fail
indicators should be active.

4.26c) If appropriate – use the “ALARM TEST” key on the Final (3rd) Stage Switch
Unit and check that the “POWER FAIL” LED and integral audible alarm
are active.

4.26d) If appropriate – temporarily disconnect the AC supply to the Final (3rd)


Stage Switch Unit and check that the integral audible alarm and “POWER
FAIL” visual indication is activated.

4.26e) If appropriate – temporarily disconnect the DC supply to the Final (3rd)


Stage Switch Unit and check that the integral audible alarm and “POWER
FAIL” visual ndication is activated.

4.26f) If appropriate – temporarily disconnect the AC & DC supply to the Final


(3rd) Stage Switch Unit and check that the integral audible alarm and
“POWER FAIL” visual indication is activated. (Power in this condition is
derived from the DB).

4.27a) Check Control Unit illumination keypad operation.

4.27b) If appropriate – check the illumination control operation on the Final (3rd)
Stage Switch Unit. (Normally, internally controlled but can also be
externally controlled per Section 2.9.4).

4.28 Check Remote Reset variable illumination (5 second use of RESET


button to engage dimmer control).
NT991BNWAS INSTALLATION & OPERATION

Section 4: Installation Checks and Alongside Set Up … (Continued).

4.29 Additional Reset facilities installation test.

4.29a) Remote Reset input facilities.

Within the distribution unit LED Reset indication (LED 5) normally flashes at
a constant rate of 4Hz unless a remote reset signal is received when the
flashing stops (hesitates) for approx 0.5 seconds. This allows all remote
reset inputs to be verified by LED 5 observation.

When using this diagnostic feature the “TAMPER ALARM” that will be
generated when the DB lid is removed can be temporarily disabled by
setting the CU key switch to the “SET” position. Ensure the system is
restored to normal operation by setting the CU key switch to “RUN” when
tests have been completed.

i) Select the SET position on the CU key switch.


ii) Remove the DB lid.
iii) If the system is configured to accept a “RESET” signal via
operator activity on the radar etc. (Section 3.1.7), operate the
radar to generate the signal and check within the DB that LED5
indicates that a RESET signal has been received.
iv) If applicable repeat step iii) for the track plotter etc.
v) Refit the DB lid and set CU to “RUN”.

4.29b) PIR Motion Detectors.

If NT990 BNWAS PIR sensors have been fitted, they must be checked and
calibrated as follows:-

PIR LED Display (see table below) is active when Switch 2 within the PIR
(LED Enable) is set to ON (FIG 2.12 refers).

LED Colour Function


RED Movement detected.
Reset Generated.
YELLOW (infra red) PIR sensor activated.
GREEN (microwave) MW sensor activated.
NT991BNWAS INSTALLATION & OPERATION

Section 4: Installation Checks and Alongside Set Up … (Continued).

Calibrating the NT990 BNWAS PIR sensor.

i) Power up the NT991 BNWAS system and wait at least 2


minutes for the detector to stabilise.

The MW range must be adjusted to the minimum necessary to


cover the required area. The adjustment potentiometer is
located middle right of the PIR PCB and must be set to the
lowest possible setting that provides reliable detection of
operator movement. (FIG 2.12. refers).

ii) Walk through the sensor area, observe the LED and confirm that
the area coverage is as required and both PIR and MW sensors
are activating (red LED).

4.29c) DB Remote “EMERGENCY CALL” facility.

Ensure the CU key switch is set to the RUN position.

If the remote “EMERGENCY CALL” facility on the DB has been connected,


activate the signal input and check the OFFICER CALL LED is illuminated
on the CU.

Press the CU RESET button to clear the alarm.

If the DB has been configured to accept an active un-acknowledged


$xxALR alarm from the track system or the central alarm panel, set the
appropriate system to generate the message and check the CU OFFICER
CALL LED is illuminated. (If DB switch SW2 pole 2 is ON – FIG 3.0 – there
will be a 30second delay before the OFFICER CALL LED illuminates).
Press the CU RESET button to clear the alarm.

4.29d) VDR and Central Alarm Panel interfaces.

If DB Alarm sentence transmission to the VDR and/or Central Alarm Panel


is not already tested, refer to FIG 3.1.6 (Central Alarm Panel) and/or FIG
3.1.8 (VDR) and verify as appropriate.

4.30 If required enable the integral intruder alarm by setting DIL switch SW5/4 ON
in the distribution unit.

4.31 Finally secure the BNWAS Control / Display Unit mounting bracket and all
other BNWAS component covers (Distribution Unit/Remote Resets etc.).

All alongside checks and set up are now complete.


NT991BNWAS INSTALLATION & OPERATION

Section 5: NT991 BNWAS Operating Instructions and Alarm Indications

5.1 Alarm Time Selection.

5.2 Operating Mode Selection.

5.3 Illumination Controls.

5.4 Officer Call Cabin Alarm Selection.

5.5 Control / Display Unit Alarm Reset.

5.6 Emergency Call.

5.7 Remote Reset Unit Cancel (NT990 BNWAS RST).

5.8 Remote Reset Unit Illumination Level.

5.9 Standard Watch Keeping Alarm Sequence.

(i) Bridge Visual Alarm/Indications.


(ii) Bridge Audio Alarm/Indications.
(iii) Officer Call Alarm/Indications.
(iv) Crew Call Alarm/Indications.

5.10 Emergency Call Alarm Indications.

5.11 Main Power Fail Alarm Indications.

5.12 2nd Power Fail Alarm Indications.

5.13 AC & DC Power Supply Failure to the Alarm Distribution Unit (ADU).

5.14 Alarm Distribution Unit Alarm Output Channel Power Failure.

5.15 Alarm Distribution Unit Alarm Test.

5.16 Main (All) Power Fail Alarm Indications.

5.17 Malfunction Alarm Indications.

5.18 Tamper Alarm Indications.

5.19 Computer Fail Alarm Indications.

5.20 System failure Indication.

5.21 Intruder Alarm.

5.22 VDR/Central Alarm Panel BNWAS Alarm/Status Messages.

5.23 Internal Battery Periodical Testing and replacement.


NT991BNWAS INSTALLATION & OPERATION

5.1 Alarm Time Selection.

The timing (silent) period is operator adjustable from 3 to 12 minutes in one minute
steps as follows: -

(i) Insert key and turn key switch to ‘SET’ position.

(ii) Press the TIME keypad to ‘Clock’ the 2 digit display to the required time
interval (3 – 12 minutes) which will be transmitted in serial data to the VDR
each time the period is changed.

(iii) Turn key switch to ‘RUN’ position and remove key.

5.2 Operating Mode Selection.

Three operating modes are available: -

(i) AUTO - Watch Alarm remotely activated by engagement of selected


equipment (Autopilot etc).

(ii) ON – Watch Alarm permanently on duty.

(iii) OFF – Watch Alarm permanently OFF.

The operating mode is selected as follows: -

(i) Insert key and turn key switch to ‘SET’ position.

(ii) Press the ‘MODE’ keypad until the AUTO/ON/OFF LED indication in the
‘WORK MODE’ domain of the control panel is as required which will be
transmitted in serial data to the VDR each time the mode is changed.

(iii) Turn keyswitch to ‘RUN’ position and remove key.

5.3 Illumination Controls.

5.3 (i) The Control/Display Unit.

Five fixed levels of illumination are available via repeat operation of the keypad
which also controls the illumination level of the deckhead mounted WAS BVA.

5.3 (ii) The Final (3rd) Stage Switch Unit (WAS ADU).

This is fitted with an operator variable rotary DIM control to provide adjustable red
Control Panel legend illumination. External illumination control can also be used via a
signal input terminal which becomes active when the illumination mode (INT or EXT)
jumper link is positioned for external. (Section 2.9.4 refers).
NT991BNWAS INSTALLATION & OPERATION

5.4 Officer Call Cabin Alarm Selection.

The NT991BNWAS control unit features an integral Officer Call selection facility which
allows any one of five, or all simultaneously, cabin locations to be selected for automatic
receipt of Officer Call Alarms if the 15 second visual plus 15 second audible bridge
alarms are not reset by watch personnel.

The Officer on Call is selected by pressing the “SELECT ON CALL OFFICER” triangular
keypad, the next Officer LED will flash. Each subsequent press of the keypad will select
the next available officer up to “ALL OFFICERS” where the next press of the keypad will
select the “MASTER” officer.

When the required Officer is selected it must be confirmed by pressing the “CONFIRM
ON CALL OFFICER” triangular keypad. If the change of Officer is not confirmed within 6
seconds then the last confirmed Officer selection will be restored.

The available Officers for selection can be restricted during installation setup so that
unused outputs (with no alarm connected) cannot be inadvertently selected by the user.

5.5 Control / Display Unit Alarm Reset.

Single push operation of the prominent red BNWAS RESET button will cancel any timed
out alarm condition and / or restart the timing period selected (3 – 12 minutes).

The RESET button will also cancel the Emergency Call Alarm (see 5.10) and 15-second
operation will cancel a ‘TAMPER’ alarm (see 5.18).

Audible alarms due to power failure are also acknowledged and silenced by RESET
button operation (see 5.11 and 5.12).

5.6 Emergency Call.

A shrouded (protected) red pushbutton labelled ‘EMERGENCY CALL’ or other remote


Officer Call facilities triggered from Track Control System etc. will activate Officer
quarters alarm(s) when operated (or other strategic back up area alarms).

The bridge visual and audible alarms are not activated for security reasons.

The Emergency Call alarm may be cancelled at any time by operation of the ‘RESET’
button. If the Emergency Call alarm is not cancelled within the specified Officer Call
timeout period (typically 90 seconds to 3 minutes) Final (3rd) Stage Crew Call alarms will
automatically be activated.

5.7 Remote Reset Unit Cancel (NT990 BNWAS RST).

Single push operation of any Remote Reset button will cancel any timed alarm condition
and / or restart the timing the timing period selected (3 – 12 minutes).

Similarly, operation of any remote Reset button will cancel the Emergency Call alarm.

“TAMPER” and “POWER FAIL” alarms are not affected by remote reset button
operation.
NT991BNWAS INSTALLATION & OPERATION

5.8 Remote Reset Unit (NT990BNWAS RST) Illumination Level.

Four fixed levels of illumination are available via 5 second continues operation of the
RESET button.

The four levels will be automatically clocked until the RESET button is released
consistent with the level of illumination required.

5.9 Standard BNWAS Watch Keeping Alarm Sequence.

The standard BNWAS sequence is a 4 stage process beyond the initial timing (silent)
period of 3 to 12 minutes as required. During the timing period the 2 digit LED display
will show a countdown in minutes accompanied by a flashing right hand decimal point to
confirm the timer is running. When the remaining timing period is less than 59 seconds
the display will show a countdown in seconds. On completion of the specified time (3 –
12 mins) the first alarm indication will be: -

(i) Bridge Visual (from Timeout for a period of 15 seconds).


Confirmed by flashing ‘BRIDGE VISUAL’ and ‘RESET’ LED on the
BNWAS Control / Display Unit, and may be accompanied by additional
deckhead mounted etc. visual indication (WAS BVA) if fitted.

Remote BNWAS Reset units will also display flashing ‘RESET’ indications.

Single operation of any RESET button will cancel and restart timing period
(3 – 12 mins) as will remote activity and movement detectors.

(ii) Bridge Audible (from Bridge Visual timeout for a period of 15 second)
confirmed by flashing ‘BRIDGE AUDIO’, ‘BRIDGE VISUAL’ and Reset
LED’s plus additional bridge mounted visual and audible alarm devices if
fitted.

Remote BNWAS Reset Units will also display flashing ‘RESET’


indications.

Single operation of any RESET button will cancel both visual and audible
alarms and will restart timing period (3 – 12 mins) as will remote activity
and movement detectors.

(iii) Officer Call (from bridge audible time out for a period of 90 to 180
seconds).
Confirmed by flashing ‘OFFICER CALL’, ‘BRIDGE AUDIO’, ‘BRIDGE
VISUAL’ and ‘RESET’ LED’s plus officer quarter Alarm units and any
additional bridge mounted visual and audible alarm devices if fitted.

Remote BNWAS units will also display flashing ‘RESET’ indications.


Single operation of any ‘RESET’ button will cancel both visual and audible
bridge plus officer quarter alarms as will remote activity and movement
detectors.
NT991BNWAS INSTALLATION & OPERATION

5.9 Standard BNWAS Watch Keeping Alarm Sequence…(Continued).

(iv) Crew Call (from Officer Call timeout - indefinitely / until cancelled).
NOTE: In certain cases, Officer Call and Crew call stages may be
combined (Section 3 refers).

Confirmed by flashing ‘CREW CALL’, ‘OFFICER CALL’, ‘BRIDGE


AUDIO’, ‘BRIDGE VISUAL’ and ‘RESET’ LEDs plus Officer quarter and
Crew area alarm units and any additional bridge located visual / audible
alarm devices if fitted.

If fitted the Final (3rd) Stage Switch Unit (if fitted) will display an “ALARM
ACTIVE” red LED accompanied by the Switch Unit integral audible alarm.

Remote BNWAS Reset units will also display flashing ‘RESET’ indications
and single operation of any ‘RESET’ button will cancel all Bridge, Officer
quarter and Crew area alarms as will remote activity and movement
detectors.

5.10 Emergency Call Alarm Indications.

Single press of the Emergency Call button will immediately activate Officer quarter
alarms but bridge audible and visual alarms will be dormant.

The BNWAS Control / Display Unit will provide flashing ‘OFFICER CALL’ LED
confirmation only which will be accompanied by flashing ‘CREW CALL’ LED on timeout
of Officer Call or if the Officer Call and Crew Call alarm functions are combined.
(Section 3 refers).

Emergency call cancelled by any ‘RESET’ button operation.

5.11 Main Power Fail Alarm Indications.

In the event of Main Power supply failure (24Vdc or 115/230v 50/60Hz) the BNWAS will
continue to function via the 24Vdc supply which should always be connected to the
Distribution Unit for back up purposes.

Main Power supply failure will be confirmed by a flashing ‘MAIN POWER FAIL’ LED
accompanied by flashing ‘ BRIDGE VISUAL’ and ‘BRIDGE AUDIO’ LED’s on the
BNWAS Control / Display Unit.

The BNWAS audible alarm and associated auxiliary Bridge visual / audio alarms (if
fitted) will also be activated and can be cancelled by any ‘RESET’ button operation.

Once reset, the BNWAS will continue to display a steady ‘MAIN POWER FAIL’ LED
indication until main power is restored.

In systems which use a Navitron Final (3rd) Stage Switch/Distribution Unit, the AC or DC
supply for this (if applicable) is only used to power Final (3 rd) Stage Crew Call Audible
Alarm Units and is normally independent of the main BNWAS power supply.
NT991BNWAS INSTALLATION & OPERATION

5.11 Main Power Fail Alarm Indications…(Continued).

In the event of 3rd Stage Switch Unit AC or DC Power Supply Failure, the Switch Unit
integral audible alarm - only - will sound accompanied by a red “POWER FAIL” LED.

The 3rd Stage Switch Unit Alarm will automatically reset on restoration of AC or DC
power or if the unit key switch is set from “ON” to “OFF”.

5.12 2nd Power Fail Alarm Indications.

In some circumstances the emergency (backup) 2nd power supply may be omitted if the
optional internal battery is fitted. The 2nd power supply monitoring function is enabled or
disabled via installation setup, see Section 3.1.3.

In the event of emergency (backup) 24Vdc power supply failure, the BNWAS will
continue to function via the main supply or via the optional internal battery.

If the monitor is enabled emergency power supply failure will be confirmed by a flashing
‘2ND POWER FAIL’ LED accompanied by flashing ‘BRIDGE VISUAL’ and ‘BRIDGE
AUDIO’ LEDs on the BNWAS Control / Display unit.

The BNWAS audible alarm and associated auxiliary Bridge visual / audio alarms (if
fitted) will also be activated and can be cancelled by any ‘RESET’ button operation.

Once reset, the BNWAS will continue to display a steady ‘2ND POWER FAIL’ LED
indication until the emergency (backup) power fault is corrected.

5.13 AC & DC Power Supply Failure to the Final (3rd) Alarm Distribution Unit.

Systems - which use the Navitron Final (3rd) Stage Switch/Distribution Unit - will be
connected to AC or DC power supplies. An additional regulated supply from the DB and
the resultant dual supplies monitor each other with power failure alarm if one is absent.

NOTE: Optimum power failure alarm indications will occur when the AC or DC supply to
the 3rd Stage Switch Unit are independent of the AC or DC power supplies to the main
BNWAS DB.

The 3rd Stage Switch Unit Alarm will automatically reset on restoration of AC or DC
power (as appropriate) or if the unit key switch is set from “ON” to “OFF”.

The normal operating position of the key switch is “ON” and should be removed by
appropriate appointed personnel to prevent unauthorised switching to “OFF”.

The “OFF” key position is only made available for service work by authorised
personnel in the event of fuse failure (indicated by Power Fail Alarm) etc. and
must be removed for normal operational use.
NT991BNWAS INSTALLATION & OPERATION

5.14 Final (3rd) Stage Alarm Distribution Unit Output Channel Power Failure.

The Navitron Final (3rd) Stage Switch Unit provides three independently fused alarm
output channels labelled CHAN 1, CHAN 2 and CHAN 3 which are confirmed as
operational (supply intact) by a green LED for each channel. In the event of internal fuse
failure, the appropriate green channel LED will turn off and the red “POWER FAIL” LED
will become active accompanied by the integral audible alarm.

This alarm will persist until the unit keyswitch is set to the “OFF” position prior to unit
access for fuse replacement.

5.15 Final (3rd) Stage Alarm Distribution Unit Alarm Test.

The Navitron Final (3rd) Stage Switch Unit is equipped with an ALARM TEST button
which, when operated, will extinguish one green channel LED and will activate the red
“POWER FAIL” LED and integral audible alarm unit.

5.16 Main (All) Power Supply Alarm Indications.

The removal or failure of all power to the BNWAS (including internal battery) obviously
prevents direct Control / Display Unit indication.

However, a changeover relay contact within the BNWAS Distribution Unit provides a
switchline to an external alarm which should be suitably connected and labelled for this
purpose. (Section 2.6 refers).

5.17 Malfunction Alarm Indications.

The ‘Malfunction’ alarm facility is available via a relay contact within the BNWAS
Distribution Unit which closes to provide a switchline to an external alarm which should
be suitably connected and labelled for this purpose. (Section 2.7 refers).

BNWAS ‘MALFUNCTION’ conditions include: -

(i) Main Power Fail.


(ii) 2ND Power Fail.
(iii) Dist. Unit to BNWAS CU communication failure.
(iv) BNWAS Computer fail.
(v) Internal battery fail.

5.18 Tamper Alarm Indications.

The integrity of the BNWAS is protected by anti tamper measures to warn of cover / lid
removal from Distribution Unit(s) / Remote Reset Unit(s) or other system components
etc.

A Tamper alarm condition will be confirmed by a flashing ‘TAMPER FAIL’ alarm LED
indication accompanied by flashing ‘BRIDGE VISUAL’, ‘BRIDGE AUDIO’ and
‘OFFICER CALL’ LEDs and associated external alarms.
NT991BNWAS INSTALLATION & OPERATION

5.18 Tamper Alarm Indications … (Continued).

If applicable the tamper red LED indication (plus accompanying visual and audible
alarms on the bridge mounted NT991 BNWAS main/display unit) will result on the Final
(3rd) Stage Alarm Distribution Unit based on interference with it or its associated Final
Stage Audible Alarm Units and will only be cancelled by replacement of lids etc. or by
keyswitch set from “ON” to “OFF”.

If the ‘TAMPER’ condition persists throughout the specified ‘OFFICER CALL’ timeout
period (90 – 180 secs) the CREW CALL alarm will automatically be activated.

The Tamper alarm can be silenced by key switch movement (RUN – SET – RUN) or by
15-second continuous operation of the main unit Reset button.

Remote Reset Unit RESET button operation will not cancel the Tamper Alarm.

If silenced by the Main unit Reset button, a steady TAMPER LED will be displayed until
extinguished by key switch movement (RUN – SET – RUN).

The Tamper condition will require correction to prevent further alarm prior to ongoing
BNWAS operation.

5.19 Computer Fail Alarm Indications.

This condition indicates an internal fault and is confirmed via a flashing ‘COMPUTER
FAIL’ LED on the main / display unit.

Qualified advice / investigation will be required as BNWAS operation will be seriously


compromised.

5.20 System failure Indication.

If the communication between the Control Unit and the distribution unit fails the Control
Unit will show “Er” in the time display. If the key switch is in the run position an audible
alarm is given which can be silenced by pressing the red reset button. Qualified advice /
investigation will be required as BNWAS operation will be seriously compromised.

5.21 Intruder Alarm.

The NT991NWAS control unit features an integral intruder alarm which is enabled by
setting DIL switch SW5/4 in the distribution unit to ON.

The intruder alarm is armed by holding down the control unit large red reset button
whilst setting the key switch to the “SET” position. The “INTRUDER” LED will flash
accompanied by an intermittent bleep for a period of 2 minutes to allow the user to
vacate the bridge, at the end of this period the intruder alarm will be active.

Movement detected by the PIR Motion sensors whilst the intruder alarm is active will
trigger the alarm. The “INTRUDER” LED will flash accompanied by an audible bleep for
an entry timeout period of 2 minutes. The alarm is disarmed by insert the key and
setting the key switch to “RUN”. If the intruder alarm is not disarmed within the entry
timeout period the full intruder alarm will trigger for a period determined by the BNWAS
time period set (3 – 12 minutes) after which the alarm will silence.
NT991BNWAS INSTALLATION & OPERATION

5.22 VDR/Central Alarm Panel BNWAS Alarm/Status Messages.

Any change in BNWAS Alarm Status is sent via an IEC61162 serial output to the VDR
and/or Central Alarm Panel. Additionally, when the BNWAS system is reset, the reset
source is also sent to the VDR (Radar/ECDIS/Motion Detectors etc.).

Refer to Sections 3.1.6 & 3.1.8 for sentence details and alarm messages that will be
available to the VDR or Central Alarm Panel displays.

5.23 Internal Battery Periodic Testing and Replacement.

The internal battery (12V 1.2Ah) is expected to have a standby service life in excess of
3 years provided the proper maintenance procedure is followed as detailed below.

Every month.

Switch off all power supply isolators to the BNWAS. Press the CU RESET switch to
cancel the audible and visual alarms. Check the BNWAS continues to function on
battery power and that the MAIN POWER FAIL and if applicable 2ND POWER FAIL
LEDs on the CU are ON.

Restore the power to the BNWAS by setting the isolators back on and check the MAIN
POWER FAIL and if applicable 2ND POWER FAIL LEDs on the CU are OFF.

Re-enable the BNWAS system by setting the CU key switch to RUN.

Every year.

Switch off all power supply isolators to the BNWAS. Press the CU RESET switch to
cancel the audible and visual alarms. Check the BNWAS continues to function on
battery power and that the MAIN POWER FAIL and if applicable 2 ND POWER FAIL
LEDs on the CU are ON.

Continue to use the BNWAS normally for approximately 0.5 hours to partially discharge
the internal battery.

Restore the power to the BNWAS by setting the isolators back on and check the MAIN
POWER FAIL and if applicable 2ND POWER FAIL LEDs on the CU are OFF.

Every 3 years.

When in port and the BNWAS is not in use, replace the BNWAS internal battery as
follows:-

Disable the generation of external alarms by setting the NT991 BNWAS CU (Control
Unit) key switch to SET.

Switch off all power supply isolators.

Remove the lid of the NT991 BNWAS DB and disconnect the battery terminals. Remove
the 2 long nuts that fix the battery retaining clamp in place. Carefully withdraw the
battery and retaining clamp from the unit. Fit the new battery and refit the retaining
clamps. Connect the battery , RED +VE, BLACK –VE. Re-fit the lid.
NT991BNWAS INSTALLATION & OPERATION

5.23 Internal Battery Periodic Testing and Replacement…(Continued).

Check the BNWAS operates on battery power and that the MAIN POWER FAIL (and
2ND POWER FAIL if applicable) LED on the CU are ON.

Restore the power to the BNWAS by setting the isolators back on and check the MAIN
POWER FAIL (and 2ND POWER FAIL if applicable) LED on the CU are OFF.

Re-enable the BNWAS by setting the CU key switch to RUN.

Section 6: NT991 BNWAS Schematics and PCB Layouts.

6.1.1 NT991 BNWAS Control Unit Main PCB Overlay (Top view).

6.1.2 NT991 BNWAS Control Unit Main PCB Overlay (Bottom view).

6.1.3 NT991 BNWAS Control Unit Main PCB Schematic.

6.2.1 NT991 BNWAS Control Unit Illumination PCB Overlay.

6.2.2 NT991 BNWAS Control Unit Illumination PCB Schematic.

6.3.1 NT991 BNWAS Distribution Unit PCB Overlay.

6.3.2 NT991 BNWAS Distribution Unit Schematic.

6.4.1 NT990 BNWAS Reset Unit PCB Overlay (Top view).

6.4.2 NT990 BNWAS Reset Unit PCB Overlay (Bottom view).

6.4.3 NT990 BNWAS Reset Unit PCB Schematic.

6.5.1 NT990 BNWAS Final (3rd) Stage Switch Unit PCB Overlay.

6.5.2 NT990 BNWAS Final (3rd) Stage Switch Unit Schematic.


NT991BNWAS INSTALLATION & OPERATION

Section 6: NT990BNWAS Schematics and PCB Layouts.

FIG 6.1.1 – NT991 BNWAS Control Unit PCB Overlay (Top View).

FIG 6.1.2 – NT991 BNWAS Control Unit PCB Overlay (Bottom View).
NT991BNWAS INSTALLATION & OPERATION

FIG 6.1.3 – NT991 BNWAS Control Unit Schematic (Page 1).


NT991BNWAS INSTALLATION & OPERATION

FIG 6.1.3 – NT991 BNWAS Control Unit Schematic (Page 2).


NT991BNWAS INSTALLATION & OPERATION

FIG 6.2.1– NT991 BNWAS Control Unit Illumination PCB Overlay.

FIG 6.2.2– NT991 BNWAS Control Unit Illumination PCB Schematic.


NT991BNWAS INSTALLATION & OPERATION

FIG 6.3.1– NT991 BNWAS Distribution Unit PCB Overlay.


NT991BNWAS INSTALLATION & OPERATION

FIG 6.3.2 – NT991 BNWAS Distribution Unit Schematic (Page 1).


NT991BNWAS INSTALLATION & OPERATION

FIG 6.3.2 – NT991 BNWAS Distribution Unit Schematic (Page 2).


NT991BNWAS INSTALLATION & OPERATION

FIG 6.3.2 – NT991 BNWAS Distribution Unit Schematic (Page 3).


NT991BNWAS INSTALLATION & OPERATION

FIG 6.4.1– NT990 BNWAS Reset Unit PCB Overlay (Top view).

FIG 6.4.2– NT990 BNWAS Reset Unit PCB Overlay (Bottom view).
NT991BNWAS INSTALLATION & OPERATION

FIG 6.4.3– NT990 BNWAS Reset Unit Schematic.


NT991BNWAS INSTALLATION & OPERATION

FIG 6.5.1 – NT990 BNWAS Final (3rd) Stage


Switch Unit PCB Overlay.
NT991BNWAS INSTALLATION & OPERATION

FIG 6.5.2 – NT990 BNWAS Final (3rd) Stage


Switch Unit Schematic (Page 1).
NT991BNWAS INSTALLATION & OPERATION

FIG 6.5.2 – NT990 BNWAS Final (3rd) Stage


Switch Unit Schematic (Page 2).

You might also like