Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

DATASHEET

Breaker protection REQ650


Relion® 650 series version 2.2

Application • Auto recloser for single breaker


• Feeder and circuit breaker back-up protection • Synchronizing, synchro check and energizing
• Easy integration to conventional or digital check
substations • Control and interlocking for one circuit breaker
Features • Selectable operator place allocation
• Fully IEC 61850 compliant, Edition 1 and Edition 2 • Software based multi-position selector switches
• Protection, monitoring and control in one IED Logic
• Extensive self-supervision including analog • Tripping and trip matrix logic
channels • Extensive logic block library for application
• Six independent parameter setting groups customization
• Ethernet interface for fast and easy communication Monitoring
with PC and SA system • Adjustable breaker monitoring with capability to
• Up to four Ethernet ports to support several system handle multiple breaker types
topologies and redundancy methods • Disturbance recorder with disturbance report
• Large HMI for visualization of single line diagrams • 200 disturbances
• Cyber security support for compliance to NERC • 40 analog channels (30 physical and 10 derived)
CIP and IEC 62351-8 with Centralized Account • 352 binary channels
Management • Event list for 1000 events
Pre-configured solutions • Event and trip value recorders
• Pre-configured and type-tested solution including • Fault locator
default settings for: • Event counters
• Breaker bay connecting a transmission line • Running hour meter
• to a busbar, with back-up protection functions • Supervision of AC input quantities
enabling single or three phase trip • Large HMI with virtual keyboard, function push
Most important protection functions buttons, and three color LED indications with
• General current and voltage protection alarm descriptions
• Voltage functions Measurements
• Two step phase- and residual overvoltage • U, I, P, Q, S, f and cos Φ
protection with definite and inverse time • Frequency measurement with accuracy of ± 2 mHz
characteristics Metering
• Two step undervoltage protection with definite • Energy metering function for energy statistics
and inverse time characteristics • Pulse counting support for energy metering
• Current functions Communication
• Instantaneous phase- and residual overcurrent • IEC 61850-8-1 including GOOSE messaging
protection • IEC 62439-3 Parallel Redundancy Protocol (PRP)
• Four step phase- and residual directional • IEC 62439-3 High-availability Seamless
overcurrent protection Redundancy (HSR)
• Thermal overload protection • IEC/UCA 61850-9-2LE Process bus for up to 4
• Breaker failure protection MUs
• Pole discordance protection • IEC 60870-5-103, DNP 3.0, SPA, LON protocols
• Stub protection • RSTP redundant communication
• Differential functions Engineering, testing, commissioning and
• High impedance differential protection maintenance
• Secondary system supervision • Protection and control IED manager PCM600 for
• Fuse failure supervision configuration, parameterization, Ethernet port/
• Current circuit supervision protocol configuration, online debugging and
• Control for one circuit breaker disturbance handling
• Forcing of binary inputs and outputs for faster • Accurate time-synchronization through PTP
and easier test and commissioning (IEC/IEEE 61850-9-3), SNTP, DNP 3.0,
• Flexible product naming by mapping utility IEC IEC 60870-5-103 or IRIG-B
61850 model to that of 650 series model • Up to four Ethernet ports that can be freely
Hardware configured as single or redundant pairs
• 1/2 x 19” 6U height case Accessories
• Power supply modules from 24 to 250 V DC ± • COMBITEST test system
20 % • COMBIFLEX auxiliary relays
• TRM modules each with 12 analog inputs • Mounting kits
• Up to 3 I/O modules Documentation
• Binary input module with 16 inputs • Role based documentation for high efficiency
• Binary output module with 24 outputs in engineering, commissioning, operations and
• Binary input/output module with 8 inputs and maintenance
12 outputs
• Connector types: compression or ring-lug Technical details are available in the REQ650
Product Guide.

Hitachi Energy We reserve the right to make technical changes We reserve the right to make technical changes
Grid Automation Products or modify the contents of this document without or modify the contents of this document without
721 59 Västerås, Sweden prior notice. With regard to purchase orders, the prior notice. With regard to purchase orders, the
Phone: +46 10 738 00 00 agreed particulars shall prevail. Hitachi Energy agreed particulars shall prevail. Hitachi Energy
Ltd. does not accept any responsibility Ltd. does not accept any responsibility
whatsoever for potential errors or possible lack whatsoever for potential errors or possible lack
of information in this document. of information in this document.
hitachienergy.com/protection-control 4CAE000285 REV E

You might also like