Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

FM Global

Property Loss Prevention Data Sheets 6-9


April 2021
Page 1 of 44

INDUSTRIAL OVENS AND DRYERS

Table of Contents
Page

1.0 SCOPE ................................................................................................................................................... 3


1.1 Changes ............................................................................................................................................ 3
1.2 Hazard .............................................................................................................................................. 3
2.0 LOSS PREVENTION RECOMMENDATIONS ....................................................................................... 3
2.1 FM Approved Equipment .................................................................................................................. 3
2.2 Construction and location ................................................................................................................. 4
2.2.1 Oven Location ......................................................................................................................... 4
2.2.2 Oven Construction and Insulation ........................................................................................... 4
2.2.3 Ducts ....................................................................................................................................... 4
2.2.4 Low-Oxygen Atmosphere Ovens ............................................................................................ 5
2.3 Protection ........................................................................................................................................... 5
2.3.1 Building Fire Protection ........................................................................................................... 5
2.3.2 Oven/Dryer Fire Protection ...................................................................................................... 5
2.3.3 Automatic Sprinkler Arrangement ............................................................................................ 5
2.3.4 Spray Dryers Handling Combustible Products ........................................................................ 8
2.4 Equipment and Processes ................................................................................................................ 9
2.4.1 Oven Wiring ............................................................................................................................. 9
2.4.2 Piping Systems ........................................................................................................................ 9
2.4.3 Manually Operated Fuel Shutoff Valves .................................................................................. 9
2.4.4 Air Supply, Oven Ventilation, and Exhaust .............................................................................. 9
2.4.5 Explosion Vents ....................................................................................................................... 9
2.4.6 Temperature Controls ............................................................................................................ 11
2.4.7 Electric Heater Safeguards .................................................................................................. 12
2.4.8 Combustion Safeguards ........................................................................................................ 12
2.4.9 Safety Ventilation ................................................................................................................... 18
2.4.10 Low-Oxygen Atmosphere Ovens ........................................................................................ 23
2.4.11 Autoclaves and Vacuformers Used for Bonding and Curing ............................................... 26
2.5 Operation and Maintenance ............................................................................................................ 26
2.5.1 Human Factors ...................................................................................................................... 26
2.5.2 Operating Parameters ........................................................................................................... 26
2.5.3 Commissioning ...................................................................................................................... 26
2.5.4 Burnouts and Fires in Indirect Air Heaters ............................................................................ 27
2.5.5 Oven Maintenance ................................................................................................................ 27
2.5.6 Explosion Vent Maintenance and Tests ................................................................................ 28
2.5.7 Electrical and Mechanical Maintenance ................................................................................ 28
2.5.8 Inspection of Safety Controls ................................................................................................ 28
2.6 Training ............................................................................................................................................ 28
2.7 Ignition Source Control .................................................................................................................... 28
2.7.1 Hot Work ................................................................................................................................ 28
3.0 SUPPORT FOR RECOMMENDATIONS ............................................................................................... 29
3.1 Fire ................................................................................................................................................... 29
3.1.1 Paint Ovens ........................................................................................................................... 29
3.1.2 Textile Dryers ......................................................................................................................... 29
3.1.3 Fiberboard Dryers .................................................................................................................. 29
3.1.4 Electric Coil Baking Ovens .................................................................................................... 29
3.1.5 Core Ovens ........................................................................................................................... 29
3.1.6 Rubber and Plastic Coating Dryers ....................................................................................... 30

©2021 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
6-9 Industrial Ovens and Dryers
Page 2 FM Global Property Loss Prevention Data Sheets

3.1.7 Coffee, Cocoa, and Peanut Roasters ................................................................................... 30


3.1.8 Organic Heat Transfer Media ................................................................................................ 30
3.1.9 Autoclaves Used for Bonding and Curing ............................................................................. 30
3.2 Fuel Explosions ............................................................................................................................... 30

List of Figures
Fig. 2.3.3.2. Typical sprinkler arrangement for a festooned cloth dryer ........................................................ 6
Fig. 2.3.3.3. Typical sprinkler arrangement for a single-pass carpet dryer ................................................... 7
Fig. 2.3.4 Typical large spray-drying unit ....................................................................................................... 8
Fig. 2.4.8.15(A). Example of application of a combustion safeguard supervising a continuous line pilot
for a group of line burners during lighting-off and firing ................................................... 17
Fig. 2.4.8.15(B). Example of application of a combustion safeguard supervising a pilot for a continuous
line burner during lighting-off and the main flame alone during firing .............................. 17
Fig. 2.4.9.1.5 Typical unacceptable safety ventilation systems using dual purpose fans alone
(recirculation combined with spill exhaust) ............................................................................ 19
Fig. 2.4.9.1.9(A). Selection of a safety ventilating fan. The reduction of volume for fan B exceeds that
of fan A for a given increase in system resistance .......................................................... 20
Fig. 2.4.9.1.9(B). Centrifugal fans; divided into three groups according to blade shape ........................ 20
Fig. 3.3.(A). Example of solvent evaporation-rate curve for a batch oven .................................................. 32
Fig. 3.3.(B). Airflow test illustrating undesirable characteristics usually present inan oven safety
ventilation system using dual purpose fans alone ................................................................... 33
Fig. 3.3.(C). Typical acceptable safety ventilation systems using safety ventilating fans, with no
recirculation through fans .......................................................................................................... 34
Fig. 3.3.1. Schematic of a low oxygen atmosphere oven and solvent recovery system ............................ 35

List of Tables
Table 2.4.9.2.4. Altitude Correction Factors ................................................................................................. 22
Table 2.4.9.2.5.8 Lower Explosive Limit Correction Factors for Elevated Oven Temperatures ................. 22
Table 2.4.10.1 Limiting Oxidant Concentrations for Flammable Gases When Nitrogen or Carbon Dioxide
are Used as Diluents .......................................................................................................... 24
Table 2.4.10.1 Limiting Oxidant Concentrations for Flammable Gases When Nitrogen or Carbon Dioxide
are Used as Diluents (cont’d) .............................................................................................. 25
Table 2.5.8.1. Test Frequency for Functionality Tests of Safety Controls .................................................... 28
Table 3.4.1. Reported Losses, 2009-2019 ................................................................................................... 35

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 3

1.0 SCOPE
This data sheet addresses the inherent fire and explosion hazards in industrial ovens and dryers from fuel,
process combustibles, and flammable volatiles.
When appropriate, references to data sheets concerning ancillary equipment and processes have been
included. The terms “oven” and “dryer” are used interchangeably in this data sheet.
Special types of ovens, dryers, and kilns and associated processes are addressed in other data sheets. (See
Section 4.0.)

1.1 Changes
April 2021. This document has been completely revised. The following significant changes were made:
A. Added a recommendation to install classified electrical equipment in the interior of ovens if flammable
vapor may be present.
B. Added a recommendation to use Data Sheet 6-11 for control of volatile vapor concentration in ducts
if bypass ducts are prohibited by environmental regulations.
C. Added a recommendation to size water supply for simultaneous operation of duct and oven sprinklers
supplied by a common water source.
D. Deleted recommendation for portable extinguishing equipment.
E. Deleted recommendation related to electrical disconnects for electric heaters.
F. Clarified gas detector recommendation to open path IR-type detectors because other technologies are
FM Approved only up to 200°C [392°F].
G. Added recommendation to conduct process hazard analysis for low-oxygen atmosphere ovens to
ensure the atmosphere cannot reach flammable limits under normal operating conditions.
H. Added a recommendation to establish a documented program for safety interlock bypass management.
I. Added recommendation to establish a documented program to address changes in operating
parameters, including conveyor speed to address loss history.
J. Added recommendation to conduct daily visual inspection of explosion vents to check for obstructions.
K. Revised test frequency for some combustion safety devices to annual.
L. Updated loss history.

1.2 Hazard
The primary hazards associated with ovens and dryers are fires and explosions. Many ovens process
combustible products or products that emit flammable vapor during drying or curing. Special atmosphere
ovens can use flammable gas in concentrations above the upper explosive limit (UEL) to aid in processing
or curing. Buildup of combustible deposits or accumulation of flammable gases in any portion of the oven,
dryer, or ductwork can lead to a serious fire or explosion. Operation, ventilation, protection, and housekeeping
recommendations in this data sheet are developed to address the loss experiences of FM Global clients.
See sections 3.2 and 3.3 for more information on fuel and process vapor explosions.
See Understanding the Hazard (UTH): Oven, Dryer and Thermal Oxidizer Fires and Explosions (P0246).

2.0 LOSS PREVENTION RECOMMENDATIONS

2.1 FM Approved Equipment


Use FM Approved equipment, materials, and services whenever they are applicable and available. For a
list of products, materials, and services that are FM Approved, see the Approval Guide.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 4 FM Global Property Loss Prevention Data Sheets

2.2 Construction and location

2.2.1 Oven Location


2.2.1.1 Locate ovens and dryers on the ground floor in buildings of noncombustible construction.
2.2.1.2 Do not locate equipment in below-grade locations. Locating the equipment in below-grade locations
should be avoided due to restricted ventilation and accessibility.
2.2.1.3 Where liquid fuels are used, locate and arrange the fuel system components (other than those directly
associated with the fuel train) in accordance with Data Sheet 7-32, Ignitable Liquid Operations; Data Sheet
7-88, Ignitable Liquid Storage Tanks; and other applicable data sheets.
2.2.1.4 Where hazardous equipment, such as a dip tank or drainboard, is located near the oven entrance,
design and arrange the equipment in accordance with Data Sheet 7-9, Dip Tanks, Flow Coaters, and Roll
Coaters.
2.2.1.5 Keep any necessary storage of cloth, paper, or other combustible materials in process at least 10 ft
(3 m) from the oven and its burners, heaters, etc.

2.2.2 Oven Construction and Insulation


2.2.2.1 Construct ovens and dryers as follows:
A. Use noncombustible construction throughout.
B. Arrange interiors with smooth surfaces to permit easy and complete cleaning.
C. Do not permit inaccessible spaces.
D. Use noncombustible racks, trays, spacers, and containers (where needed), and place them inside ovens
so they can be easily cleaned.
E. Make joints between sections of insulated metal panels tight to minimize the leakage of condensable
vapor into the interiors of the panels.
F. Provide hazardous location rated electrical equipment in the interior of ovens where flammable vapor
is or may be present in accordance with FM Global Property Loss Prevention Data Sheet 5-1.
2.2.2.2 Insulate floors of ovens that operate above 300°F (150°C) to the same degree as the oven walls
and roof, and protect against physical damage. Insulation may consist, for example, of a smoothly troweled
layer of insulating concrete, applied after the side walls are erected. For the aggregates in the insulating
concrete, use perlite, vermiculite, diatomaceous earth, or the equivalent. Use a layer 2 in. (50 mm) thick for
300°F (150°C) oven heat, 3 in. (75 mm) for 400°F (205°C), etc., adding 1 in. (25 mm) for each 100°F (55°C)
increase.
2.2.2.3 For outdoor ovens, use special construction to withstand windstorms. See Data Sheet 1-28, Design
Wind Loads.

2.2.3 Ducts
2.2.3.1 Design and install ducts in accordance with Data Sheet 7-78, Industrial Exhaust Systems.
2.2.3.2 Insulate ducts and ventilate the space around them to keep temperatures of combustible construction
below 160°F (70°C). See Data Sheet 1-13, Chimneys.
2.2.3.3 Locate the exhaust duct inlet in the zone or area where the concentration of flammable vapor inside
the oven or dryer is greater.
2.2.3.4 Pitch ducts in which flammable vapor condenses so they drain to suitable traps or other safe locations.
2.2.3.5 Avoid the use of a common manifold exhaust duct from multiple ovens or with other equipment. This
increases the fire and explosion exposure from one to the other. However, common exhaust ducts may be
necessary where ovens are connected to solvent recovery systems and certain fume disposal or cleaning
equipment. See Data Sheet 6-11, Thermal and Regenerative Catalylic Oxidizers.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 5

2.2.3.6 Local regulations may prohibit the use of bypass ducts for environmental reasons. If bypass ducts
are prohibited by local regulations, ensure vapor concentration in the ductwork is controlled in accordance with
FM Global Property Loss Prevention Data Sheet 6-11.

2.2.4 Low-Oxygen Atmosphere Ovens


2.2.4.1 Minimize air infiltration and loss of atmosphere by ensuring that the oven and ducts are essentially
gas-tight. Provide gaskets on service doors to minimize leakage.
2.2.4.2 Design the end openings for the product transfer to minimize air and inert atmosphere movement
through the entrance and exit openings.

2.3 Protection

2.3.1 Building Fire Protection


2.3.1.1 Provide sprinklers at the ceiling level based on the surrounding occupancy.

2.3.2 Oven/Dryer Fire Protection


2.3.2.1 Provide automatic sprinkler protection in the oven or dryer under any of the following conditions:
A. Construction is combustible.
B. Material being processed is combustible.
C. Racks, trays, spacers, conveyors, or containers are combustible.
D. Accumulations of combustible drippings or deposits are present on the interior oven surfaces or on
racks, trays, etc.
E. Provide sprinkler protection for dipped or flow-coated metal at least in the part of the oven where dripping
occurs.
F. Provide automatic sprinklers in ducts or plenum chambers that accumulate combustible deposits, and
in the housings or impeller casings of large, important fans. See Data Sheet 7-78, Industrial Exhaust
Systems, for protection for ducts, fans, and stacks.
2.3.2.2 Conduct a study to identify the appropriate response of critical equipment (e.g., fuel supply/heating
system, conveyors, fans, dampers) upon actuation of the sprinkler system. Factors for determining the proper
response include the design of the oven or dryer, the source(s) of combustible materials, the ability to isolate
combustible sources, the impact of fresh air, and the consequences of shutting the equipment down or
keeping it in operation. Provide interlocks to automatically perform these actions, as determined by the study.
See other data sheets for more detailed information on appropriate actions for specific equipment, processes,
and/or occupancies.

2.3.3 Automatic Sprinkler Arrangement

2.3.3.1 General System Design


Design the system as follows:
A. Use sprinklers with a temperature rating approximately 50°F (28°C) higher than the high temperature
limit setting.
B. Arrange the sprinklers on a maximum spacing of 8 ft by 8 ft (2.4 m by 2.4 m).
C. Design sprinklers to discharge at least 20 gpm (75.7 L/min) from 12 sprinklers. Ensure a minimum
discharge pressure of 7 psi (0.5 bar) is maintained from all sprinklers. For heavy festooned materials, such
as plastic and linoleum, increase the sprinkler flow to 30 gpm (113.6 L/min).
As a general rule, the footprint of the oven/dryer can be used as the sprinkler operating area for smaller
equipment. For larger ovens or dryers (see Figures 2.3.3.2 and 2.3.3.3), accounting for 12 sprinklers to
operate is sufficient.
D. Where duct and oven sprinklers share a common supply, the design should accommodate simultaneous
operation.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 6 FM Global Property Loss Prevention Data Sheets

E. Install the system in accordance with Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers.
F. Locate piping on the outside of the oven, with the sprinklers nipple-down in a pendant position by
inverted U bends. If there is not room for the sprinklers themselves, place them in dome-shaped recesses
at least 10 in. (250 mm) in diameter.

2.3.3.2 Festooned Cloth Dryers


Install automatic standard sprinklers in festooned cloth dryers, as shown in Figure 2.3.3.2. For protection
within the festoons, install pendent standard or sidewall sprinklers in a staggered arrangement.

Fan
Fan Fan chamber
Cloth Heater
Roll

Work space

Roll
Fan
Fan Heater Fan chamber

Vapor drying B Baking


Section B-B
Section A-A

Duct Duct Duct

Fan
Fan Fan LEGEND
- Automatic upright standard
sprinkler
- Automatic pendent standard
Roll sprinkler
A A - O.S.&Y. sprinkler central
valve
- Pipe rise or drop

Supply

Plan

Fig. 2.3.3.2. Typical sprinkler arrangement for a festooned cloth dryer

2.3.3.3 Carpet Dryers


If carpet cloth makes a single pass between closely spaced hot air ducts, install automatic standard sprinklers
as shown in Figure 2.3.3.3.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 7 FM Global Property Loss Prevention Data Sheets

Air
intake

Fan Fan

Carpet Carpet

SECTION B-B SECTION C-C

Air
intake Exhaust Exhaust

Supply

Fan Fan

Carpet

Recirculating ductwork
SECTION A-A

B C
Fan chamber
Air intake

A Exhaust
A

Exhaust

Supply

B C
PLAN LEGEND
Automatic upright standard sprinklers
Automatic pendent standard sprinklers
Pipe rise or drop

Fig. 2.3.3.3. Typical sprinkler arrangement for a single-pass carpet dryer

2.3.3.4 Festooned Paper, Linoleum, and Plastic Dryers


Provide automatic sprinkler protection in accordance with 2.3.3.1. Provide a minimum clearance of 18 in.
(450 mm) between sprinklers and the top of paper festoons.

2.3.3.5 Organic Heat Transfer Media


See Data Sheet 7-99, Organic and Synthetic Fluids, for additional design guidelines for ovens heated with
organic heat transfer media.

2.3.3.6 Ovens, Dryers, and Lumber Dry Kilns for Wood Processing
For details of automatic sprinkler and deluge system design, see Data Sheet 7-10, Wood Processing and
Woodworking Facilities.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 8 FM Global Property Loss Prevention Data Sheets

2.3.3.7 Printing Plants


For ovens or dryers associated with printing operations, provide automatic fire protection in accordance with
Data Sheet 7-96, Printing Plants.

2.3.4 Spray Dryers Handling Combustible Products


Install sprinklers in spray dryers handling combustible products (see Figure 2.3.4) as follows:

Fixed temp. heat-responsive


device for deluge valve

Air diffuser plate


AS
Dust
Sprinklers or Product feed collector Roof
spray nozzles as
applicable AS
20' Storage
bin
(fines)
AS Exhaust
Product fines blower
Explosion vents

AS
100'

Sprinklers or
spray nozzles as
applicable

Exess-temp.- AS
limit switch Skirt
Exess-temp.-
Hot air limit switch
furnace
AS
Combustion Fixed temp.heat
chamber responsive device for
deluge valve
AS

Deluge valve
(if applicable)

Dried product to packing


or process
A.S. Main

Fig. 2.3.4 Typical large spray-drying unit

A. Locate the sprinklers or water spray nozzles around the periphery of the dryer at the top. For dryers
having an air-diffuser plate above the product spray head, locate the sprinklers or spray nozzles beneath
the diffuser plate; no protection is needed in the space above. Space sprinklers 8 ft (2.4 m) apart around
the periphery.
B. In spray dryers having a skirt, install a second set of sprinklers or water spray nozzles beneath the
skirt, using the same arrangement and spacing as at the top of the dryer.
C. Make sure automatic sprinklers, if used, have temperature ratings appropriate for the maximum
operating temperature of the equipment. For operating temperatures above 650°F (343°C), use open-head
deluge systems.
D. Actuate deluge systems, if used, by fixed-temperature heat-responsive devices having temperature
settings from 100°F to 125°F (55°C to 70°C) above the maximum operating temperature of the equipment.
Locate the devices at the top of the dryer. Alternatively, if there is an air-diffuser plate, locate the devices

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 9

immediately below the diffuser plate. Do not use rate-of-rise detection devices because of rapid
temperature changes during startup.

2.4 Equipment and Processes

2.4.1 Oven Wiring


2.4.1.1 Install wiring in accordance with locally or nationally recognized applicable code requirements. Use
wiring insulation suitable for the maximum temperatures employed.

2.4.2 Piping Systems


2.4.2.1 For gas-fired or oil-fired ovens or dryers, arrange fuel supply, transfer, and piping systems safely as
outlined in Data Sheet 7-32, Ignitable Liquid Operations; Data Sheet 7-88, Ignitable Liquid Storage Tanks;
Data Sheet 7-54, Natural Gas and Gas Piping; and other FM Global recommended practices for handling,
piping, and storing gas and oil.
2.4.2.2 For oil-fired ovens or dryers, install emergency shutoff valves or equivalent interlocks in the oil supply
piping system to ensure the prompt shutdown of oil flow in the event of a fire. Install these valves in addition
to safety shutoff valves installed in the combustion safeguard system (see Section 2.4.8.8). The number
and location of emergency shutoff valves will vary depending on the piping system size, complexity, and the
potential exposure created by a release. See Data Sheet 7-32, Ignitable Liquid Operations, for additional
information on these devices and their appropriate placement in the piping system.

2.4.3 Manually Operated Fuel Shutoff Valves


2.4.3.1 Provide each gas-fired or oil-fired oven with a manually operated emergency fuel shutoff valve. Locate
these valves so they are prominent and accessible, preferably outside the area of the oven.

2.4.4 Air Supply, Oven Ventilation, and Exhaust


2.4.4.1 For ovens and dryers located in a building, provide sufficient make-up air to the room/building
containing the oven or dryer to ensure all air required for combustion and safety ventilation is available. This
is in addition to the air required for room/building ventilation and any other equipment that uses air.
2.4.4.2 When air is provided by dampers or louvers, provide interlocks to prevent oven and dryer operation
unless the dampers/louvers are proved in the open position.
2.4.4.3 Provide interlocks for any fans/blowers required for room air supply, combustion air, safety ventilation
in the oven or dryer, air circulation within the oven or dryer, and exhaust from the oven or dryer in accordance
with Sections 2.4.4 and 2.4.9.
2.4.4.4 Select oven recirculation and exhaust fans compatible with the maximum exhaust temperature, the
material, and the vapor present during operation.

2.4.5 Explosion Vents


Recommendations in this section are applicable to the design of explosion vents and latches for ovens and
dryers other than spray dryers. For explosion protection of spray dryers, see Data Sheet 7-76.
For protection of buildings and other structures, see Data Sheet 1-44, Damage-Limiting Construction; Data
Sheet 7-76, Prevention and Mitigation of Combustible Dust Explosions and Fires; and other applicable data
sheets.
2.4.5.1 Provide explosion vents for ovens where there are fuel or process vapor explosion hazards.
2.4.5.2 Design explosion vents in accordance with the following, as applicable:
A. For weak construction (structure/equipment designed to withstand internal pressures less than 1.5
psi [0.1 bar]), size explosion vents in accordance with Data Sheet 1-44, Damage-Limiting Construction.
B. For strong construction (structure/equipment designed to withstand internal pressures greater than 1.5
psi [0.1 bar]), size explosion vents in accordance with Data Sheet 7-32, Ignitable Liquid Operations.
C. For installations with multiple zones, treat each zone separately when calculating explosion venting.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 10 FM Global Property Loss Prevention Data Sheets

D. For ovens having horizontal conveyors nearly as wide as the oven, with a relatively large volume below
the conveyor where the flammable mixtures could accumulate, locate vents on the oven wall both above
and below the plane of the conveyor.
E. Distribute vents evenly along the length of the oven so the maximum distance between vents does
not exceed five times the width or height of the oven, whichever is smaller.
F. Locate vents as close as possible to ignition sources. If the oven is compartmentalized, install as much
venting as practical near ignition sources.
G. Provide a distance of at least two explosion vent diameters between an explosion vent outlet and any
large, flat obstruction (e.g., a wall). Use hydraulic diameter for vents that have a cross section other than
circular.
H. Preferably, vent outdoors. For ovens located indoors, a vent pipe or duct may sometimes be needed
to direct discharge to a safe outdoor location. Vent pipes and ducts will, however, increase the vented
explosive pressure experienced by the equipment. Vent pipes and ducts with a length-to-diameter ratio
(L/D) of 1 or less can usually be installed on either high-strength or low-strength equipment if there are no
obstructions in the discharge. Do not vent indoors unless the building room volume is at least ten times
the vented volume of the oven.
I. Use square or circular vents whenever possible. Where rectangular vents are unavoidable, ensure the
longer side is not more than 3 times the shorter side.
J. Use lightweight vent panels, preferably not more than 2.5 lb/ft2 (12 kg/m2).
K. Ensure there are no combustibles exposed to the flame jet that would exit the vent. If possible, allow
for a distance of 50 ft (15 m) between vents and combustibles that are easily ignited by a short-duration
fire exposure.

2.4.5.3 Vent Panel or Door


2.4.5.3.1 If vent doors are hinged on one side and held by latches on the other side, secure the vent doors
as follows:
A. Use FM Approved oven door latches for explosion venting.
B. Use the following formula to calculate the maximum allowable release force per latch. Because of the
effect of the hinge restraint, only consider one half of the force on the door surface in the calculations
for the latch settings and selection.
HINGED DOOR FORMULA:
A × Pr = F × L A = Panel area, ft2 (m2)
2 Pr = Release pressure, lb/ft2 (Pa)
Or F = Latch release force, lb (N)
L = Number of latches
A × Pr = F
2 L
Example A
Hinged door area (A) 8 ft2 (0.74 m2)
Design release pressure (Pr) 20 lb/ft2 (957.6 Pa)
Number of latches (L) 3
English
8 ft2 × 20 lb/ft2 = F = 26.7 lb maximum allowable release force per latch
2 3
Metric
0.74 m2 × 957.6 Pa = F = 118.1 N maximum allowable release force per latch
2 3
Note: 118.1 N × 0.1020 kg/N = 12.0 kg

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 11

C. Obtain the latch release force from the manufacturer’s literature and its listing in the Approval Guide.
D. Select and install the hinges to resist at least 200% of the total latch release force.
E. Secure or restrain vent panels and doors at the bottom or on one side as necessary to prevent flying
missile damage. Do not hinge panels at the top, as the panel weight will impede the discharge of gas
through the vent opening. Additionally, the panel may close due to gravity following its operation.
F. Arrange vent doors so they do not close by themselves after opening, thus creating a vacuum inside
the oven after an explosion.
2.4.5.3.2 If vent wall panels are secured by latches on two or four sides, with no hinges, secure the panels
as follows:
A. Use FM Approved explosion-relieving fasteners.
B. Roof panels may be secured by the panel weight alone.
C. Both wall and roof panels may be secured by shear pins of specific shear strength that will break at
the designed panel-oven release pressure.
D. Use the following formula to calculate the maximum allowable release force per latch. Deduct the weight
of the roof panels from the design release pressure before calculating the fasteners or latch forces.
UNHINGED PANEL FORMULA:
A × Pr = F × L

Or

A × Pr = F
L
Example B
Panel Area (A) 8 ft2 (0.74 m2)
Design release pressure (Pr) 20 lb/ft2 (957.6 Pa)
Number of latches (L) 4
English
8 ft2 × 20 lb/ft2 = F = 40 lb maximum allowable release force per latch
4
Metric
0.74 × 957.6 = F = 177.2 N maximum allowable release force per latch
4
Note: 177.2 N × 0.1020 kg/N = 18.1 kg

2.4.5.4 Explosion vents need not be provided on low-oxygen atmosphere ovens due to the difficulty of
maintaining the oven gas tight. The inert atmosphere and the emergency inert system provide appropriate
explosion prevention.

2.4.6 Temperature Controls


2.4.6.1 Never exceed the safe operating temperature of the dryer or oven.
2.4.6.2 Provide an excess temperature limit control (requiring manual reset) that is independent of any
automatic or manual temperature control. Arrange the interlock to activate an audible/visual alarm and
automatically shutdown the fuel supply or source of heat. Ensure the excess temperature limit controller
indicates the temperature and is marked with the set point.
2.4.6.3 If combustible materials are processed in the oven, set the limit at least 100°F (55°C) below the
autoignition temperature of the material being processed.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 12 FM Global Property Loss Prevention Data Sheets

2.4.6.4 Locate the sensor for the excess temperature limit control in accordance with a risk assessment to
determine the optimal location for hazard mitigation.
2.4.6.5 For gas-fired or oil-fired ovens and dryers, interlock the excess temperature limit control with the
safety shutoff valves.
2.4.6.6 For steam-heated ovens and dryers, interlock the excess temperature limit control with a self-closing
valve in the steam supply line.
2.4.6.7 For electrically heated ovens and dryers, interlock the excess temperature limit control with a contactor
in the main supply circuit to the heating units. Do not use the contactor that is used for temperature control.
2.4.6.8 Only use components for the excess temperature control that will fail safe (i.e., cause the same
response as an excess temperature condition).
2.4.6.9 For zoned ovens, provide separate excess temperature limit controls in each zone.
2.4.6.10 For zoned ovens, provide an audible/visual low temperature alarm in a zone if a low temperature
condition will result in evaporation of a flammable vapor in a downstream zone exceeding the level that can
be exhausted by the exhaust ventilation system.

2.4.7 Electric Heater Safeguards


2.4.7.1 Protect electric heating units and infrared lamps from physical damage or contact with the work by
guards or baffles.
2.4.7.2 Provide a high temperature interlock, arranged to audibly alarm and shut down the heating system.

2.4.8 Combustion Safeguards


This section provides guidelines for burner system sequencing, combustion safeguards and interlocks for
the prevention of fuel explosions in industrial ovens and dryers.
Basic safeguards for oven and dryer burner systems include:
A. Proof of adequate combustion air and ventilation air.
B. A reliable ignition source before fuel can reach the main burner.
C. A limited trial-for-ignition of the main burner flame.
D. Shutoff of fuel on flame failure. Flame outage is the ultimate effect of undesirable existing conditions
in the fuel-air supplies and fuel-air mixing and ignition-system equipment.
E. At least one hardwired manual emergency shutdown switch through which the operator can shut down
all fuel and ignition energy to the oven or dryer. Locate the emergency shutdown switch to permit operator
access during upset or fire conditions.
F. Safety interlock trips. When an oven or dryer operates automatically without constant operator
attendance, all trip interlocks require manual reset unless the interlock system includes a high-high (or
low-low) redundant interlock. In those cases, operation of the high (or low) interlock may not require a
manual reset provided the control system is designed to automatically restart the oven or dryer when the
trip condition clears. Operation of the high-high or low-low interlock means its associated high or low
interlock did not function and safety shutdown requiring a manual reset is required. All trips require operator
intervention and manual reset for ovens and dryers not designed for unattended automatic operation.
The proper combination of interlocks and flame-supervisory combustion safeguards is essential. Supervision
of fuel pressures, airflow, essential air-damper positions, fans, purging, oil temperatures, and oil-atomizing
medium is important for anticipating the development of unsafe conditions and for initiating a safety shutdown
even though flame outage has not yet occurred. This supervision gives further protection by preventing
improper sequences of operation that could result in a hazardous condition.

2.4.8.1 Purge Ventilation


2.4.8.1.1 At gas-fired and oil-fired ovens, provide an automatic pre-ventilation period to purge the work
chambers and/or combustion chambers of fuel vapor and flammable gases that may have accumulated during
shutdown before fuel safety shutoff valves and electric ignition can be energized.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 13

For indirect-fired ovens, an automatic purge for the work chambers may be omitted. A manually controlled
purge by the best available means is acceptable provided no flammable vapor is given off by the materials
processed.
For direct-fired ovens, manually controlled purge by the best available means is acceptable, provided the
following criteria are met:
A. The volume of the oven, based on external dimensions, is less than 350 ft3 (10 m3).
B. No flammable vapor is given off by the work processed.
C. Interlocks are provided and their contacts wired into the oven’s safety control circuit.
This will ensure opening of oven doors and fresh-air inlet dampers and operation of fans before the fuel safety
shutoff valve(s) can be energized and opened and electric ignition activated.
For both mechanical and natural-draft ventilation systems, it may be necessary to open doors and have the
fresh-air inlet and exhaust dampers in the open position to provide sufficient purge air. Provide interlocks
to prove the dampers and doors in the correct position or use mechanical stops and cutaway dampers.
2.4.8.1.2 Provide a purge of at least four volume changes with fresh air by operating the recirculating and
ventilating fans.

2.4.8.2 Purge Relighting


2.4.8.2.1 In the event of a safety shutdown, a relight may be attempted without a timed re-purge provided
there is sufficient mechanical ventilation to prevent the accumulation of a flammable atmosphere. Continued
operation of the fans (supply, exhaust, and recirculation) may maintain the purged condition.
2.4.8.2.2 Where sufficient mechanical ventilation is not available, provide a purge as outlined in Section
2.4.8.1.
2.4.8.2.3 Reignite burners having pilots with the pilots. Do not attempt to ignite burners from the hot refractory.
Reignite burners individually in accordance with the normal lighting sequence.

2.4.8.3 Combustion-Air Blower and Products-of-Combustion Ventilating Fan Interlocks


2.4.8.3.1 Interlock each fan/blower to ensure that they are placed in operation before the fuel safety shutoff
valves and electric ignition can be energized. This also ensures that failure of any fan will automatically close
the safety shutoff valves and deactivate the ignition system. Ensure fans and blowers are multi-belt driven
unless a direct coupling drive is used. The following are acceptable interlocking methods:
A. Mount a rotational switch on the fan’s drive shaft and wire it into the safety control circuit. The switch
closes when the fan reaches the predetermined speed for adequate ventilation.
B. Wire the auxiliary contact of an overcurrent-protected starter for the fan motor into the safety control
circuit.
C. Wire a contact of a relay, whose coil is energized from the load side of an overcurrent-protected starter
for the fan motor, into the safety control circuit.
D. Energize the safety control circuit directly (or through a transformer) from the load side of an
overcurrent-protected starter for the fan motor.
Caution: The protection of the starter should not exceed the conventional rating required for the fan motor
alone.
2.4.8.3.2 Provide an airflow or differential pressure switch for each fan wired into the safety control circuit.
This is not needed for oil burners where there is a direct shaft connection between the fuel pump and
combustion air fan.

2.4.8.4 Fuel Pressure Interlocks


2.4.8.4.1 Provide fuel pressure interlocks, low and high gas pressure switches for gas burners, low oil
pressure switches for oil burners, and low atomizing medium pressure switches (air or steam) for oil burners.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 14 FM Global Property Loss Prevention Data Sheets

2.4.8.5 Oil Preheating Equipment and Low-Oil-Temperature Interlocks


2.4.8.5.1 Provide oil temperature interlocks for heavy oil burners that require preheated oil. The interlocks
should prevent lighting-off if the oil temperature is below that recommended by the burner manufacturer, and
shut off all fuel (close oil safety shutoff valves) if oil is not at the recommended temperature during firing.

2.4.8.6 Proved Low-Fire-Start Interlock


2.4.8.6.1 Provide a low-fire-start interlock where the burner must be started at a low fire setting.

2.4.8.7 Individual Burner Valves and Observation Ports


2.4.8.7.1 At manually operated ovens, provide a separate, manually operated quarter-turn valve for each
burner whenever practical. Use valve handles that are constructed of metal and visually indicate the ON and
OFF positions.
2.4.8.7.2 At manually operated ovens, provide observation ports for each of the burners so pilots, electric
igniters and flame-sensing elements of combustion safeguards can be easily observed.
2.4.8.7.3 Locate observation ports for burners fueled through individual valves so that the ignition sources
can be positively observed before and while the operator opens the valve to light the burner.

2.4.8.8 Safety Shutoff Valves


2.4.8.8.1 For gas-fired burners, provide two safety shutoff valves for each pilot and main burner system, a
system being one or more burners operated as a unit. If the pilot or burner system input exceeds 400,000
Btu/hr (117 kW), provide proof-of-closure on one of the safety shutoff valves.
Exception: If an explosion-resistant (including heat recovery system) radiant tube-type of heating system
is used, a single safety shutoff valve is adequate.
2.4.8.8.2 For a multi-burner system, if it is desired to shut off an individual burner for process reasons or
upon loss of flame, provide a common main safety shutoff valve and individual safety shutoff valve with
proof-of-closure at each burner. Verify the burner safety shutoff valve is closed after shutdown. If it is not
proved closed, ensure all safety shutoff valves in the system are closed.
2.4.8.8.3 For oil-fired burners, provide a single safety shutoff valve. Or, provide two safety shutoff valves,
one having proof-of-closure, if (a) the oil pressure is greater than 125 psi (862 kPa), (b) the oil pump is
independent of the burner, or (c) the oil pump operates during gas-firing for combination oil/gas burners.
Exceptions:
A. If an oil burner using No. 4 or lighter oil is provided with an individual control unit (pump, pressure
regulators, and shutoff valve) in the burner assembly, a safety shutoff valve external to the burner assembly
may be omitted. The control unit should shut off fuel within 5 seconds following de-energization of the
oil-burner motor.
B. If an oil burner using No. 4 or lighter fuel oil is provided with an individual motor-driven blower in the
burner assembly and air supplied by this blower is used to aspirate and supply the fuel oil to the burner,
a safety shutoff valve external to the burner assembly is not required. The system should shut off fuel
within five seconds following de-energization of the combustion air blower motor.
C. If an oil burner using No. 4 or lighter fuel oil is of the aspirating type, using compressed air to withdraw
oil from a reservoir, a fuel-oil safety shutoff valve cannot usually be practically applied. A gas safety shutoff
valve should be installed in the aspirating air line to the burner to shut off fuel within five seconds following
de-energization of the safety shutoff valve.
2.4.8.8.4 Provide a permanent and ready means to periodically check the tightness of the main gas burner’s
safety shutoff valves. See Data Sheet 6-0, Elements of Industrial Heating Equipment.

2.4.8.9 Fuel-Air Mixers


2.4.8.9.1 Do not use low-pressure (below 1 psi [6.9 kPa, 0.069 bar]) atmospheric inspirators. A gas-air mixer
with a blower or compressor is preferable to a high-pressure atmospheric inspirator.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 15

2.4.8.10 Limiting Burner Turndown


2.4.8.10.1 Limit burner turndown at gas and oil burner systems so stable flames and complete combustion
are obtained at the low firing rate. Gas-fired oven heaters, for example, may have burners using zero
governor inspirator mixers where the heater pressure is highly negative with respect to room pressure. Limit
turndown so the proportion of air at the mixer does not fall below 85% of the amount needed for complete
combustion. Where the desired turndown would reduce the air below 85%, the diaphragm of the zero governor
may be specially loaded by connecting the space in the housing above the diaphragm (which is normally
vented outdoors or other safe location) to the combustion heater chamber.
2.4.8.10.2 At gas-fired heaters that have burners using low-pressure atmospheric inspirator mixers, install
the burner only for constant firing at a fixed rate or on/off firing. It may be used for high-low or modulated firing,
provided the low firing is 50% or more of rated burner input.

2.4.8.11 Combustion Air Piping Systems


2.4.8.11.1 Interlock the combustion air and fuel supplies so failure of either will shut off and lock out the fuel.
Fuel gas usually leaks through zero governors if gas cocks have not been closed after blower shutdown.
The mixture in the combustion air piping may be ignited by a flashback through the burner started by hot
furnace refractory. Even with furnaces under 100 ft3 (2.8 m3) in volume, provide interlocking where two or more
furnaces are supplied by one blower.
2.4.8.11.2 If the combustion air blower can aspirate fuel, provide an interlock to prevent blower operation
during the purge period to minimize possible leakage from the aspirating effect.

2.4.8.12 Automatic Fire Checks and Safety Blowouts


2.4.8.12.1 Provide automatic fire checks and safety blowouts (sometimes called “backfire preventers”) in
piping systems that distribute flammable air-gas mixtures from gas mixing machines to protect the piping and
the machines in the event of an explosion. (Note: Automatic fire checks and safety blowouts cannot be
installed in burner systems using blower mixers that do not permit valves to be located in piping downstream
from their outlets.)
Install automatic fire checks and safety blowouts in accordance with the following recommendations:
A. Install the automatic fire checks upstream, as close as practicable to the burner inlets. Be certain to
follow the fire check manufacturer’s instructions. Either install a separate fire check at each burner or at
each group of burners. The second method is generally more practical if a system consists of many
closely spaced burners.
B. Provide a separate, manually-operated gas cock at each automatic fire check to shut off the flow of
the air-gas mixture after a flashback has occurred. Locate the cocks upstream, as close as practical to the
inlets of the automatic fire checks.
Caution: Never reopen any of these cocks after a flashback has occurred until the fire check has cooled
sufficiently to prevent reignition of the flammable mixture and it has been properly reset.
C. Provide a safety blowout device (backfire preventer) near the outlet of each gas mixing machine where
the piping is larger than 2.5 in. (65 mm) NPS or equivalent to protect the machine if an explosion passes
through an automatic fire check.
2.4.8.12.2 Follow the manufacturer’s instructions in installing these devices. Acceptable safety blowouts are
available from some manufacturers of gas-mixing machines. They incorporate the following components
and design features:
• a flame arrestor
• a blowout disk
• a provision for automatically shutting off the supply of the air-gas mixture to the burners in the event
of a flashback passing through an automatic fire check

2.4.8.13 Pilots and Ignitors


2.4.8.13.1 For the main burners of gas-fired and oil-fired ovens, use premixed pilots with sufficiently large
capacities to ensure ignition of the main burners.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 16 FM Global Property Loss Prevention Data Sheets

2.4.8.13.1.1 External oven heaters can be provided with pilots with low-pressure (gas pressure below 1.0
psi [6.9 kPa, 0.069 bar]) atmospheric inspirator mixers supplied with undiluted gas, if the heater chambers
into which the pilots fire are continuously maintained sufficiently negative (at least -0.20 in. water column [-50
Pa, -0.5 mbar]) with respect to room-air pressure. To ensure this negative pressure, induce the proper amount
of fresh air for complete combustion using motor-driven fans.
2.4.8.13.1.2 The main burners of gas-fired and oil-fired automatic and semi-automatic-lighted ovens can be
ignited by normal gas-fired or oil-fired pilots. Provide combustion safeguards wired into the safety control
circuit as described in Section 2.4.8.15, unless the ovens are indirect-fired and have explosion-resistant
heating systems.
2.4.8.13.1.3 Gas and light (No. 4 or lighter) oil-fired ovens can be provided with direct electric ignition if the
design of the burners renders gas pilots impractical.
2.4.8.13.2 Ensure the pilot flame is stable, even during substantial fluctuations in draft or back pressure.
2.4.8.13.3 Ruggedly design each pilot mounting assembly and install securely so the pilot cannot be moved
out of the position where it will furnish reliable ignition for the burner.

2.4.8.14 Direct Electric Ignition


2.4.8.14.1 At gas or light-oil burners, including multi-nozzle power burners and continuous-line burners having
direct electric ignition, automatically limit the trial-for-ignition periods to 5 seconds. Do not use direct electric
ignition for main burners with a fuel input greater than 2,500,000 Btu/hr (732 kW) unless a low-fire start is
provided using a slow-opening valve or a modulating motor with interlock.
2.4.8.14.2 If more than 5 seconds is needed to reliably ignite the burner due to time needed for fuel to reach
the burner, the trial-for-ignition period can be extended if it can be demonstrated that 25% of the LEL cannot
be exceeded during the extended time.

2.4.8.15 Combustion Safeguards


2.4.8.15.1 Install FM Approved combustion safeguards at gas-fired and oil-fired ovens to supervise burner
flames. It is acceptable to supervise the flames of two adjacent main burners with a single combustion
safeguard if the burners will ignite one from the other at all firing rates. The maximum flame failure response
time is 4 seconds.
2.4.8.15.2 Supervise the main burner flame alone rather than supervising the pilot and main burner flames
simultaneously. With the former system, the main burner’s trial-for-ignition periods can be automatically
limited.
2.4.8.15.3 Install flame-sensing elements in accordance with the manufacturer’s instructions, and ensure
they are securely mounted so their position in respect to the pilot and main burner flames will not change.
Combustion safeguards are usually practical for line burners if they are arranged in groups so that a
combustion safeguard for each group may supervise a continuous line pilot during light-off and firing (see
Figure 2.4.8.15(A)). Combustion safeguards are also usually practical if continuous line burners (including
radiant-cup burners or line-burner sections attached consecutively to a common burner manifold and having
a reliable flame propagation characteristic from one to the other) are arranged in groups so that a combustion
safeguard for each group will supervise a pilot during lighting-off and main flame alone during firing (see
Figure 2.4.8.15(B)).

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 17

One group of line burners


(other groups protected likewise)

Line 3
burners
Continuous
premixed Pilot gas
line pilot

Main burner gas


(one psi or over)
Flame sensing
element
2 1

1. Approved main gas safety shutoff valve. Manual-opening, automatic-closing


valve or automatic-opening and closing valve, to suit firing method used.
2. Permanent and ready means for making periodic tightness checks of
main gas safety shutoff valve.
3. Approved pilot gas safety shutoff valve.

Fig. 2.4.8.15(A). Example of application of a combustion safeguard supervising a continuous line pilot for
a group of line burners during lighting-off and firing

3 4 5

Premixed gas Continuous line burner


50 ft. (15.3m) max.
Pilot burner

Premixed gas

1 2 Burner
manifold

1. Approved main gas safety shutoff valve. Manual-opening, automatic-closing


valve or automatic-opening and closing valve, to suit firing method used.
2. Permanent and ready means for making periodic checks of main gas safety
shutoff valve.
3. Approved pilot gas safety shutoff valve.
4. Pilot flame sensing element. Wired into safety control circuit so that it is
automatically cut out of combustion safeguard's flame detecting circuit at
end of trial-for-ignition period. (Flame rod shown, but a photoconductive
cell, infrared or ultraviolet scanner may be used.)
5. Main flame sensing element. Wired into combustion safeguard's flame
detecting circuit, unlike pilot flame sensing element 4, it is not cut out but
remains in the flame detecting circuit during light-off and firing. (Flame rod
shown, but a photoconductive cell, infrared or ultraviolet scanner may
be used.)

Fig. 2.4.8.15(B). Example of application of a combustion safeguard supervising a pilot for a continuous line burner
during lighting-off and the main flame alone during firing

2.4.8.16 Operation Sequencing


2.4.8.16.1 For gas and oil pilots and main burners, automatically limit the trial-for-ignition (interrupted pilots)
and main flame establishing periods to 15 seconds.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 18 FM Global Property Loss Prevention Data Sheets

2.4.8.16.2 Limit automatic recycling to one attempt to relight after accidental flame failure during firing. Do
not use automatic recycling except for automatically lighted ovens having pilots.
2.4.8.16.3 At continuous-line gas burners, the total length of burner supervised by a single FM Approved
combustion safeguard should be not more than 50 ft (15.3 m). At burners where the total length exceeds 20
ft (6.1 m) the trial-for-ignition periods should be automatically limited to not more than 15 seconds (see Figure
2.4.8.15(B). This includes those consisting of a limited number of individual radiant-cup burners or line-
burner sections that are supplied from a common burner manifold, have reliable flame propagation between
consecutive burners without special external flame-propagation devices, and are located directly adjacent
to one another.

2.4.9 Safety Ventilation

2.4.9.1 General
2.4.9.1.1 Dilute the vapor evaporated at the peak rate to a concentration not exceeding 25% of the LEL using
safety ventilation. Flammable vapor concentrations up to 50% of LEL are permitted if continuous vapor
concentration indicators and controllers are used as recommended in Section 2.4.9.2.5.
2.4.9.1.2 Provide an automatic pre-ventilation period for each oven startup at gas-, oil-, steam- or electric-
heated ovens to purge the work chamber of any flammable vapor before the heating or electric ignition
systems can be activated and the conveyor placed in operation.
2.4.9.1.3 Provide a purge consisting of at least four volume changes with fresh air.
2.4.9.1.4 Damper Design
2.4.9.1.4.1 If closure or incorrect positioning of any door or damper will prevent proper purging of the entire
oven work chamber, interlock it with the safety-control circuit to ensure proper positioning before and during
the purge period.
2.4.9.1.4.2 Design throttling dampers so the system will handle at least the minimum ventilation rate required
for safety at normal operation when they are set in their maximum throttling position. This can be done by
cutting away part of the dampers or permanently stopping them partially open to produce the necessary
ventilation rate as proved by airflow tests. This does not apply to any dampers that may be required in
connection with special extinguishing systems.
2.4.9.1.4.3 In ovens where dampers and variable-speed fans control the safety ventilation or temperature
by modulating airflow, design the system so that reducing the volume of air cannot reduce the safety
ventilation rate below that required for safe operation. If LEL detectors are used, provide a fast-acting
continuous LEL detector interlocked to shut down the source of heat and solvent or product feed, and bypass
the exhaust to atmosphere where an oxidizer is used, at no more than 50% of the LEL. See Section 2.4.9.2.5.
2.4.9.1.5 Provide a positive safety ventilation system using one or more motor-driven centrifugal fans to safely
dilute and discharge vapor given off by the work to oxidizers/solvent recovery systems or out-of-doors. Do
not return atmosphere containing flammable vapor to the heated work chamber through the fans (see Figure
2.4.9.1.5) unless the system is designed to prevent excessive concentrations. See Section 2.4.9.2 and Data
Sheet 6-11, Thermal and Regenerative Catalytic Oxidizers.
2.4.9.1.6 Circulate the fresh air within the oven to all parts of the work chamber and around the material
being heated. This is best done by motor-driven circulating or recirculating fans so arranged that there are
no pockets where solvent vapor can accumulate.
2.4.9.1.7 Provide interlocks for fans, conveyors, and heating systems to ensure the following:
A. All fans whose failure would adversely affect the safety ventilation rate or flow pattern are placed in
operation before the conveyor can be started.
B. Failure of any fan will automatically stop the conveyor, close the safety shutoff valves, and deactivate
the ignition (of gas-fired or oil-fired ovens) or de-energize electrically heated ovens. If stopping the
conveyor is likely to result in the work igniting, provide interlocks to ensure the following:
1. The conveyor is in operation before the safety shutoff valves can be energized and opened and
the electric ignition system activated (for gas-fired and oil-fired ovens), or the heating system energized
(for electric-heated ovens).

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 19

Damper
Recirculating Inlet blast
fan gate
Fresh air Recirculating Damper
Heater in fan
Heater
radiator
tubes

Recirculating Splitter
Recirculating fan damper
fan
Inlet blast gate
Splitter
Fresh air
damper Heater in
Fresh
air
in Direct gas line burner

Outdoor
exhaust stack Damper

Damper Recirculating fan Recirculating


fan
Heater
Fresh
air Electric
Fresh air in resistance
in heaters

Air Inlet blast gate Air


lock Oven lock
Entrance Exit
Recirculating fans
KEY

Heater Splitter Safety ventilation


damper
Recirculation
Fresh
air in

Fig. 2.4.9.1.5 Typical unacceptable safety ventilation systems using dual purpose fans alone
(recirculation combined with spill exhaust)

2. Failure of the conveyor will automatically close the safety shutoff valves, deactivate the ignition
system, or (for electric-heated ovens) open the contactor in the main power supply.
It is acceptable to move the conveyor semi-automatically to remove work from the oven in the event of a
conveyor stoppage due to fan failure. This may be controlled by a pushbutton switch.
Where an automatic material feeding system supplies a conveyor at a point adjoining the oven entrance
(as with a lithograph oven coater) the feeding system may be interlocked with the fans instead of the conveyor.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 20 FM Global Property Loss Prevention Data Sheets

2.4.9.1.8 Connect safety ventilating fans to their motors by direct coupling or V-belt drive using two or more
belts.
2.4.9.1.9 Select each fan so that, under field conditions, its operating point will fall in the steep portion of
the characteristic curve of volume versus static pressure with fan speed constant (see Figure 2.4.9.1.9(A)).
Increased resistance in the system at ducts and inlets, the effect of outdoor wind conditions or fans drawing
from the same room, etc., will produce the minimum reduction in the safety ventilation rate. To ensure each
fan will have an adequate pressure characteristic for normal safety ventilation duty, select the fan with the
following blade-tip speeds in operating condition:
• At least 7,500 ft/min (2,300 m/min) for fans having backward inclined blades (see Figure 2.4.9.1.9(B),
Group 1)
• At least 6,800 ft/min (2,100 m/min) for fans having radial tip blades (see Figure 2.4.9.1.9(B), Group 2)
• At least 5,000 ft/min (1,500 m/min) for fans having forward curved blades (see Figure 2.4.9.1.9(B), Group
3)

PREFERRED CHARACTERISTIC
Fan A -steep CURVE
Fan speed constant
Fan B -flat Normal operating point
for required safety
ventilation
Static pressure

1 2

c e
an
l
s ist tic
S re is 1
m er
te ract
s
sy a 2
S- ch

Volume Required safety


ventilation
Fig. 2.4.9.1.9(A). Selection of a safety ventilating fan. The reduction of volume for fan B exceeds that of fan A for
a given increase in system resistance

A A
A Trailing tangent

Group 1. Left, backward-inclined. Angle A less than 90°


Group 2. Center, radial-tip. Angle A equals 90°
Group 3. Right, foward-curved. Angle A greater than 90°
Angle A is the blade angle at the tip, that is, the angle between the slope of the blade at the
outer tip and the trailing tangent to the circumference of the wheel.

Fig. 2.4.9.1.9(B). Centrifugal fans; divided into three groups according to blade shape

2.4.9.1.10 Provide a fan interlock in the oven safety-control circuit for each fan whose failure would adversely
affect the safety ventilation rate or flow pattern. There are four acceptable methods:
A. Mount a rotational switch on the fan’s drive shaft and wire it into the safety-control circuit.
B. Wire an auxiliary contact of an overcurrent-protected starter for the fan motor into the safety control
circuit.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 21

C. Wire a contact of a relay whose coil is energized from the load side of an overcurrent-protected starter
for the fan motor into the safety-control circuit.
D. Energize the safety-control circuit dirirectly (or through a transformer) from the load side of an
overcurrent-protected starter for the fan motor.
Caution: The overcurrent protection of the starter should not exceed the convention rating required for the
fan motor alone.
2.4.9.1.11 Provide an airflow or differential pressure switch for each fan wired into the safety control circuit.

2.4.9.2 Rate Determination


2.4.9.2.1 Determine the necessary safety ventilation rate for batch, continuous, and powder curing ovens
using the calculations in Appendix C.1.
2.4.9.2.2 Fuel Correction
For direct-fired ovens, add the volume of combustion products to the volume calculated for safety ventilation
to obtain the total safety ventilation. The volume of combustion products may be calculated as follows:
English:
Total Burner Rating (Btu/hr) / (95 x 60) = ft3/min at 70°F
Metric:
Total Burner Rating (kW) x 60/3600 = m3/min at 20°C

2.4.9.2.3 Temperature Correction


Consider temperature correction factors when selecting the size of exhaust fan needed to move the required
volume of fresh air referred to 70°F (21°C) into an oven operating at “t” degrees. For example, to move a
volume of 1000 cfm (28.3 m3/min) of fresh air referred to 70°F (21°C) into an oven operating at 300°F (149°C),
it is necessary to exhaust:
English:
Vt = V70 × 460 + t or Vt = V70 × 460 + t
530 460 + 70
460 + 300°F
× 1000 cfm = 1434 cfm of exhaust at 300°F
460 + 70°F
Metric:
Vt = V21 × 273 + t or Vt = V21 × 273 + t
294 273 + 21
273 + 149°C × 28.3 m3/min = 40.6 m3/min at 149°C
273 + 21°C
Where Vt = Fan size (volume) at temperature t

2.4.9.2.4 Altitude Correction


If the altitude of the process exceeds 1000 ft (305 m), apply a correction factor to the necessary ventilation
rate in accordance with Table 2.4.9.2.4.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 22 FM Global Property Loss Prevention Data Sheets

Table 2.4.9.2.4. Altitude Correction Factors


Altitude, ft (m) Correction Factor
0 (0) 1.00
1000 (305) 1.04
2000 (610) 1.08
3000 (915) 1.12
4000 (1220) 1.16
5000 (1524) 1.20
6000 (1829) 1.25
7000 (2134) 1.30
8000 (2438) 1.25
9000 (2743) 1.40
10,000 (3048) 1.45

2.4.9.2.5 Vapor Concentration Detectors/Controllers


2.4.9.2.5.1 Provide continuous-type, vapor-concentration detectors/controllers at ovens that (because of
special process demands) are operated at vapor concentrations above 25% of the lower explosive limit. See
Data Sheet 5-49, Gas and Vapor Detectors and Analysis Systems, and Data Sheet 6-11, Thermal and
Regenerative Catalylic Oxidizers. These detectors/controllers are occasionally used with continuous-process
ovens where large amounts of ignitable liquids are evaporated.
2.4.9.2.5.2 Arrange the vapor-concentration detector to alarm at no more than 45% of the LEL. Automatically
shut down the process at no more than 50% of the LEL.
2.4.9.2.5.3 In multi-zone ovens, sample the atmosphere in each zone, except where it has been determined
that the atmosphere in that zone cannot exceed 25% of the lower explosive limit (LEL).
2.4.9.2.5.4 Select the sample point location to provide an average oven concentration. To make this sample
point effective, the atmosphere circulation in the oven should be sufficient to avoid pockets of high vapor
concentration. Do not sample too close to the evaporation surface because the concentration will be very high
there.
2.4.9.2.5.5 Use FM Approved open-path type infrared gas detectors installed directly on the oven or dryer
to minimize system response time. The response time for detection and appropriate response, such as
damper actuation, should be 5 seconds or less.
2.4.9.2.5.6 Install these devices according to the manufacturer’s instructions and have them serviced
periodically by the manufacturer or qualified personnel.
2.4.9.2.5.7 Calibrate the detector appropriately for the solvents being used. Obtain correction factors from
the manufacturer for the solvents being used.
2.4.9.2.5.8 Correct the actuation settings for the maximum anticipated oven temperature. Lower explosive
limit (LEL) values decrease with higher oven temperatures (see Table 2.4.9.2.5.8).

Table 2.4.9.2.5.8 Lower Explosive Limit Correction Factors for Elevated Oven Temperatures
Oven Temperature LEL Correction Factor
77°F (25°C) 1.00
212°F (100°C) 0.94
300°F (149°C) 0.90
400°F (204°C) 0.86
500°F (260°C) 0.82
Note: These values were derived from data presented in US Bureau of Mines Bulletin 627.

To determine the exact LEL corrected for temperature, use the following equation from US Bureau of Mines
Bulletin 627:
LELt = LEL77°F [1 - 0.000436 (t°F - 77°F)]
LELt = LEL25°C [1 - 0.000784 (t°C - 25°C)]

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 23

2.4.10 Low-Oxygen Atmosphere Ovens


2.4.10.1 Perform a process hazard analysis in accordance with Data Sheet 7-45, Process Safety, to determine
allowable oxygen content of the oven atmosphere based on the flammability level of the solvent to ensure
the atmosphere cannot reach flammable limits under normal operating conditions. See Table 2.4.10.1.
2.4.10.2 Provide an oxygen analyzer for each oven zone to control the oxygen content. Provide a second
analyzer system to actuate an inert gas emergency purge. Connect this analyzer directly to the emergency
purge system bypassing all process control devices.
2.4.10.3 Provide metering and control with the inert gas flow control. Equip the system with an automatic
emergency inerting mode using a manually-operated switch.
2.4.10.4 Provide emergency standby power for the fans and safety controls.
2.4.10.5 Provide for the availability of an emergency purge in the event of a power failure.
2.4.10.6 Design the inert and emergency gas system to prevent over-pressurization of the piping and (glass
tube) flow meters.
2.4.10.7 Protect the oven from over-pressure because of the emergency inerting. An emergency vent actuated
during the emergency purge may be provided.
2.4.10.8 Design the inert gas system including any vaporizers to provide the maximum flow rates for all
demand conditions.
2.4.10.9 Design vaporizers, when provided, to provide 150% of the highest purge-gas flows. Consider loss
of power.
2.4.10.10 Size inert gas storage for process and emergency purge to have at least a minimum of five oven
volumes for oven purge.
2.4.10.11 Provide a visual or audible alarm arranged to alarm if inert gas flow can be interrupted due to low
temperature or low flow from the vaporizer.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 24 FM Global Property Loss Prevention Data Sheets

Table 2.4.10.1 Limiting Oxidant Concentrations for Flammable Gases When Nitrogen or Carbon Dioxide are Used as
Diluents
Updated or Adjusted Data Original Data
N2-Air Mixture CO2-Air Mixture N2-Air Mixture CO2-Air Mixture
Gas/Vapor LOC LOC LOC LOC
Paraffins (alkanes)
b
Methane 11.1a (13.1)b 12.1 14.6b
b b
Ethane (9.5) (11.9)b 11.0 13.4b
a b
Propane 10.7 (12.8)b 11.4 14.3b
b b
n-Butane (10.6) (13.0)b 12.1 14.5b
b b
Isobutane (methylpropane) (10.5) (13.3)b 12.0 14.8b
b b
n-Pentane (10.6) (12.9)b 12.1 14.4b
c c
Isopentane (2-methylbutane) (10.5) (13.0)c 12.0 14.5c
b b
n-Hexane (10.4) (13.0)b 11.9 14.5b
c c
n-Heptane (10.0) (13.0)c 11.5 14.5
Cycloparaffins (cycloalkanes, naphthenes)
b b
Cyclopropane (10.2) (12.4)b 11.7 13.9b
Olefins (alkenes)
a b
Ethylene (ethene) 8.5 (10.2)b 10.0 11.7b
b b
Propylene (propene) (10.0) (12.6)b 11.5 14.1b
b b
α-butylene (1-butene) (10.1) (12.5)b 11.6 14.0b
c c
Isobutylene (2-methylpropene) (10.5) (13.5)c 12.0 15.0c
c c
Isopentene (2-methyl-1-butene) (10.0) (12.5)c 11.5 14.0c
Diolefins (dienes)
b b
1,3-Butadiene (8.9) (11.6)b 10.4 13.1b
Aromatics
d d
Benzene (11.4) (12.4)b 11.4 13.9b
d,e
Ethylbenzene 9.0 - 9.0d,e -
d,f
Diethylbenzene 8.5 - 8.5d,f -
d,f
Divinylbenzene 8.5 - 8.5d,f -
g,h
Toluene 9.5 - 9.5g,h -
d,i
Vinyltoluene 9.0 - 9.0d,i -
d,j
Styrene (phenylethene) 9.0 - 9.0d,j -
Alcohols
c c
Methyl aclohol (methanol) (8.5) (10.5)c 10.0 12.0c
c c
Ethyl alcohol (ethanol) (9.0) (11.5)c 10.5 13.0c
g,h
Ethyl alcohol (ethanol) 8.7 - 8.7g,h -
g,h
n-Propyl alcohol (n-propanol) 8.6 - 8.6g,h -
k,h
Isopropyl alcohol (2-propanol) 9.5 - 9.5k,h -
c,l
t-Butyl alcohol (t-butanol) - (15.0) - 16.5c,l
g,h
Isobutyl alcohol (2-methyl-1- 9.1 - 9.1g,h -
propanol)
c,l
Isohexyl alcohol (2-ethyl-1-butanol) (7.9) - 9.3c,l -
Esters
c c
Methyl Formate (8.5) (11.0)c 10.0 12.5c
c c
Methyl acetate (9.5) (12.0)c 11.0 13.5c
k,h k,h
n-Propyl acetate 10.1 - 10.1 -
g,h
Isopropyl acetate 8.8 - 8.8g,h -
g,h
n-Butyl acetate 9.0 - 9.0g,h -
g,h
Isobutyl acetate 9.1 - 9.1g,h -
c c
Isobutyl formate (11.0) (13.5)c 12.5 15.0c
Ethers
c c
Methyl ether (9.0) (11.5)c 10.5 13.0c
c c
Ethyl ether (9.0) (11.5)c 10.5 13.0c
m m
Propylene oxide (6.6) - 7.8 -
Ketones
c c
Acetone (10.0) (12.5)c 11.5 14.0c
c c
Methyl ethyl ketone (9.5) (12.0)c 11.0 13.5c

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 25

Table 2.4.10.1 Limiting Oxidant Concentrations for Flammable Gases When Nitrogen or Carbon Dioxide are Used as
Diluents (cont’d)
Updated or Adjusted Data Original Data
N2-Air Mixture CO2-Air Mixture N2-Air Mixture CO2-Air Mixture
Gas/Vapor LOC LOC LOC LOC
Organo-chlorides
c
n-butyl chloride (12.5)c - 14.0 -
b,n
(10.5)b,n - 12.0 -
b,o
Methylene chloride (17.5)b,o - 19.0 -
c,n
(15.5)c,n - 17.0 -
Ethylene dichloride (11.5)c - 13.0 -
b,n b,n
(10.0) (15.0)b,n 11.5 16.5b,n
c
1,1,1-Trichloroethane (12.5) - 14.0c -
c,n
Tricholoroethane (7.7) - 9.0c,n -
d,h
Vinyl Chloride 13.4 - 13.4d,h -
d
Vinylidene chloride 15.0 - 15.0d -
Inorganic Compounds
c c
Carbon disulfide (4.3) (6.4)c 5.0 7.5c
a c
Carbon monoxide (in air) 5.1 (5.1)c 5.5 5.5c
a c
Hydrogen (in air) 4.6 (4.6)c 5.0 5.2c
c c
Hydrogen sulfide (in air) (6.4) (10.0)c 7.5 11.5c
Miscellaneous nitrogen-containing compounds
c
UDMH (1,1-dimethyl hydrazine) (6.0) - 7.0c -
Commercial fuels
Motor Gasolines
c c
(70/100) (10.5) (13.5)c 12.0 15.0c
c c
(100/130) (10.5) (13.5)c 12.0 15.0c
c c
(115/145) (10.5) (13.0)c 12.0 14.5c
Aviation fuels
c,l c,l
Kerosene (8.5) (11.5)c,l 10.0 13.0c,l
c,l c,l
JP-1 fuel (9.0) (12.5)c,l 10.5 14.0c,l
c c
JP-3 fuel (10.5) (13.0)c 12.0 15.5c
c c
JP-4 fuel (10.0) (13.0)c 11.5 14.5c
Natural gas
b b
(Pittsburgh natural gas) (10.5) (12.9)b 12.0 14.4b
* Reproduced with permission of NFPA from NFPA 69, Standard on Explosion Prevention Systems, 2019 edition. Copyright© 2018, National
Fire Protection Association. For a full copy of NFPA 69, please go to www.nfpa.org.

Note:
a
All experiments performed at 25° C (77° F) unless otherwise indicated.
120 L (31.7 gal) apparatus — I. A. Zlochower and G. M. Green, “Mining Publication: The Limiting Oxygen Concentration
and Flammability of Gases and Gas Mixtures” (June 2009).
b
Flammability tube — Table 44 of Bureau of Mines Bulletin 503, “Limits of Flammability of Gases and Vapors” (1952).
c
Flammability tube — Table 11 of J. M. Kuchta, A. L. Furno, A. Bartkowiak, and G. H. Martindill, “Effect of Pressure and
Temperature on Flammability Limits of Chlorinated Combustibles in Oxygen-Nitrogen and Nitrogen Tetroxide-Nitrogen
Atmospheres” (1968).
d
~5 L (1.3 gal) vessel, ASTM E681, Standard Test Method for Concentration Limits of Flammability of Chemicals (Vapors
and Gases) (2015). – The Dow Chemical Company (Unpublished).
e
Experiments performed at 70°C (158°F).
f
Experiments performed at 114°C (237.2°F).
g
~5 L (1.3 gal) vessel, ASTM E2079, Standard Test Methods for Limiting Oxygen (Oxidant) Concentration in Gases and
Vapors (2013); — L. G. Britton, “Using Heats of Oxidation to Evaluate Flammability Hazards,” Process Safety Progress
(2002).
h
Experiments performed at 60°C (140°F).
i
Experiments performed at 105°C (221°F).
j
Experiments performed at 73°C (163.4°F).
k
~5 L (1.3 gal) vessel, ASTM E2079, Standard Test Methods for Limiting Oxygen (Oxidant) Concentration in Gases and
Vapors (2013) — L. G. Britton, The Dow Chemical Company, 1999 (Unpublished Report).
l
Experiments performed at 150°C (302°F).
m
R. M. Jones, “Reducing the Inflammability of Fumigants with Carbon Dioxide,” Industrial & Engineering Chemistry
Research (1933).
n
Experiments performed at 100°C (212°F).
o
Experiments performed at 30°C (86°F).

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 26 FM Global Property Loss Prevention Data Sheets

2.4.11 Autoclaves and Vacuformers Used for Bonding and Curing


2.4.11.1 Use one or more of the following safeguards depending on the value of the work load, the amount
of damage to the load by interruption of the curing cycle, and the cost of the safeguard in relation to the
value of the load:
A. Cut-off valves on the vacuum line to each platen, arranged to close automatically if vacuum is lost
within the plastic bag.
B. Use of an inert gas such as nitrogen, carbon dioxide, or waste off-gas as the pressurizing medium,
reducing the oxygen content to 10% or less
C. A water spray protection system in the autoclave (water spray, where provided for cooling the load at
the end of the curing cycle, may also be used for fire protection)
D. High-temperature cutout
E. High chilled water temperature alarm or cutout (heat supply)

2.5 Operation and Maintenance

2.5.1 Human Factors

2.5.1.1 Safety Control Bypass Management


2.5.1.1.1 Develop and implement a program for documenting and tracking bypasses of safety interlocks
(jumpers) by operations staff. Documentation should include reason for bypass, authorizing personnel,
expected time to reinstatement, and procedure for reinstating safety control.
2.5.1.1.2 Substitute alternate means to supervise the interlock being bypassed in accordance with operating
procedures.
2.5.1.1.3 Minimize the amount of time the safety control is out of service.

2.5.1.2 Safety Shutdown Investigation


2.5.1.2.1 Following any safety shutdown, determine the cause of the shutdown prior to restarting equipment.
2.5.1.2.2 Include operating procedures to delay restart of equipment based on cool-down or purge time to
prevent a flammable atmosphere from developing in the oven or dryer.
2.5.1.2.3 Include operating procedures to identify equipment operating outside of normal parameters following
a safety shutdown, and remove it from service prior to restarting equipment.

2.5.2 Operating Parameters


2.5.2.1 Develop and implement a plan for deviating from normal operating conditions, including, but not limited
to:
• Conveyor speed, where applicable
• Oven/dryer temperature
• Materials being processed
• Ventilation rate/fan speed
• Structural alterations to the enclosure
Several oven and dryer losses involved materials being overheated due to changes in the conveyor and/or
oven/dryer setpoints without evaluating the impact of the changes.

2.5.3 Commissioning

2.5.3.1 Installation Tests


2.5.3.1.1 Before an oven is placed in service, measure the minimum ventilation rate provided by the safety
ventilation system. At the same time, check the evaporation rate to ensure the safety ventilation system
capacity will be adequate. Tests have often shown wide variance between design capacity and actual
measurements taken in the field.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 27

2.5.3.1.2 Measure the ventilation rate before making any process changes that would affect the rate of
ventilation required. These include changing the character of the work or solvent (or the percentage by weight
of solvent), increasing batch loads or conveyor speeds, shortening pre-drying periods, and increasing
oven/dryer temperatures or ramp rates. Moreover, before making such changes, determine the evaporation
rate and recalculate safety ventilation. Never operate an oven with its safety ventilation system impaired
or overburdened.
2.5.3.1.3 Special hazards are introduced when ovens are connected to solvent recovery or fume incineration
systems, so make frequent checks of the safety ventilation’s adequacy. Include determination of the
evaporation rate and airflow.
If oxidizers are not sized properly, they may not be able to maintain the required temperature at full airflow.
Cutting back on the ventilation to increase temperature is hazardous. If this condition exists, increase the
burner size.

2.5.4 Burnouts and Fires in Indirect Air Heaters


2.5.4.1 If heat exchangers in indirect gas-fired or oil-fired air heaters can be seriously damaged by burnouts
or fire from carbon or soot deposits, take the following precautions:
A. Maintain burner-mixer adjustments to provide for complete combustion. Do not permit flame
impingement on heat exchanger tubes.
B. Follow a rigid cleaning schedule to prevent accumulation of soot or carbon.
C. Keep heater and oven fans running after burners are shut down to prevent abnormal temperature
buildup in the heat exchanger from residual heat in the combustion chamber.
D. Allow no dampers or other obstructions in the hot air ducts that would affect the free flow of air through
the heat exchanger.
E. Provide an excess temperature limit switch at each discharge duct for products of combustion leaving
the heat exchanger, arranged to shut off all fuel to the burners if temperature of the products of combustion
rises 50°F (28°C) above the normal maximum.

2.5.5 Oven Maintenance


2.5.5.1 Maintain all equipment in good condition.
2.5.5.2 Inspect and test safety controls at least annually and in accordance with the manufacturer’s
instructions.
2.5.5.3 Clean ovens and ducts at regular intervals if they are subject to buildups of flammable deposits of
condensed solvent or oil vapor, or accumulations of combustible lint, dust, or other material. In general, do
not allow combustible deposits in ducts for paint, varnish, and core-baking ovens to accumulate to more
than 1/8 in. (3 mm) thickness between cleanings. The rate at which deposits build varies considerably with
different ovens and processes; no specific schedule can cover all ovens. Clean new ovens on a weekly
schedule until sufficient experience is obtained to establish the necessary frequency.
2.5.5.4 Clean deposits and drips from racks, trays, and conveyors regularly. Use metal (or other
noncombustible material) trays to collect drippings from ovens and drainboards. Use trays that can be
removed for cleaning.
2.5.5.5 Pay particular attention to cleanliness at heaters with steam coils, housings, and ductwork since these
are the hottest spots where charring and eventual ignition are most likely. Remove fuel oil leakage or
condensed oil vapor in the vicinity of oven heaters frequently, and tighten piping to prevent further leakage.
Also pay particular attention to the end of ducts supplying fume incinerators since these incinerators are a
likely ignition source.
The method of cleaning varies with the nature of the deposits. Scraping with non-sparking tools is probably
the most widely used method for soft or easily removed deposits. Exceptionally hard deposits may have
to be melted by steam, or the ducts dismantled and scraped. Even burning out dismantled ducts at a safe
location in the yard is a method that has been used. Remove lint and dust by vacuum cleaning. Do not blow
with compressed air or steam because of the possibility of explosion from a combustible dust cloud.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 28 FM Global Property Loss Prevention Data Sheets

2.5.6 Explosion Vent Maintenance and Tests


2.5.6.1 Visually inspect explosion vents at least daily to ensure the vents are not obstructed.
2.5.6.2 Visually inspect explosion vents at least quarterly for signs of corrosion or other damage.
2.5.6.3 Conduct and document pull/push tests of hinged or latched explosion vents with pressure release
measurement at least annually.

2.5.7 Electrical and Mechanical Maintenance


2.5.7.1 Perform maintenance on a complete and rigid schedule, specific for each device (see Data Sheet
5-20, Electrical Testing). Keep complete records of the preventive maintenance program.

2.5.8 Inspection of Safety Controls


2.5.8.1 Function-test safety controls on a regular schedule, but at least in accordance with Table 2.5.8.1.

Table 2.5.8.1. Test Frequency for Functionality Tests of Safety Controls


Interlock Test Frequency
Igniter and burner components Semiannual1
Combustion air supply system Semiannual1
1
Piping, wiring, and connections of all interlocks and Semiannual
shutoff valves
Combustion control system Semiannual1
1
Calibration of indication and recording instruments Semiannual
1
Automatic fire checks Semiannual
1
Operating sequence tests, all components Semiannual
1
Combustible gas analysis automatic interlocks (calibrate Semiannual
as needed)
1
Gas cleaner and drip leg Semiannual
Explosion venting latches Semiannual1
1
Conveyor interlocks Semiannual
Fuel safety shutoff valve(s) for leakage Annual
Fan and airflow interlocks Annual
Purge interlocks Annual
Flame failure system components Annual
High-temperature limit switch Annual
Door-and-damper limit switches Annual
Oil pressure and temperature interlocks Annual
Oil Atomizing media interlocks Annual
High and low gas fuel pressure interlocks Annual
1
Semiannual or annual, as required by manufacturer’s instructions or operating history

2.6 Training
2.6.1 Develop and implement an operator training program in accordance with Data Sheet 10-8, Operators.
Include normal operation and emergency response in the training program.
2.6.2 Train operators in relighting procedures following accidental flame failure. Procedures will vary with
the individual oven.

2.7 Ignition Source Control

2.7.1 Hot Work


Develop and implement a hot work management program in accordance with FM Global Property Loss
Prevention Data Sheet 10-3, Hot Work Management, to strictly control all hot work operations.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 29

3.0 SUPPORT FOR RECOMMENDATIONS


Most oven/dryer losses are due to fires and explosions. The following sections describe many of the typical
causes of fire and explosion. Burner management, temperature control, safety ventilation, control of solvent
feed, explosion venting, and cleaning of internal deposits are all very important safeguards. Installation and
testing of safety devices, control of ignition sources, good housekeeping, and the installation of automatic
sprinklers are equally important loss prevention practices. If an LEL detection system is installed, it is critical
that it be properly designed and have a fast response time. Losses have occurred where these detection
systems did not respond due to improper installation.

3.1 Fire
Fires have occurred at dryers and ovens of practically every type. The following types of ovens have been
most frequently involved in fire:
• Coated metal (paint) ovens
• Textile, fiberboard, and paper dryers
• Ovens for impregnated electric coils
• Core ovens
• Dryers for evaporating low-flash-point solvents used in rubber coating

3.1.1 Paint Ovens


Spontaneous heating and autoignition of deposits in ovens or ducts cause one out of three paint oven fires.
Paint drippings or coated parts coming in contact with burner flames or electric heaters are another leading
cause.
In batch ovens, overheating due to failure of thermostatic controls and the use of combustible racks, trays,
or spacers account for more than half of the fire losses. Flammable deposits of condensed vapor in exhaust
ducts are the second most important defect.
Most duct fires occur at ovens using lacquer or other finishes whose deposits are subject to spontaneous
ignition. Occasionally, serious fires occur in oil-fired oven heaters, usually involving soot deposits in heat
exchanger tubes.

3.1.2 Textile Dryers


Most fires in dryers for textile fibers are caused by ignition of lint that has accumulated on high-pressure
steam coils. To avoid excessive temperatures, pressure at coils should not exceed 100 psi (690 kPa, 6.9 bar)
(steam temperature 338°F [170°C]) and should preferably be below 75 psi (520 kPa, 5.2 bar) (steam
temperature 320°F [160°C]). Ignition has occurred in carbonized stock from wool dryers that was either
improperly neutralized or packed too tightly while still hot from the dryer.

3.1.3 Fiberboard Dryers


Fires usually start in broken bits of board and dust that accumulate in the bottom of a fiberboard dryer or
in heating ducts. Ignition is usually by continued heating of these accumulations at hot spots, or abnormally
high dryer temperatures.

3.1.4 Electric Coil Baking Ovens


Overheating of coils or deposits, following the failure of thermostatic controls, emphasizes the importance
of providing separate excessive temperature alarms or cutoff switches. Drippings or coils in contact with
heaters and heating elements are the second leading fire cause, showing the need for safe location and
guards. Broken bulbs have caused fires at ovens using infrared lamps.

3.1.5 Core Ovens


Deposits of condensed core-oil vapor is responsible for most fires in core ovens. The deposits are subject
to spontaneous ignition, build up rapidly and are difficult to remove. Deposits several inches thick have been
reported in exhaust ducts that were not regularly cleaned.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 30 FM Global Property Loss Prevention Data Sheets

3.1.6 Rubber and Plastic Coating Dryers


At coating machines, printing presses and similar dryers evaporating large quantities of solvents, most fires
were caused by condensed deposits in either the ducts or dryers. Ignition was most frequently by spontaneous
heating, but static sparks caused many fires at the coater. See Data Sheet 7-96, Printing Plants.

3.1.7 Coffee, Cocoa, and Peanut Roasters


Overheating in the roaster and ignition of chaff or dust in the exhaust system are the two most prevalent
causes of fire in coffee, cocoa and peanut roasters. The roasting operation depends on the operators because
the food products are heated close to their ignition points. Inattention by the operator will likely result in
overheating. Mechanical or power supply failures also may cause roaster contents to overheat. This can go
undetected until the finish material is discharged into the cooling pan where it may burst into flames.

3.1.8 Organic Heat Transfer Media


Some ovens and dryers use an organic heat transfer media instead of steam or hot water. Data Sheet 7-99,
Heat Transfer by Organic and Synthetic Fluids, describes various fluids, fluid heating systems and the
recommended safeguards for the installations. The fluids are generally high-flash-point ignitable liquids. If
the fluid escapes from the system and is ignited, a severe fire can result. The organic-fluid filled heat
exchangers usually operate at temperatures that can result in spontaneous heating and ignition of synthetic
or natural fibers and materials.

3.1.9 Autoclaves Used for Bonding and Curing


Commercial autoclaves are widely used for bonding and curing processes. For bonding, the components
to be fabricated are coated with an adhesive and clamped together. They are then wrapped in a woven
asbestos or fire retardant cloth blanket, sealed inside a high strength chemically inert plastic “bag” having
vacuum connectors, placed on metal frames or platens, and put into the autoclave. A vacuum is drawn within
the plastic bag. The autoclave is then pressurized and heated. After several hours at curing temperature,
the bonded material is cooled by air or water spray. Pressurizing is usually by air. Heating is most commonly
by steam coils although electrical resistance heaters and direct-fired gas heaters are sometimes used.
For curing, layers of the material are coated with adhesive or resin and wrapped around the mandrel. After
covering with a plastic or silicone rubber bag, the whole is placed in the autoclave, the bag evacuated, and
the same procedure followed as for bonding.
There have been many fires in autoclaves, usually during the curing cycle. Most reported losses have
occurred in autoclaves fabricating aircraft and missile components. They have been attributed to spontaneous
heating of the cloth blanket or the plastic bag, or of waste paper or other foreign material accidentally
introduced into the autoclave. In addition, because fires are consistently preceded by loss of vacuum, it has
been theorized that pin hole leaks develop in the evacuated bag, permitting air to rush in. This may heat
the plastic bag and generate static electricity that ignites the bag or the mixture of air and solvent vapor from
the adhesive.
Although autoclave fires usually do not cause serious fire damage, the frequency has been high. They
interrupt the curing cycle so that the entire work load often must be scrapped, and the autoclave must be
shut down for clean up and testing before it can be restarted.

3.2 Fuel Explosions


Fuel explosions may occur from the ignition of unburned fuel or flammable products of incomplete combustion
during lighting-off, firing, or relighting. Explosions can also occur after shutdown if fuel leaks into the
combustion chamber.
The loss experience emphasizes the importance of providing suitable combustion safeguards and interlocks,
and assigning competent operators to carry out all lighting-off, relighting, and shutdown operations. Thorough
inspection, testing and maintenance programs must be established and maintained.
In gas-fired ovens and dryers, lighting-off explosions have occurred because of gas leakage during
shutdowns, by operators who failed to close all main burner valves before opening the main gas safety shutoff
valve, and because of unreliable pilots.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 31

Firing explosions have occurred after accidental flame failures at ovens where burner flames were not
supervised by combustion safeguards. The most important cause was operation of burners with insufficient
air for complete combustion, resulting in the formation of dangerous mixtures of carbon monoxide, hydrogen,
and air.
Relighting explosions were caused by operators who, after accidental flame failure, did not properly purge
with fresh air before they activated electric ignition or introduced a lighting torch.
In oil-fired ovens, there were few fuel explosions reported because of the smaller number of these units in
service. Lighting-off explosions were caused by operators who failed to properly purge with fresh air between
unsuccessful repeated attempts to ignite burners.
Firing explosions have occurred after accidental flame failures at ovens where burner flames were not
supervised by combustion safeguards. The remainder was due to the operation of burners with insufficient
air for complete combustion, which resulted in the formation of dangerous mixtures of carbon monoxide,
hydrogen and air.

3.3 Process Vapor Explosions


An explosion hazard exists in any oven or dryer where at least one of the following conditions is found:
A. The work space temperature level exceeds the flash point of any ignitable liquids in the work space.
B. The work space is subjected to combustion products (e.g., direct-fired ovens).
It is impractical to eliminate all ignition sources at ovens used for processing materials that emit flammable
vapor during the heating cycle. Primary dependence for prevention of a vapor explosion must be placed
on diluting the vapor with fresh air to well below the lower explosive limit and discharging them outdoors by
a positive and dependable system. This is known as “safety ventilation.” Safety ventilation is typically
designed to maintain a continuous oven or dryer atmosphere below 25% of the lower explosive limit (LEL).
The majority of the oven vapor explosions were due to failure to determine the solvent evaporation rate or
measure the rate of safety ventilation provided before making process changes. These include unusual
operational conditions not foreseen for inclusion in the safety control system design or operational procedures.
Some of these critical changes involved different solvents, increased batch loads and speeding up conveyors.
High speed coating or print dryers using flammable vapor indicator/controllers had explosive vapor
concentrations develop before the system could react. Errors by personnel, such as operating with the
ventilation throttling dampers improperly set and equipment defects account for the remainder. Sometimes
the fresh air is reduced to save energy or because the oxidizer burner is not large enough.
Batch ovens are inherently more hazardous than continuous (conveyor) ovens because the work load is
introduced all at once, causing the evaporation rates to peak and then fall (see Figure 3.3(A)).
It is usually practical to dilute vapor to below or barely below the lower explosive limit (LEL) when flammable
volatiles are being evaporated at the peak evaporation rate. During the rest of the heating cycle, with a fixed
ventilation rate, the ventilation is excessive and the oven wastes heat. For work carrying the same amount
of flammable volatiles, the batch oven requires a much higher safety ventilation rate than the continuous type.
With large batch ovens, safety ventilation requirements become uneconomically high, and there is a strong
incentive for users to make unsafe reductions.
In continuous ovens, the work and the amount of flammable volatiles enter at a nearly constant rate so that
the evaporation rate is also nearly constant. This makes it practical to dilute the flammable vapor to 25%
or less of the lower explosive limit at all times. Also, the continuous oven is inherently more economical to
heat.
Two design deficiencies have caused process safety ventilation explosions. Most oven manufacturers now
recognize the solutions:
A. Forced safety ventilation systems using dual purpose fans alone (recirculation combined with spill
exhaust) are also not sufficiently dependable. Such systems usually develop only a slight pressure and
are affected by the same variables as natural draft systems (see Figure 3.3(B)). Typical acceptable safety
ventilation systems using safety ventilating fans, with no recirculation through the fans are shown in Figure
3.3(C).

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 32 FM Global Property Loss Prevention Data Sheets

140
(63.6)

120
(54.5)
Evaporation loss-lb (kg)
100
(45.4) Oven drying curve after
30 min. still air dry
80
(36.3) Still air dry
60 curve Oven drying curve
(27.2) after 45 min. still
air dry
40 Fast
(18.2) dripping
not measured
20
(9.1) Work loaded
into oven
10 20 30 40 50 60 70
Time in minutes after dipping
Fig. 3.3.(A). Example of solvent evaporation-rate curve for a batch oven

B. Safety ventilation systems using natural draft alone are not dependable. The intended upward flow in
the exhaust duct and stack is too easily reduced or even reversed. Temperature changes, outdoor winds,
residue deposits or other obstructions in the exhaust duct or stack, restrictions at fresh air inlets and other
fans drawing from the same room are variables that can too easily affect the slight pressure usually
developed in such systems for producing the ventilation rate required for safety. The increased safety
afforded by forced ventilation is now recognized by oven manufacturers.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 33

+0.1 + 25. Pa
+ 0.25 m bar
in) 2 2650CFM(75m /min)
3

Burner - products of Safety ventilation 3


/m
exhaust stack 6m
(0.
3
combustion exhaust stack FM
1 2800CFM(79.3m /min)
2

Static pressure - ins. water column (Pa, m bar)


22C
1 0.0
0 215CFM
2
3
(6.1m /min) 1

E
-0.1 - 25. Pa
- 0.25 m bar

Throttling -0.2 - 50. Pa


C damper - 0.5 m bar
Back Fan
draft
diverter D
D1 B -0.3 - 75. Pa
D2 - 0.75 m bar

-0.4 - 100. Pa
Recirc. Recirc. - 1.0 m bar
supply top 2
header return
Radiator 1
tubes - 125. Pa
-0.5 - 1.25 m bar
Gas E D C B A
burner box Fresh
Recirc. air Measuring stations
bottom return inlet Average of
D1 & D2
A

Test No. 1 Test No. 2


Throttling Damper Wide Open Throttling Damper Closed
Amount of fresh air drawn into oven by fan, 215 cfm 6.1 m3/min 22 cfm 0.6 m3/min
measured at station E
Amount of air recirculated through fan, 2.585 cfm 73.2 m3/min 2.628 cfm 74.4 m3/min
measured at station D
Total flow of air through fan, measured at 2.800 cfm 79.3 m3/min 2.650 cfm 75.0 m3/min
station C
Static pressure measured at fan inlet, -0.48 in. WC -120 Pa -0.43 in. WC -107 Pa
station B (-1.2 mbar) (-1.07 mbar)
Static pressure measured at fan outlet, +0.04 in. WC +10 Pa +0.06 in. WC +15 Pa
station C (+0.1 mbar) (+0.15 mbar)
Numerical sum of fan inlet and outlet 0.52 in. WC 130 Pa 0.49 in. WC 122 Pa
pressures (sum of static pressures (1.3 mbar) (1.22 mbar)
measured at stations B and C)
Note: The dual-purpose fan system is undesirable because it develops practically no change in the static pressure rise through
the fan even when the throttling damper is moved from open to closed.

Fig. 3.3.(B). Airflow test illustrating undesirable characteristics usually present in


an oven safety ventilation system using dual purpose fans alone

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 34 FM Global Property Loss Prevention Data Sheets

Safety ventilation
Safety ventilation Safety ventilating exhaust stack
exhaust stack fan

Burner-products
Safety ventilating Recirculating fan
of combustion
fan return exhaust stack
Fresh
Heater fan air Explosion
resisting
Fresh air for radiators
combustion and safety
ventilation fresh air input
Burner
Supply

Heater

Safety ventilation Safety ventilation


exhaust stack exhaust stack

Safety ventilating Safety ventilating


fan fan
Recirculating fan Recirculating fan
Fresh air Fresh air
Heater Heater
Supply Supply

Return Return

Safety ventilation Fresh air input stack Safety ventilation


exhaust stack (safety ventilation) exhaust stack
Air Air KEY
lock Oven lock
Entrance Exit
Safety ventilation
Recirculating fans Splitter
damper
Heater

Recirculating fan
(with "spill" exhaust)

Safety ventilating fan

Fig. 3.3.(C). Typical acceptable safety ventilation systems using safety ventilating fans, with no recirculation through fans

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 35

3.3.1 Low Oxygen Atmosphere Ovens


Low-oxygen atmosphere ovens and dryers are designed to operate with elevated vapor concentrations by
limiting the oxygen concentration with an inert gas atmosphere. These units are usually associated with
solvent recovery systems using vapor condensers or carbon bed absorbers. See Data Sheet 7-2, Waste
Solvent Recovery.
Part of the solvent vapor-laden oven atmosphere, 1% to 3%, is cleaned at the solvent recovery unit (see
Figure 3.3.1). The cleaned atmosphere is recombined with the recirculation stream and passed back through
the oven.

Solvent recovery

Blower

Solvent vapor Cleaned inert


laden inert gas gases
atmosphere
Recirculation

Oven-dryer

Fig. 3.3.1. Schematic of a low oxygen atmosphere oven and solvent recovery system

3.4 Loss History

3.4.1 Introduction
Table 3.4.1 shows the oven and dryer losses reported to FM Global for the period from 2009 to 2019. Two
thirds of all oven and dryer losses were fires, with property damage driving fire losses.

Table 3.4.1. Reported Losses, 2009-2019


% of Total Losses by Average Gross Total % of Loss Due to % of Loss Due to
Reported Peril Value Loss Property Damage Time Element
Fire 55.4% US$1,970,000 65% 35%
Explosion 41.4% US$3,903,000 33% 67%
Mechanical 1.7% US$1,590,000 37% 63%
Breakdown
Temperature Change 0.7% US$1,800,000 2% 98%
Sprinkler Leakage 0.7% US$1,800,000 100% 0%
Electrical Breakdown 0.1% US$150,000 56% 44%
Collapse 0.1% US$196,000 92% 8%

3.4.2 Contributing Factors

3.4.2.1 Lack of Automatic Sprinklers


Lack of sprinkler protection where needed was cited as a negative contributing factor in approximately
one-third of reported losses. Automatic sprinklers installed as recommended in this data sheet can minimize
the consequences/severity of a fire involving an oven or dryer by preventing the fire from spreading to
adjacent combustible construction and other equipment.

3.4.2.2 Adequacy and Maintenance/Inspection of Safety Devices


There were many different safety devices in losses where adequacy and/or maintenance of safety devices
was cited as a negative loss factor. Some examples include lack of calibration on gas detectors resulting in
oven atmospheres exceeding LEL, a lack of gas detectors in a batch oven, failure of heat detector/high
temperature limits, and conveyor speed interlocks.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 36 FM Global Property Loss Prevention Data Sheets

3.4.2.3 Equipment Restarted Without Corrective Action


In approximately 5% of oven and dryer losses, equipment that had previously shutdown on a safety interlock
was restarted without corrective action being taken by operators. In these cases, 94% were reported as
explosion losses.

3.4.2.4 Inadequate Operating Procedures


Operating procedures were cited as a negative loss factor in approximately 8% of losses reported to FM
Global. Although there is significant overlap between this category and 3.4.2.3, there are a significant number
of unique losses when inadequate operating procedures contributed to the severity of the loss.

3.4.3 Illustrative Losses

3.4.3.1 Unsprinklered Bakery Oven Fire Spreads to Combustible Construction, Destroys Building
A fire occurred in a bakery oven, most likely due to combustible deposits stuck to the oven conveyor. Automatic
sprinklers were not provided in the oven or in the production area of the facility. The oven and facility were
provided with high-temperature and flame detection interlocks arranged to stop the conveyor system. These
interlocks failed, resulting in ignited material transferring from the oven to a plastic spiral conveyor cooling belt.
The plastic conveyor then caught fire, which developed sufficient heat to ignite combustible building
construction materials. It reportedly took approximately 40 minutes for the local fire department to arrive at
the facility. By that time, the entire building was involved in the fire. The building ultimately collapsed,
destroying the building and all contents.

3.4.3.2 Bakery Oven Fire Spreads to Exhaust Duct Chase and Roof
A fire occurred in the last zone of a bakery production oven as the oven was being shut down for cleaning.
The oven was provided with a manually-activated fire protection system. However, employees attempted
to fight the fire with portable fire extinguishers instead of activating the fire protection system in the oven. The
fire then spread to the exhaust ductwork, which had not been cleaned in approximately one week. The
resulting temperatures ignited the walls of the exhaust chase, and eventually spread to the roof. The majority
of the property damage was thermal damage to approximately 9,000 ft2 (840 m2) of the roof covering and
rooftop equipment. Time element (TE) was negligible as the production from the impacted oven was shifted
to other areas of the plant.

3.4.3.3 Faulty Gas Control Valve, Operator Error Lead to Rotary Dryer Explosion
A rotary dryer in a corn ethanol plant was equipped with a problematic fuel gas control valve, requiring frequent
manual resets. On the day of the incident, the fuel control valve was manually reset by plant personnel
following a safety shutdown for an unrelated cause. At that time, operators noted that the reported gas control
valve position was not consistent with the gas flow rate reported by the flow meter. The valve position reported
0% open while the meter reported increasing gas flow to the burners. An initial explosion resulted in three
of four explosion vents relieving. These vents were replaced, and the dryer was successfully restarted even
though the gas control valve did not appear to be operating within design parameters. A second explosion
occurred in the dryer, followed by two subsequent explosions in the associated cyclones.

3.4.3.4 Malfunctioning Interlock, Operator Error lead to Extensive Fire Damage


A radiant processing oven used to process plastic sheets was provided with an optical sensor interlocked
to shut down the conveyor in the event that a plastic sheet was overheated and sagged below the conveyor
level. On the day of the incident, a plastic sheet was jammed in the oven, became overheated and eventually
ignited. The optical sensor failed to initiate the interlock, so additional plastic sheets continued to enter the
oven, fueling the fire. The operator noticed the fire but did not press the manual emergency stop button. The
operator left the area to obtain a manual fire extinguisher. Other nearby employees also gathered manual
fire extinguishers and began attempting to extinguish the fire. In total, 40 manual fire extinguishers were
discharged onto the fire in a 10 minute period, but did not extinguish the fire. The emergency stop button was
reportedly pressed after manual firefighting efforts were abandoned and sprinklers activated. The fire spread
above the suspended ceiling to other parts of the facility. The fire was extinguished by the automatic
sprinklers before local firefighters arrived on scene. Firefighters cut multiple holes in the roof to assist with

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 37

smoke control and to confirm the fire above the suspended ceiling had been extinguished. The oven and
associated equipment were destroyed, and at least 90 gaylords of food-grade plastic pellets were discarded
due to contamination.

4.0 REFERENCES

4.1 FM Global
Data Sheet 1-13, Chimneys
Data Sheet 1-28, Wind Design
Data Sheet 1-44, Damage-Limiting Construction
Data Sheet 1-57, Plastics in Construction.
Data Sheet 2-0, Installation Guidelines for Automatic Sprinklers.
Data Sheet 5-20, Electrical Testing
Data Sheet 5-49, Gas and Vapor Detectors and Analysis Systems
Data Sheet 6-0, Elements of Industrial Heating Equipment
Data Sheet 6-11, Thermal and Regenerative Catalylic Oxidizers
Data Sheet 7-2, Waste Solvent Recovery
Data Sheet 7-9, Dip Tanks, Flow Coaters, and Roll Coaters
Data Sheet 7-10, Wood Processing and Woodworking Facilities
Data Sheet 7-32, Ignitable Liquid Operations
Data Sheet 7-54, Natural Gas and Gas Piping
Data Sheet 7-76, Prevention and Mitigation of Combustible Dust Explosions and Fires
Data Sheet 7-78, Industrial Exhaust Systems
Data Sheet 7-88, Ignitable Liquid Storage Tanks
Data Sheet 7-96, Printing Plants
Data Sheet 7-99, Heat Transfer by Organic and Synthetic Fluids
Data Sheet 10-3, Hot Work Management
Approval Guide, an online resource FM Approvals, see “Explosion Venting Wall Systems”

4.2 NFPA Standards


National Fire Protection Association (NFPA). Standard for Ovens and Furnaces. NFPA 86.
National Fire Protection Association (NFPA). Venting of Deflagrations. NFPA 68.

APPENDIX A GLOSSARY OF TERMS


Autoclave: A heated pressure vessel used to treat materials. Refer to Section 3.1.9 for additional information.
Autoignition: Spontaneous ignition of material without a source of ignition or internal reaction.
Automatic fire check: A check valve that closes when a fusible link is heated by a flame.
Batch oven: An oven that does not have a continuous feed of material into it. Temperature ramps up at a
specified rate to a temperature that then remains constant for a certain amount of time (soak time) before a
cooling cycle begins. Material is inserted and removed only before and after the heating cycle.
Combustion safeguard: A safety controller and flame scanner that responds directly to flame properties.
It senses the presence of flame and causes fuel to be shut off in the event of flame failure. A combustion
safeguard will typically also monitor other safety devices such as fuel pressure and airflow switches.
Deflagration: A rapid combustion or explosion that travels at a velocity less than the speed of sound and
therefore does not detonate. A pressure wave precedes the flame front. Pressure can increase by about a
factor of 10. Detonation can be several orders of magnitude greater. For an explosion to occur, confinement
is also needed.
Explosion vent: A light-weight, explosion-relieving panel or membrane that is lightly fitted on the top or side
of an oven. Vents are designed to open at a low pressure so pressure will be quickly relieved inside the
oven. Doors fitted with FM Approved explosion latches may also provide explosion relief.
Explosive range: In between the lower and upper explosive (flammable) limits of a flammable material. A
flammable material can ignite if a mixture of air (or other oxidizer) and the material in a gaseous state falls in

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 38 FM Global Property Loss Prevention Data Sheets

this range. For example, if a mixture of toluene and air contains between 1.1 and 7.1% toluene by volume,
it can ignite. Temperature, pressure and oxygen concentration can change the explosive range.
Festooned: Material processed in an oven that is hanged or draped between a series of points.
FM Approved: References to “FM Approved” in this data sheet mean the product or service described has
satisfied the criteria for FM Approval. See the Approval Guide, an online resource of FM Approvals, for a
complete listing of products and services that are FM Approved.
Fume incinerator: A thermal oxidizer used to destroy pollutants exhausted from ovens that use solvents
for the process. Regenerative thermal oxidizers (RTO) and regenerative catalytic oxidizers (RCO) also
perform this function.
Inerting gas: A nonflammable gas, such as argon or nitrogen, that is used to displace air and make the
atmosphere nonflammable.
Ignitable liquid: Any liquid or liquid mixture capable of fueling a fire, including flammable liquids, combustible
liquids, inflammable liquids, or any other term for a liquid that will burn. An ignitable liquid is one that has
a fire point.
Igniter: A source of ignition for a burner. Can be electric or fuel-fired.
LEL detector: A combustibles analyzer that gives a reading in terms of percent of LEL for the sampled
atmosphere.
Lower explosive limit: The minimum concentration of a flammable vapor in air at which ignition can occur.
Pilot: A fuel-fired igniter.
Plenum: A chamber from which a fan draws air. May be fitted with heating/cooling coils and damper vanes.
Purge: To flush a combustion chamber with fresh air, usually 4 volumes.
Safety blowout device: Used in a premixed fuel line to protect equipment such as a compressor from a
flareback. Consists of a flame arrestor, fire check valve, and rupture disk.
Safety ventilation: Ventilation of an oven with fresh air to keep solvent vapor diluted well below the LEL.
Normally measured and calculated using the exhaust flow rate.
Standard cubic feet (scf): Air quantity, referenced to dry air at 70°F (21°C) and 29.92 inch Hg (1 bar)
pressure. This measurement is often used for fan capacity ratings. If referenced in determining ventilation
capacity, standard cubic feet must be converted to actual cubic feet by accounting for site-specific temperature
and altitude conditions.
Solvent recovery system: An unfired system used to remove solvent vapor from the exhaust stream.
Trial-for-ignition: The maximum amount of time fuel can be admitted to a pilot or burner at startup if flame
is not detected.
Turndown: The operating range of a burner, or the ratio of the maximum firing rate to the lowest firing rate
(e.g., 10 to 1).
Upper explosive limit: The maximum concentration of a flammable vapor in air at which ignition can occur.

APPENDIX B DOCUMENT REVISION HISTORY


The purpose of this appendix is to capture the changes that were made to this document each time it was
published. Please note that section numbers refer specifically to those in the version published on the date
shown (i.e., the section numbers are not always the same from version to version).
April 2021. This document has been completely revised. The following significant changes were made:
A. Added a recommendation to install classified electrical equipment in the interior of ovens if flammable
vapor may be present.
B. Added a recommendation to use Data Sheet 6-11 for control of volatile vapor concentration in ducts
if bypass ducts are prohibited by environmental regulations.

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 39

C. Added a recommendation to size water supply for simultaneous operation of duct and oven sprinklers
supplied by a common water source.
D. Deleted recommendation for portable extinguishing equipment.
E. Deleted recommendation related to electrical disconnects for electric heaters.
F. Clarified gas detector recommendation to open path IR-type detectors because other technologies are
FM Approved only up to 200°C [392°F].
G. Added recommendation to conduct process hazard analysis for low-oxygen atmosphere ovens to
ensure the atmosphere cannot reach flammable limits under normal operating conditions.
H. Added a recommendation to establish a documented program for safety interlock bypass management.
I. Added recommendation to establish a documented program to address changes in operating
parameters, including conveyor speed to address loss history.
J. Added recommendation to conduct daily visual inspection of explosion vents to check for obstructions.
K. Revised test frequency for some combustion safety devices to annual.
L. Updated loss history.
July 2014. The following major changes were made:
A. Revised terminology and guidance related to ignitable liquids to provide increased clarity and
consistency. This includes replacement of references to “flammable” and “combustible” liquid with
“ignitable” liquid throughout the document.
B. Reorganized the document to provide a format that is consistent with other data sheets.
C. Provided additional information relative to the construction and proper location of ovens and dryers.
D. Modified recommendations related to explosion vents.
E. Provided guidance on the proper design of fuel supply, transfer, and piping systems for gas-fired and
oil-fired ovens and dryers, including reference to other applicable data sheets.
F. Revised the oven and dryer ventilation system design guidance to meet current industry practices. This
includes accounting for the impact of altitude on the necessary ventilation rates, and the elimination of
the use of nominal (i.e., estimated) solvent rate data for continuous ovens.
G. Revised Appendix C, Ventilation System Design, to conform to current industry practices, to provide
increased clarity, and to provide additional guidance on the measurement of safety ventilation rates.
H. Provided more specific design guidance for the sprinkler protection of ovens and dryers.
June 2009. The reference source for solvent chemical properties has been changed to NFPA 86, Standard
for Ovens and Furnaces. NFPA 325M, Fire Hazard Properties of Flammable Liquids, Gases, and Volatile
Solids, has been withdrawn by the NFPA.
September 2003. This data sheet has been rewritten.
(2.1.2.3.4) The allowable clearance between exhaust ducts and stored combustible materials has been
increased from 18 to 30 inches (45 to 75 cm) in agreement with Data Sheet 6-4/12-69, Oil- and Gas-Fired
Single-Burner Boilers.
(2.1.3.4) The explosion venting recommendations have been revised to be in agreement with Data Sheet
1-44, Damage-Limiting Construction for weak construction and NFPA 68, Venting of Deflagrations for strong
construction. The traditional 15 to 1 ratio, which is not based on anything except experience, has been
dropped.
(2.1.4.4.2) The minimum safety control testing frequency has been changed from monthly to quarterly. This
is a more realistic and practical approach.
(2.2.3.1) Temperature control recommendations have been revised, are more flexible and take into account
flammable materials, multiple zones, location and set points. Low temperature alarms are recommended

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 40 FM Global Property Loss Prevention Data Sheets

for multiple zones with process solvents. Rating of components such as thermocouple extension wires is
also addressed. The previous Section 2.3.2.8 on excess temperature interlocks has been combined with this
section.
(2.3.3.4 and 2.4.2.1) The recommendation for airflow switches is no longer an option and is now required.
(2.3.2.7) A low fire interlock is recommended for gas and oil, not just oil.
(2.3.2.10 Previous section) The section on FM cocks has been deleted. FM cock systems are still in existence,
but should not be recommended for new installations. Combustion safeguard systems should be used.
(2.3.2.12) The three options were deleted. All that is needed is an interlock to prevent the fuel-aspirating
combustion fan from running during purge. A second safety shutoff valve is already required, and the
recommendation for an FM cock system has been deleted. A proof-of-closure switch is already required on
burner systems greater than 400,000 Btuh (117 kW), and is not available on valves under 0.75 inches (2
cm).
(2.3.2.14(b)) The option for a second safety shutoff valve has been deleted since this is now always required.
(2.3.2.15) The recommended maximum trial-for-ignition time has been decreased to 5 seconds for direct
spark ignition. A pilot can be supervised with a flame scanner whereas an electric igniter cannot. This time
can be extended if needed, however.
(2.3.2.19.3 Previous section) The allowance for one flame scanner supervising two burners has been deleted.
There is already an allowance for line-type burners to be supervised by a single scanner.
September 2000. Changes to safety ventilation and safety shutoff valve recommendations were made to
be in agreement with NFPA 86 1999. These changes are justified based on loss experience and because there
is no reason to differ from NFPA 86 with regard to any of these changes.
The nominal amounts of air required to render a solvent barely explosive have been increased for continuous
and batch ovens. Example calculations have been revised to reflect this. The nominal amounts of air have
been increased because the previous amounts did not account for LEL correction, and also so that the nominal
method would be safe to use for more solvents. For batch ovens, this is especially important because the
LEL can be reached at peak evaporation. This change does not affect Oven VentilationCalc for continuous
ovens because a calculated method is used as opposed to the nominal method.
An equation has been added for LEL temperature correction. LEL correction is important because the LEL
is reduced at elevated temperatures. This is not new to NFPA 86 and has been used all along in Oven
VentilationCalc. The data sheet contained an LEL correction table, but did not include this factor in the
examples.
LEL detector trip set point has been changed from 60% to 50%. This is not new to NFPA 86 and is in
agreement with Data Sheet 6-11, Thermal and Regenerative Catalylic Oxidizers.
The amount of air required for combustion is now always added to the amount of safety ventilation needed
for the process vapors regardless of the amount. The one third rule has been dropped. The NFPA 86
committee decided that there was no known reason for this rule.
Two safety shutoff valves are now recommended for all pilots and burners, regardless of size. A
recommendation for multi-burner operation was also added.
June 1999. This document has been reorganized to provide a consistent format.

APPENDIX C SUPPLEMENTAL INFORMATION

C.1 Ventilation System Design

C.1.1 General
Whenever possible, determine necessary safety ventilation rates based on evaporation rates and properties
of the solvents as determined from laboratory or field testing of individual site processes (i.e., detailed solvent
rate data). “Detailed” in this context indicates an understanding of the rate of change of the introduction of
solvents into the process atmosphere to a degree sufficient to determine peak process atmosphere solvent
mass fractions. This information usually derives from detailed records of process flow rates. Often, this is

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 41

obtained by weighing coated components prior to their insertion into the oven, and removing and weighing
them at different times throughout the process to determine how much solvent had evolved at those times.
If detailed solvent rate data is unknown and unavailable, the use of nominal data may be used in some cases,
using typical evaporation rates for most common solvents as applied to coated or dipped metal. Different
solvents, work application, and degree of absorption will produce different evaporation rates of the volatiles.
Dipped sheet metal produces the highest evaporation rates ordinarily encountered.

C.1.2 Ventilation Rate Calculations


For both batch and continuous type ovens, the safety ventilation system should furnish sufficient fresh air
ventilation to dilute the vapor to a concentration not exceeding 25% of the lower explosive limit (LEL).

C.1.2.1 Batch Ovens


1. Calculate the necessary safety ventilation rate to dilute the vapors from 1 gallon (liter) of ignitable liquid
to just below the lower explosive limit (100% LEL).
V = (8.33*SG)/(0.075*VD) * (100/LEL) [English]
V = (0.998*SG)/(1.201*VD) * (100/LEL) [Metric]
Where V = ventilation volume per gallon (liter) of solvent (ft3/gal [m3/L])
SG = specific gravity (water = 1)
VD = vapor density (air = 1)
LEL = lower explosive limit (% by volume)
2. Multiply the calculated ventilation volume by the peak solvent evaporation rate.
VA = V * ER
Where:
VA = ventilation rate for peak solvent evaporation rate (ft3/min [m3/min]).
V = ventilation volume per gallon (liter) of solvent (ft3/gal [m3/L]).
ER = evaporation rate (gallons [liters] per unit time).
If detailed solvent evaporation rate data is unavailable, assume VA = 450 ft3/min (12.6 m3/min).
3. Apply a safety factor of 4 (i.e., 25% LEL).
4. If the temperature of the process exceeds 250°F (121°C), apply an additional safety factor of 1.4.
5. Add the products of combustion, if applicable (see Section 2.4.9.2.2).
6. If the temperature of the process exceeds 250°F (121°), apply a temperature correction factor to account
for the impact of temperature on exhaust efficiency (see Section 2.4.9.2.3).
7. If the altitude exceeds 1000 ft (305 m), apply an altitude correction factor (see Section 2.4.9.2.4).
English:
Where: 0.89 is the specific gravity (water = 1)
2.8 is the vapor density (air = 1)
1.4 is the lower explosive limit, % by volume
8.33 is the weight of 1 gal of water, lb
0.075 is the weight of 1 ft3 of air, lb

8.33 lb × sp. gr. × 100


0.075 lb × v.d. (LEL)
8.33 lb × 0.89 × 100 = 2520 ft3/gal solvent
0.075 × 2.8 1.4

Metric:
Calculate meters of vapor from evaporation of 1 l of the solvent,

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 42 FM Global Property Loss Prevention Data Sheets

Where: 0.89 is the specific gravity (water = 1)


2.8 is the vapor density (air = 1)
1.4 is the lower explosive limit, % by volume
0.998 is the weight of 1 l of water, kilograms
1.201 is the weight of 1 cubic meter of air, kilograms

0.998 kg × 0.89 × 100 = 18.8 m3/l solvent


1.201 kg (2.0) 1.4

C.1.2.2 Continuous Ovens


1. If the temperature of the process exceeds 250°F (121°), correct the LEL.
LELt = LEL77°F [1 - 0.000436(t - 77°F)] [English]
LELt = LEL25°C [1 - 0.000784(t - 25°C)] [Metric]
Where LEL77°F (LEL25°C) = lower explosive limit at ambient temperature
LELt = lower explosive limit corrected for process temperature
t = process temperature
2. Calculate the necessary safety ventilation volume to dilute the vapors from 1 gallon (liter) of ignitable liquid
to just below the lower explosive limit (100% LEL):
V = (8.33*SG)/(0.075*VD) * (100/LEL) [English]
V = (0.998*SG)/(1.201*VD) * (100/LEL) [Metric]
Where V = ventilation volume per gallon (liter) of solvent (ft3/gal [m3/L])
SG = specific gravity
VD = vapor density
LEL = lower explosive limit (% by volume)
3. Multiply the calculated ventilation volume by the solvent flow rate.
VA = V * FR
Where VA = ventilation rate for peak evaporation rate (ft3/min [m3/min])
V = ventilation volume per gallon (liter) of solvent (ft3/gal [m3/L])
FR = solvent flow rate (gallons [liters] per unit time)
4. Apply a safety factor of 4 (i.e., 25% LEL).
5. Add the products of combustion, if applicable (see Section 2.4.9.2.2).
6. If the temperature of the process exceeds 250°F (121°), apply a temperature correction factor to account
for the impact of temperature on exhaust efficiency (see Section 2.4.9.2.3).
7. If the altitude exceeds 1000 ft (305 m), apply an altitude correction factor (see Section 2.4.9.2.4).

C.1.2.3 Powder Curing Ovens


For powder fusing or curing in continuous ovens, design and test data should be available for the maximum
powder application rate and the percent of volatiles released during the cure cycle. Calculate the necessary
ventilation as follows:
1. If the temperature of the process exceeds 250°F (121°), correct the LEL.
LELt = LEL77°F [1 - 0.000436(t - 77°F)] [English]
LELt = LEL25°C [1 - 0.000784(t - 25°C)] [Metric]
Where LEL77°F (LEL25°C) = lower explosive limit at ambient temperature
LELt = lower explosive limit corrected for process temperature
t = process temperature
2. Calculate the necessary safety ventilation volume to dilute the vapors from 1 gallon (liter) of powder to
just below the lower explosive limit (100% LEL):

©2021 Factory Mutual Insurance Company. All rights reserved.


Industrial Ovens and Dryers 6-9
FM Global Property Loss Prevention Data Sheets Page 43

V1 = (8.33*SG)/(0.075*VD) * (100/LEL) [English]


V1 = (0.998*SG)/(1.201*VD) * (100/LEL) [Metric]
Where V1 = ventilation volume per gallon (liter) of powder (ft3/gal [m3/L])
SG = specific gravity
VD = vapor density
LEL = lower explosive limit (% by volume)
3. Divide the calculated ventilation rate by the density of the powder to determine the necessary safety
ventilation volume to dilute the vapors from 1 pound (kg) of powder to just below the LEL (or the corrected
LELt, if applicable).
V2 = V1 / ρ
Where V1 = ventilation volume per gallon (liter) of powder (ft3/gal [m3/L])
V2 = ventilation volume per lb (kg) of powder (ft3/lb [m3/kg])
ρ = Powder density (lb/gal [kg/L])
4. Multiply the calculated ventilation volume by the powder feed rate.
V3 = V2 * FR
Where V3 = ventilation rate based on oven’s powder feed rate (cfm [m3/min])
V2 = ventilation volume per pound (kg) of solvent (ft3/lb [m3/kg])
FR = powder feed rate (pounds [kg] per unit time)
5. Adjust the ventilation rate based on the percentage of volatiles released by the powder. The percentage
of flammable gases given off varies widely with the type of powder: approximately 2% in epoxy, 3% for acrylics,
5% for polyesters and 9% for vinyl. The release value of 9% is generally accepted for the purpose of
calculating ventilation rates. It is assumed that all volatiles given off are flammable, although the exact
compositions are normally unknown.
VA = V3 * FV
Where VA = ventilation rate based on the percentage flammable vapor released (ft3/min [m3/min])
V3 = ventilation rate based on oven’s powder feed rate (ft3/min [m3/min])
FV = flammable vapors released (%).
6. Apply a safety factor of 4.
7. Add the products of combustion, if applicable (see Section 2.4.9.2.2).
8. If the temperature of the process exceeds 250°F (121°), apply a temperature correction factor to account
for the impact of temperature on exhaust efficiency (see Section 2.4.9.2.3).
9. If the altitude exceeds 1000 ft (305 m), apply an altitude correction factor (see Section 2.4.9.2.4).

C.1.3 Measurement of Safety Ventilation Rates


Dilution of a solvent with air is based on mass fractions, and the mass of air in one unit of volume (e.g.,
one cubic foot or meter) varies inversely with temperature and elevation (i.e., directly with pressure).
Therefore, the volume of air required to dilute a certain mass of flammable vapor is relative to the temperature
and pressure at which the volume was measured
The actual volume of air necessary to dilute a defined quantity of solvent vapor at a specific location will
vary from the standard air volume determined by calculations. Therefore, the calculation procedures in this
appendix include corrections for ovens operating at high temperatures and/or altitudes. This allows
conversion from standard air volumes to actual air volumes at elevated temperatures and/or altitudes. These
corrected values should be compared to the air volume as measured on site.
The actual air volume is specific to the point of measurement. For example, if the air is measured in a location
prior to process heating, such as at the fan intake, corrections for elevated temperatures should not be
applied in the calculations. If the air is measured in a location after process heating, such as in the oven
exhaust, corrections for elevated temperatures should be applied. The contractor responsible for the
measurements should clearly stipulate the temperature at the point of measurement.

©2021 Factory Mutual Insurance Company. All rights reserved.


6-9 Industrial Ovens and Dryers
Page 44 FM Global Property Loss Prevention Data Sheets

While an understanding of the actual air volume necessary to dilute a flammable vapor is important, standard
air volume (e.g., standard cubic feet or meters per minute) still needs to be considered to verify if the fan
selected for a specific process will provide the required amount of air flow at process conditions. Fans are
typically rated by the manufacturers in terms of conditions at standard atmospheric conditions (e.g., scfm), In
order to compare the process conditions to the fan ratings, a review of calculations or revised fan curves
that compare standard to actual air volume based on the specific oven process is necessary.

C.1.4 Symptoms of Inadequate Ventilation


Vapor explosions often occur some time after ventilation becomes inadequate. Investigate the following
symptoms and take corrective action immediately:
A. A cold exhaust duct or stack while the oven is operating (usually indicates reversal of flow in the stack
or inadequate safety ventilation)
B. Evidence of negative pressure in the oven room, with respect to adjoining rooms and outdoors when
the door to the oven room is opened (may indicate inadequate safety ventilation and sometimes reversal
of airflow in the exhaust stack)
C. A record of fires or puffs from work in a particular oven (may indicate inadequate safety ventilation,
dangerously high vapor concentrations, and increased probability of an eventual serious oven explosion)
D. A record of work leaving the oven with paint incompletely dried (an indication of inadequate safety
ventilation)
E. Heavy deposits of condensed paint vapor at the exhaust stack outlet (may indicate that interior fouling
has dangerously reduced the safety ventilation) flow
F. Paint fume deposits around oven door cracks (may indicate higher pressure inside the oven than in
the oven room, and a lack of positive safety ventilation)

C.2 Other Standards


The corresponding NFPA standards are NFPA 86, Standard for Ovens and Furnaces; and NFPA 68, Standard
on Explosion Protection by Deflagration Venting. There are no known major conflicts with NFPA 86. Some
deviations are as follows:
• Data Sheet 6-9 permits manually controlled purge where the external oven volume is less than 350 ft3
(10 m3).
• Data Sheet 6-9 permits natural draft ventilation of a work chamber when less than 64 ft3 (1.8 m3).
NFPA 86 provides recommended venting ratios and other guidance with reference to NFPA 68. NFPA 68
discusses explosion venting for a broad range of building occupancies and equipment. There are conflicts
with the referenced NFPA 68 in the method of determining the vent size, the recommended maximum mass
of the vent, and allowing the relief of the vented gases into a structure. The design criteria of NFPA 68 address
equipment that appears to be considerably stronger than a typical oven.

©2021 Factory Mutual Insurance Company. All rights reserved.

You might also like