WF9613°A°°°°
WF9613°A°°°°
WF9613°A°°°°
Model: WF9613°A°°°°
Code WF
Size 9613
Model ° - Heat pumps with reversible water side
Version A - High efficiency
Set-up ° - Standard
Heat recovery ° - Without heat recovery
Evaporator ° - Standard and in compliance to PED directions
Power supply ° - 400V/3/50Hz with fuses
Selection data
Capacity kW 2,289.8
Input power kW 458.6
Input current A 777
EER W/W 4.99
Ls: Load percentage; Pf: Capacity; Pa: Input power; Ef: EER; Gw: Inlet water temperature (Source side circuit); Gd:
Temperature difference (Source side circuit); Uw: Outlet water temperature (System side circuit); Ud: Temperature
difference (System side circuit).
Water flow and glycol percentage are kept the same at all load percentages.
The sound levels are given at full load, without pumps (if available) and at nominal conditions (external circuit water temperature (in/out):
30.0/35.0 °C, users circuit water temperature (in/out): 12.0/7.0 °C).
Electric data
Full Load Amps (FLA) A 1,053.00
Locked Rotor Amps (LRA) A 1,376.00
Power supply 400V/3/50Hz with fuses
Series
Indoor unit with high-efficiency compressors.
The base, the structure and the panels are made of steel treated with rustproof polyester paint.
The machine allows operation in cooling or heating mode via cycle reverse on the hydraulic side.
Nominal powers
Cooling capacity: 2,289.8 kW (water system side 12.0 °C / 7.0 °C, water source side 32.0 °C / 37.0 °C)
Model
Heat pumps with reversible water side
Version
High-efficiency version obtained by appropriately sizing the condensing surface through the use of an adequate number of
cooling modules.
Refrigerant
HFC R134a, this is characterised by low ODP (ozone depletion potential) and is classified A1 within the safety group in
accordance with the ASHRAE 34-1997 standard.
Cooling circuit
- Made with a copper pipe with welded silver alloy joints.
- Thermostatic valve that modulates gas flow depending on chiller load.
- Filter-drier: it can collect debris and any traces of humidity in the refrigerant circuit.
- Sight glass: used to check the refrigerating gas load and any humidity in the refrigerant circuit.
- Solenoid valve: it closes when the compressor turns off, preventing the flow of refrigerant gas towards the evaporator.
It is envisaged only if no mechanical thermostatic valve is fitted.
- Liquid and pressing line taps: allow the refrigerant to be intercepted in the event of extraordinary maintenance.
Circuit number: 3
Compressor number: 3
Bearing structure
Supporting structure made of hot-dipped galvanised steel sheets, painted with polyester powders, built to guarantee easy
accessibility for service and maintenance.
Compressor
Positive displacement compressor with double screw rotors in steel alloys with semi-hermetic construction type with electric
motor cooled by suction gas.
The compressor is equipped with electric heating to heat the oil: this prevents the refrigerant from becoming excessively
soluble in the oil, thus reducing viscosity, and is automatically powered when the unit is stopped.
Power supply
400V/3/50Hz with fuses
Electrical panel
It contains the power section, the management of the controls and safety devices and the on-board control panel.
It is equipped with a door-lock disconnecting switch to disconnect the power supply by using the opening lever itself. This
lever can be blocked with padlocks during maintenance to prevent the machine from being accidentally powered.
All the cables are numbered so they can be immediately recognised.
Transducers
The unit is supplied equipped with water temperature probes at the exchanger inlet and outlet.
- Low-pressure transducer (one per circuit): it makes it possible to show the value of the compressor intake pressure on
the microprocessor electronic card display; it is installed on the low pressure side of the refrigerant circuit and shuts
down compressor operation in the case of abnormal operating pressure.
- High-pressure transducer (one per circuit): it makes it possible to show the value of the compressor delivery pressure
on the microprocessor electronic card display; it is installed on the high pressure side of the refrigerant circuit and shuts
down compressor operation in the case of abnormal operating pressure.
Electronic regulation
- Control board with microprocessor.
- Control panel.
- Remote ON/OFF with external contact without voltage.
- Multi-language menu.
- Independent control of the individual compressors.
- Amperometric transformer.
- Cumulative faults block signal.
- Historical alarms function.
- Daily/weekly programming.
- Temperature display of the input and output water.
- Alarms display.
- Integral proportional adjustment of the output water temperature (precision up to ±0.1K).
- Function with double set-point linked to an external contact.
- Always Working function. In the case of critical conditions (e.g. an environmental temperature that is too high) the
machine does not stop but can adjust itself and supply the maximum power in those conditions.
- PDC "Pull Down Control" function for preventing the activation of the power steps when the temperature of the water
quickly approaches the set-point. Optimises machine functioning when working normally and in the presence of load
variation, ensuring the best efficiency of the machine in all situations.
- Compensation of the set-point on the basis of the external temperature or from external analogue signal (4-20 mA).
- Compressor rotation management.
Accessories
- For the list and the accessories compatibility see the product data sheet.
Conformity
Inside every unit there is the declaration of CE conformity with reference to the serial number of the appliance.
The unit complies with the following harmonised standards:
- IEC EN 61000-6-2 and IEC EN 61000-6-4 (Immunity and electromagnetic emissions for industrial environments)
- EN378 (Refrigerating systems and heat pumps - Safety and environmental requirements)
- EN12735 (Copper and copper alloys - Seamless, round copper tubes for air conditioning and refrigeration)
- UNI1285-68 Calculation of resistance of metal pipes subject to internal pressure
- EN60204-1 (Safety of machinery - Electrical equipment on machines)
The unit is in compliance with the following directives:
- LVD Directive: 2014/95/EC
- Electromagnetic Compatibility Directive 2014/30/EC
- Machinery Directive 2006/42/EC
- PED Directive regarding pressurised devices 2014/68/EC
The product satisfies the Total Quality Assurance procedure (form H) with certificate no.06/270-QT3664 Rev.10 issued by
notified body no.1131 CEC via Pisacane 46, Legnano (MI) - Italy.