LA400UL - Install and Manual
LA400UL - Install and Manual
LA400UL - Install and Manual
INSTALLATION MANUAL
OPERATOR REQUIRES A
LIFTMASTER EXTERNAL
MONITORED ENTRAPMENT
PROTECTION DEVICE BE
INSTALLED IN ALL
ENTRAPMENT ZONES
•
THIS PRODUCT IS TO BE INSTALLED AND Access installation and technical support
SERVICED BY A TRAINED GATE SYSTEMS guides or register this product
TECHNICIAN ONLY.
Take a photo of the camera
•
This model is for use on vehicular passage 1. icon including the points ( ).
gates ONLY and not intended for use on
pedestrian passage gates.
2. Send it in by texting the
•
This model is intended for use in Class I, II, photo to 71403.
and III vehicular swing gate applications.
•
Visit LiftMaster.com to locate a professional
installing dealer in your area. LA400PKGULTECH
This gate operator is compatible with myQ®
•
and Security+ 2.0® accessories.
LiftMaster
300 Windsor Drive
Oak Brook, IL 60523
TABLE OF CONTENTS
SAFETY 2
OPERATION 28
Safety Symbol and Signal Word Review....................................................2
Control Board Overview...........................................................................28
Usage Class...............................................................................................3
Manual Release........................................................................................29
UL325 Entrapment Protection Requirements............................................3
Reset Button............................................................................................29
Safety Installation Information...................................................................4
Party Mode..............................................................................................29
Gate Construction Information...................................................................5
Operator Alarm .......................................................................................30
INTRODUCTION 6 Remote Control........................................................................................30
Carton Inventory........................................................................................6
ACCESSORY WIRING 31
Operator Specifications..............................................................................7
External Control Devices..........................................................................31
Site Preparation.........................................................................................8
Maglock...................................................................................................32
Check your gate.........................................................................................8
Miscellaneous Wiring...............................................................................32
INSTALLATION 9
MAINTENANCE 33
Installation Tips.........................................................................................9
Important Safety Instructions..................................................................33
Step 1 Attach Brackets to Operator.........................................................10
Maintenance Chart...................................................................................33
Step 2 Determine Mounting Location......................................................11
Batteries...................................................................................................33
Step 3 Position the Operator...................................................................12
Step 4 Secure the Brackets......................................................................13 TROUBLESHOOTING 34
Step 5 Install the Control Box..................................................................14 Diagnostic Codes.....................................................................................34
Step 6 Earth Ground Rod.........................................................................16 Diagnostic Codes Table...........................................................................35
Step 7 Wire the Operator Arm to the Control Board................................16 Control Board LEDs.................................................................................37
Step 8 Dual Gate Setup............................................................................17 Troubleshooting Chart.............................................................................38
Step 9 Install Entrapment Protection.......................................................20 APPENDIX 41
Step 10 Power Wiring..............................................................................22
Bracket Types..........................................................................................41
Step 11 Finish Installation.......................................................................23
Step 10 Solar Panels...............................................................................42
ADJUSTMENT 23 Limit Setup with a Remote Control..........................................................46
Limit and Force Adjustment.....................................................................23 REPAIR PARTS 47
Obstruction Test......................................................................................25
Standard Control Box...............................................................................47
PROGRAMMING 26 Gate Operator Arm...................................................................................47
Remote Controls (Not Provided).............................................................26 WIRING DIAGRAM 48
LiftMaster Internet Gateway (not provided).............................................27
Standard Control Box...............................................................................48
Erase All Codes........................................................................................27
Erase Limits.............................................................................................27 ACCESSORIES 49
Constant Pressure Override (CPO)..........................................................27 WARRANTY 51
To Remove and Erase Monitored Entrapment Protection Devices...........27
TEMPLATE FOR POST BRACKET MOUNTING 52
SAFETY
Safety Symbol and Signal Word Review
When you see these Safety Symbols and Signal Words on the following pages, they will alert
you to the possibility of Serious Injury or Death if you do not comply with the warnings that
accompany them. The hazard may come from something mechanical or from electric shock. MECHANICAL
Read the warnings carefully.
When you see this Signal Word on the following pages, it will alert you to the possibility of
damage to your gate and/or the gate operator if you do not comply with the cautionary
statements that accompany it. Read them carefully.
IMPORTANT NOTE: ELECTRICAL
• BEFORE attempting to install, operate or maintain the operator, you must read and fully
understand this manual and follow all safety instructions.
• DO NOT attempt repair or service of your gate operator unless you are an Authorized
Service Technician.
WARNING: This product can expose you to chemicals including lead, which are known to the State of California to cause cancer or birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov.
2
SAFETY
Usage Class
Class I - Residential Vehicular Gate Operator
A vehicular gate operator (or system) intended for use in garages or
parking areas associated with a residence of one-to four single families.
Class II - Commercial/General Access Vehicular
Gate
A vehicular gate operator (or system) intended for use in a commercial
location or building such as a multi-family housing unit (five or more
single family units), hotel, garages, retail store, or other buildings
accessible by or servicing the general public.
Class III - Industrial/Limited Access Vehicular
Gate
A vehicular gate operator (or system) intended for use in an industrial
location or building such as a factory or loading dock area or other
locations not accessible by or intended to service the general public.
Class IV - Restricted Access Vehicular Gate
Operator
A vehicular gate operator (or system) intended for use in a guarded
industrial location or building such as an airport security area or other
restricted access locations not servicing the general public, in which
unauthorized access is prevented via supervision by security personnel.
l SAVE THESE
INSTRUCTIONS.
3
SAFETY
1. Vehicular gate systems provide convenience and security. Gate systems 9. The Stop and/or Reset (if provided separately) must be located in the
are comprised of many component parts. The gate operator is only one line-of-sight of the gate. Activation of the reset control shall not cause
component. Each gate system is specifically designed for an individual the operator to start.
application. 10. A minimum of two (2) WARNING SIGNS shall be installed in the area
2. Gate operating system designers, installers and users must take into of the gate. Each placard is to be visible by persons located on the side
account the possible hazards associated with each individual of the gate on which the placard is installed.
application. Improperly designed, installed or maintained systems can 11. For a gate operator utilizing a non-contact sensor:
create risks for the user as well as the bystander. Gate systems design a. Reference owner’s manual regarding placement of non-contact
and installation must reduce public exposure to potential hazards. sensor for each type of application. See Install Entrapment
3. A gate operator can create high levels of force in its function as a Protection section.
component part of a gate system. Therefore, safety features must be b. Care shall be exercised to reduce the risk of nuisance tripping,
incorporated into every design. Specific safety features include: such as when a vehicle trips the sensor while the gate is still
l Edges Sensors (contact) moving.
l Photoelectric Sensors c. One or more non-contact sensors shall be located where the risk of
l Vertical Posts entrapment or obstruction exists, such as the perimeter reachable
l Instructional and Precautionary Signage by a moving gate or barrier.
4. Install the gate operator only when: 12. For a gate operator utilizing a contact sensor such as an edge sensor:
a. The operator is appropriate for the construction and the usage a. One or more contact sensors shall be located where the risk of
class of the gate. entrapment or obstruction exists.
b. All exposed pinch points are eliminated or guarded, and guarding b. A hard wired contact sensor shall be located and its wiring
is supplied for exposed rollers. arranged so the communication between the sensor and the gate
5. The operator is intended for installation only on gates used for operator is not subject to mechanical damage.
vehicles. Pedestrians must be supplied with a separate access opening. c. A wireless device such as one that transmits radio frequency (RF)
The pedestrian access opening shall be designed to promote pedestrian signals to the gate operator for entrapment protection functions
usage. Locate the gate such that persons will not come in contact with shall be located where the transmission of the signals are not
the vehicular gate during the entire path of travel of the vehicular gate. obstructed or impeded by building structures, natural landscaping
6. The gate must be installed in a location so that enough clearance is or similar obstruction. A wireless device shall function under the
supplied between the gate and adjacent structures when opening and intended end-use conditions.
closing to reduce the risk of entrapment. Swinging gates shall not open d. One or more contact sensors shall be located on the inside and
into public access areas. outside leading edge of a swing gate. Additionally, if the bottom
7. The gate must be properly installed and work freely in both directions edge of a swing gate is greater than 4 inches (10.1 cm) but less
prior to the installation of the gate operator. than 16 inches (406 mm) above the ground at any point in its arc
of travel, one or more contact sensors shall be located on the
8. Permanently mounted access controls intended for users to activate, bottom edge.
must be located at least 6 feet (1.8 m) away from any moving part of
the gate and where the user is prevented from reaching over, under,
around or through the gate to operate the controls. Outdoor or easily
accessible controls shall have a security feature to prevent unauthorized
use. Exception: Emergency access controls only accessible by
authorized personnel (e.g. fire, police) may be placed at any location in
the line-of-sight of the gate.
4
SAFETY
1. General Requirements
3. Vehicular Horizontal Swing Gate
1.1 Gates shall be constructed in accordance with the provisions
given for the appropriate gate type listed, refer to ASTM F2200 3.1 The following provisions shall apply to Class I, Class II and Class III
for additional gate types. vehicular horizontal swing gates:
1.2 Gates shall be designed, constructed and installed to not fall 3.1.1 Gates shall be designed, constructed and installed so as not to
over more than 45 degrees from the vertical plane, when a create an entrapment area between the gate and the supporting
gate is detached from the supporting hardware. structure or other fixed object when the gate moves toward the fully
open position, subject to the provisions in 3.1.1.1 and 3.1.1.2
1.3 Gates shall have smooth bottom edges, with vertical bottom
edged protrusions not exceeding 0.50 inches (12.7 mm) when 3.1.1.1 The width of an object (such as a wall, pillar or column) covered by
other than the exceptions listed in ASTM F2200. a swing gate when in the open position shall not exceed 4 inches
(102 mm), measured from the center line of the pivot point of the
1.4 The minimum height for barbed tape shall not be less than 8 gate. Exception: For a gate not in compliance with this provision,
feet (2.44 m) above grade and for barbed wire shall not be the defined area must be provided with entrapment protection per
less than 6 feet (1.83 m) above grade. UL 325.
1.5 An existing gate latch shall be disabled when a manually 3.1.1.2 Except for the zone specified in Section 3.1.1.1, the distance
operated gate is retrofitted with a powered gate operator. between a fixed object such as a wall, pillar or column, and a swing
1.6 A gate latch shall not be installed on an automatically operated gate when in the open position shall not be less than 16 inches
gate. (406 mm). Exception: For a gate not in compliance with this
provision, the defined area must be provided with entrapment
1.7 Protrusions shall not be permitted on any gate, refer to ASTM protection per UL 325.
F2200 for Exceptions.
3.2 Class IV vehicular horizontal swing gates shall be designed,
1.8 Gates shall be designed, constructed and installed such that constructed and installed in accordance with security related
their movement shall not be initiated by gravity when an parameters specific to the application in question.
automatic operator is disconnected, in accordance with the
following.
1.8.1 Vehicular horizontal swing gate. Shall not result in
continuous, unimpeded movement in either direction along
the arc of its path of travel.
1.9 For pedestrian access in the vicinity of an automated vehicular
gate, a separate pedestrian gate shall be provided. The
pedestrian gate shall be installed in a location such that a
pedestrian shall not come in contact with a moving vehicular
access gate. A pedestrian gate shall not be incorporated into
an automated vehicular gate panel.
2. Specific Applications
2.1 Any non-automated gate that is to be automated shall be
upgraded to conform to the provisions of this specification.
2.2 This specification shall not apply to gates generally used for
pedestrian access and to vehicular gates not to be automated.
2.3 When the gate operator requires replacement, the existing gate
shall be upgraded to conform to the provisions of this
specification.
2.4 When the gate of an automated gate system requires
replacement, the new gate shall conform to the provisions of
this specification.
5
INTRODUCTION
Carton Inventory
NOT SHOWN: Documentation packet and hardware bag
Hardware Inventory
NOTE: Hardware quantities shown below are for LA412DC. Quantities are doubled for LA412DCS.
Flat Washer 5/16" (1) Hex Nut 5/16"-18 (1) Key (2)
Keylock Cap
Hex Bolt 5/16"-18 x 1-1/2" (1) Hex Bolt 3/8"-16 x 1-1/2" (1) Pin (2)
Optional Accessories
Push-to-Open Bracket (Model 50-19503)
If your application requires the gate to be pushed open, a push-to-open
bracket is required, see Accessories.
Expansion Board (Model K1D8387-1CC)
Large Metal Control Box for Solar Applications
(Model XLSOLARCONTUL)
Required for solar installations (batteries not included). Requires two
33AH batteries, battery tray, and solar battery harness, see Accessories.
6
INTRODUCTION
Operator Specifications
Usage Classification Class I, II, & III
Main AC Supply 120 Vac, .5 Amps (6.5 Amps including Accessory Outlets)
System Operating Voltage 24 Vdc Battery Run / Direct Plug-in Transformer Charge
Accessory Power 24 Vdc, 500mA max. for ON + SW (switched)
Solar Power Max 24 Vdc at 60 watts max.
Maximum Gate Weight/Length 850 lbs. (385.6 kg) / 10 ft (3.0 m)
750 lbs. (340.2 kg) / 12 ft (3.7 m)
650 lbs. (294.8 kg) / 14 ft (4.3 m)
550 lbs. (249.5 kg) / 16 ft (4.9 m)
90 Degree Travel Time* 15-18 seconds
Maximum Travel Range* 115 degrees
Maximum Daily Cycle Rate 100 cycles / day
Maximum Duty Cycle 4 min on
Operating Temperature -20°C to 60°C (-4°F to 140°F)
Expansion Board Optional
External Entrapment Protection Device Inputs (non- Main board - up to 2 close entrapment protection devices and 1 open entrapment
contact and/or contact) protection device.
Expansion board - up to 3 entrapment protection devices configurable to either close or
open direction and up to 4 edge sensors using wireless edge sensor kit model LMWEKITU.
*Travel time and range are affected by A and B mounting dimensions, see INSTALLATION.
7
INTRODUCTION
Site Preparation
Check the national and local building codes BEFORE installation.
Safety Gate
Entrapment protection devices are required to protect against any Gate must be constructed and installed according to ASTM F2200
entrapment or safety conditions encountered in your gate application. standards (refer to page 4). Gate must fit specifications of operator (refer
Install a warning sign (two provided) on the inside and outside of the to specifications).
property, where easily visible.
8
INSTALLATION
l To AVOID damaging gas, power or other underground utility lines, l ALWAYS wear protective gloves and eye protection when changing
contact underground utility locating companies BEFORE digging more the battery or working around the battery compartment.
than 18 inches (46 cm) deep.
Installation Tips
Do's
l Weld a horizontal bar across entire gate on any installation for l The operator can be mounted on top of the gate frame.
strength. Make sure that the operator is mounted level or it will not l The operator must be installed at least 12" (30 cm) from the ground.
function properly.
l Make sure there is slack in the operator cable.
Don'ts
l DO NOT install upside down. l DO NOT install on ANY pedestrian passageways, doorways, or gates.
l DO NOT install next to sprinklers or any area that may expose the l DO NOT over-bend the operator cable. Doing this will cause the wires to
bottom of operator to water. eventually break.
l DO NOT install on uphill or downhill gates. l DO NOT weld the crossbar on just a few pickets, or they could bend.
9
INSTALLATION
10
INSTALLATION
Template Method
1. Close the gate.
2. Place the template (provided on the back page of this manual) under
the center of the gate hinge point.
3. Use a screwdriver or dowel rod to temporarily mark the location in
front of the gate post.
OR
Tape Measure Method
1. Close the gate.
2. Place the measuring tape under the center of the gate hinge point
and measure out 7 inches (17.8 cm).
3. Use a screwdriver or dowel rod to temporarily mark the location of
the first measurement.
4. Measure 7 inches (17.8 cm) from the previous mark.
5. Use the screwdriver or dowel rod to mark the location of the second
measurement.
Alternate Dimensions
The ideal installation measurements are A = 7" (17.8 cm) and B = 7"
(17.8 cm). If different measurements are used, the sum of A and B
cannot be greater than 15" (38.1 cm).
DIMENSION CHART
A B
7" (17.8 cm) 7" (17.8 cm)
8" (20.3 cm) 6" (15.2 cm)
7-1/2" (19.1 cm) 7-1/2" (19.1 cm)
6-1/2" (16.5 cm) 6-1/2" (16.5 cm)
6" (15.2 cm) 6" (15.2 cm)
11
INSTALLATION
NOTE: The post bracket assembly can be mounted several places on the
gate post.
1. Open the gate to desired open position (no greater than 100°) and
hold operator against gate.
2. Place the operator arm against gate post at the desired position.
Temporarily secure gate post bracket with clamp. The gate operator
(arm) must be level.
3. Mark mounting holes on gate for reference. Temporarily secure the
gate bracket using a clamp.
4. Align the pull-to-open bracket to a position as CLOSE AS POSSIBLE
above the screwdriver or dowel rod.
5. Insert hex bolt through pull-to-open bracket and post bracket and
secure with washer, lock washer and nut.
12
INSTALLATION
13
INSTALLATION
14
INSTALLATION
Post Mount
NOTE: The post mount option is not recommended for the 33AH battery
application.
1. Open the control box. The control box door may be removed by
opening the door 90°. Lift the door from the hinges and set aside
until the installation is complete.
2. The control box can be mounted to a post with 'U' bolts (refer to
chart). The knock out will accommodate a 3/8" diameter 'U' bolt.
Select center mounting holes (top and bottom) and knock out using
a screwdriver and hammer.
3. Secure the control box to mounting surface with U-bolts and rubber
washers (not provided) to ensure a watertight seal.
15
INSTALLATION
16
INSTALLATION
17
INSTALLATION
Wired Setup
18
INSTALLATION
19
INSTALLATION
20
INSTALLATION
Control Board
CLOSES EYES/INTERRUPT
(2 Terminals) The CLOSE EYES/INTERRUPT input is for photoelectric
sensor entrapment protection for the close direction. When an
obstruction is sensed during gate closing the gate will open to the full
open position and resets the Timer-to-Close. This input will be
disregarded during gate opening.
CLOSE EDGE
(2 Terminals) The CLOSE EDGE input is for edge sensor entrapment
protection for the close direction. When an obstruction is sensed during
gate closing the gate will reverse to the full open position, disengaging
the Timer-to-Close. This input will be disregarded during gate opening.
OPEN EYES/EDGE
(2 Terminals) The OPEN EYES/EDGE input is for photoelectric sensor or
edge sensor entrapment protection for the open direction. When an
obstruction is sensed during gate opening the gate will reverse for 4
seconds then stop. This input will be disregarded during gate closing.
21
INSTALLATION
All control wiring used to connect external devices to Class 2 circuits of the operator must be (QPTZ) Power-Limited Circuit Cables, Type CL2, CL2P,
CL2R, or CL2X or other cable with equivalent or better electrical, mechanical, and flammability ratings.
22
INSTALLATION
ADJUSTMENT
Limit and Force Adjustment
Introduction
Your operator is designed with electronic controls to make travel limit
LIMIT SETUP LEDS
and force adjustments easy. The adjustments allow you to program
where the gate will stop in the open and close position. The electronic SET SET CLOSE OPERATOR MODE EXPLANATION
controls sense the amount of force required to open and close the gate. OPEN LED
The force is adjusted automatically when you program the limits but LED
should be fine tuned using the REVERSAL FORCE dial on the control OFF OFF NORMAL MODE Limits are set
board (refer to Fine Tune the Force section) to compensate for
environmental changes. The limit setup LEDs (located next to the SET BLINKING BLINKING LIMIT SETTING Limits are not set
OPEN and SET CLOSE buttons) indicate the status of the limits, refer to MODE
the table to the right. BLINKING ON LIMIT SETTING Open limit is not set
The limits can be set using the control board (below) or a remote control MODE
(refer to Limit Setup with a Remote Control in the Appendix). Setting the
limits with a remote control requires a 3-button remote control ON BLINKING LIMIT SETTING Close limit is not set
programmed to OPEN, CLOSE, and STOP. MODE
NOTE: The TEST buttons on the control board will not work until the ON ON LIMIT SETTING Limits are set
limits have been set and the required entrapment protection devices are MODE
installed.
23
ADJUSTMENT
24
ADJUSTMENT
Obstruction Test
The operator is equipped with an inherent (built in to the operator)
obstruction sensing device. If the gate encounters an obstruction during
motion, the operator will reverse direction of the gate and then stop. The
following procedure will test ONLY the inherent (built in to the operator)
obstruction sensing device:
1. Open and close the gate with the TEST BUTTONS, ensuring that the
gate is stopping at the proper open and close limit positions.
2. Place an object between the open gate and a rigid structure. Make
sure that any external entrapment protection devices will NOT be
activated by the object.
3. Run the gate in the close direction. The gate should stop and reverse
upon contact with the object. If the gate does not reverse off the
object, reduce the force setting by turning the force control slightly
counter-clockwise. The gate should have enough force to reach both
the open and close limits, but MUST reverse after contact with an
object.
4. Repeat the test for the open direction.
Test the operator after any adjustments are made.
25
PROGRAMMING
There are 3 different options for programming the remote control depending on how you would like the remote control to function. Choose a
programming option:
OPTION DESCRIPTION PROGRAMMING STEPS
Single button as OPEN Program a single button on the remote 1. Press and release the LEARN button (operator will beep and green
only control for open only. The Timer-to-Close XMITTER LED will light). NOTE: The operator will time out of
can be set to close the gate. programming mode after 30 seconds.
2. Press the OPEN button.
3. Press the remote control button that you would like to program.
Single button (SBC) as Program one remote control button as an 1. Press and release the LEARN button (operator will beep and green
OPEN, CLOSE, and STOP open, close, and stop. XMITTER LED will light). NOTE: The operator will time out of
programming mode after 30 seconds.
2. Press the remote control button that you would like to program.
Three separate buttons as Program each remote control button as an 1. Press and release the LEARN button (operator will beep and green
OPEN, CLOSE, and STOP open, close, and stop. XMITTER LED will light). NOTE: The operator will time out of
programming mode after 30 seconds.
2. Press the OPEN, CLOSE, or STOP button, depending on the desired
function.
3. Press the remote control button that you would like to program.
The operator will automatically exit learn mode (operator will beep and green XMITTER LED will go out) if programming is successful. To program
additional Security+ 2.0® remote controls or remote control buttons, repeat the programming steps above.
NOTICE: This device complies with Part 15 of the FCC rules and Industry Canada’s license-exempt RSSs. Operation is subject to the following two conditions: (1) this device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
This device must be installed to ensure a minimum 20 cm (8 in.) distance is maintained between users/bystanders and device.
This device has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC rules and Industry Canada ICES standard. These limits are designed
to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
26
PROGRAMMING
Erase Limits
1. To erase the limits, press and hold the SET OPEN and SET CLOSE
buttons simultaneously (5 seconds) until both the SET OPEN and SET
CLOSE LEDs blink rapidly and the operator beeps.
2. Release the buttons and the SET OPEN and SET CLOSE LEDs will blink
slowly indicating the limits will need to be set.
27
OPERATION
28
OPERATION
Manual Release
In case of a power failure, the operator can be disengaged from the gate.
With an operator, the release action may sometimes feel stiff/jerky, which
is normal and has no effect on function. NOTE: It is normal for the
operator to run slow right after a disconnect or complete loss of AC/
battery power (the operator will need to run a complete open and close
cycle).
Release
1. Insert the key into the lock.
2. Turn the key counter-clockwise 180°.
3. Turn the release lever counter-clockwise 180°.
Operator is in manual mode and the gate can be opened and closed
manually. The lock relay will activate then turn off after 2 minutes to
conserve power.
Engage
1. Turn the release lever clockwise 180°. This engages the motor.
2. Turn the key clockwise 180°. This locks the release lever.
3. Remove the key and store in a safe place. The operator is now
engaged.
Reset Button
The reset button is located on the side of the control box and serves
several functions:
l Press the reset button to stop a moving gate during a normal
open/close cycle, like a stop button.
l Press the reset button once while the gate is in open position to
disable the Timer-to-Close. The gate will stay in the open position.
To restart the Timer-to-Close either press the reset button or activate
the gate with a programmed remote control.
l Press the reset button to shut off the alarm and reset the operator.
Party Mode
Press the reset button once while the gate is in open position to disable the Timer-to-Close. The gate will stay in the open position. To restart the Timer-to-
Close either press the reset button or activate the gate with a programmed remote control.
Party Mode can also be enabled from a KPW5 or KPW250 keypad (not provided). To use the Party Mode Feature:
1. Enter a valid 4-digit PIN when the gate is at the Open Limit and the timer is running.
2. The operator will chirp indicating the timer is canceled.
Perform one of the following to restart the gate:
1. Re-enter the 4-digit PIN.
2. Activate a Hard input or a programmed remote.
29
OPERATION
Operator Alarm
If a contact sensor detects an obstruction twice consecutively the alarm
will sound (up to 5 minutes) and the operator will need to be reset.
When the inherent force of the operator (RPM/current sensor) detects the
following (twice consecutively) the alarm will sound (up to 5 minutes)
and the operator will need to be reset.
A. The operator arm or gate is incorrectly installed.
B. The gate does not meet specifications.
C. Gate hinges are too tight or broken and the gate is not moving freely.
D. The gate is moving and a car pushes the gate.
E. A foreign object is on the gate frame while the gate is moving.
F. The gate hits the driveway or curb and gets stuck or bent in an
awkward position.
Remove any obstructions. Press the reset button to shut off the alarm and
reset the operator. After the operator is reset, normal functions will
resume.
The operator alarm will beep 3 times with a command if the battery is
low.
Remote control
Single Button Control (SBC) Functionality
Once the remote control has been programmed the operator will operate
as follows:
When gate is in the closed position, activation of the remote control
button will open the gate. During the open cycle another activation of the
remote control will stop the gate and the next activation of the remote
control will close the gate.
When the gate is in the open position, activation of the remote control
button will close the gate. If the remote control is activated while the gate
is closing, the gate will stop and the next activation will open the gate.
30
ACCESSORY WIRING
All control wiring used to connect external devices to Class 2 circuits of the operator must be (QPTZ) Power-Limited Circuit Cables, Type CL2, CL2P,
CL2R, or CL2X or other cable with equivalent or better electrical, mechanical, and flammability ratings.
31
ACCESSORY WIRING
Maglock
LOCK (2 Terminals, N.C. and COM)
Relay contact output, Normally - closed (N.C.) output for maglocks.
Relay activates prior to motor activation and during motor run. Relay is
off when motor is off.
Miscellaneous wiring
Single button control (SBC) (2 Terminals)
Gate command sequence - Open, Stop, Close, Stop,...
Soft open (maintained switch does not override external safeties and
does not reset alarm condition).
Fire department open input (2 Terminals)
Acts as hard open.
Maintained input overrides (ignores) external safeties (photoelectric
sensor and edge), pauses Timer-to-Close momentary input logic as
single button control and safeties remain active, re-enables Timer-to-
Close.
Accessory power 24 VDC, MAX 500 mA (4
Terminals)
l SWITCHED: Switched ON with gate motion and at the open limit
when Timer-to-Close is active. Turns off 5 seconds after motion.
l UNSWITCHED: 24 Vdc voltage out to power accessories, always ON.
32
MAINTENANCE
l ALWAYS wear protective gloves and eye protection when changing the battery or working around the battery compartment.
Maintenance Chart
Disconnect all power (AC, solar, battery) to the operator before servicing. The operator's AC Power switch ONLY turns off AC power to the control
board and DOES NOT turn off battery power. ALWAYS disconnect the batteries to service the operator.
DESCRIPTION TASK CHECK AT LEAST ONCE EVERY
MONTH 6 MONTHS 3 YEARS
Entrapment Protection Devices Check and test for proper operation X
Warning Signs Make sure they are present and replace if worn or broken X
Manual Release Check and test for proper operation X
Gate Inspect for wear or damage; ensure it still complies with
X
ASTM F2200, see page 5
Accessories Check all for proper operation X
Electrical Inspect all wire connections X
Mounting Hardware Check for tightness X
Operator Inspect for wear or damage X
Batteries Replace X
NOTES:
l Severe or high cycle usage will require more frequent maintenance checks.
l It is suggested that while at the site voltage readings be taken at the operator. Using a digital voltmeter, verify that the incoming voltage to the operator
is within ten percent of the operator’s rating.
Batteries
Batteries will degrade over time depending on temperature and usage. The operator alarm will beep 3 times with a command if the battery is low. Batteries
do not perform well in extremely cold temperatures. For best performance, the batteries should be replaced every 3 years. Use only LiftMaster part
29-NP712 for replacement batteries. The batteries contain lead and need to be disposed of properly.
The standard control box comes with two 7AH batteries.
33
TROUBLESHOOTING
To protect against fire and electrocution: For continued protection against fire:
l DISCONNECT power (AC or solar and battery) BEFORE installing or l Replace ONLY with fuse of same type and rating.
servicing operator.
Diagnostic Codes
NOTE: When cycling or disconnecting power (ac/dc) to the control board, it is recommended that you unplug the J15 plug.
The operator will show the code sequence number followed by the code
number:
To Exit
Press and release the STOP button to exit. The display will also time out
after two minutes of inactivity.
The operator will only keep track of up to 20 codes, then will start saving
over the oldest codes as new codes occur.
34
TROUBLESHOOTING
35
TROUBLESHOOTING
36
TROUBLESHOOTING
37
TROUBLESHOOTING
Troubleshooting Chart
SYMPTOM POSSIBLE CAUSES SOLUTIONS
Operator does not a. No power to control board a. Check AC and battery power
run and diagnostic b. Open fuse b. Check fuses
display not on. c. If on battery power only, low or dead c. Charge batteries by AC or solar power or replace batteries
batteries d. Replace defective control board
d. Defective control board
Control board a. Reset switch is stuck a. Check reset switch
powers up, but b. Stop button active or jumper not in place b. Check Stop button is not “stuck on”, or verify that the stop button is a
motor does not for stop circuit normally closed circuit, or put a jumper on the stop circuit.
run. c. If on battery power only, low or dead c. Charges batteries by AC or solar power or replace batteries
batteries d. Check all Open and Close inputs for a “stuck on” input
d. Open or Close input active e. Check all Entrapment Protection Device inputs for a “stuck on” sensor
e. Entrapment Protection Device active f. Check all vehicle detector inputs for a “stuck on” detector
f. Vehicle loop detector or probe active g. Replace defective control board
g. Defective control board
Arm moves, but a. Arm does not extend or retract enough a. Disengage the arm and ensure arm moves freely
cannot set correct during travel b. Examine the hinge point where the arm mounts to the gate post. Make
limits. b. Arm is interfering with mounting bracket sure that the arm housing does not hit or interfere with the gate post or
c. Gate is too difficult to move mounting bracket. Correct as necessary.
c. Disconnect arm from gate and move gate manually. Gate must move
easily and freely through its entire range, limit-to-limit. Repair gate as
needed.
Gate does not fully a. Arm does not extend or retract enough a. Disengage the arm and ensure arm moves freely
open or fully close during travel b. Examine the hinge point where the arm mounts to the gate post. Make
when setting b. Arm is interfering with mounting bracket sure that the arm housing does not hit or interfere with the gate post or
limits. c. Gate is too difficult to move mounting bracket. Correct as necessary.
c. Remove arm from gate and move gate manually. Gate must move easily
and freely through its entire range, limit-to-limit. Repair gate as needed.
Operator does not a. Check Open and Close command input a. Check all Open and Close inputs for a “stuck on” input
respond to a wired LEDs b. Check Stop button is not “stuck on”
control/command b. Stop button is active c. Check Reset button
(example: Open, c. Reset button is stuck d. Charges batteries by AC or solar power or replace batteries
Close, SBC, etc.) d. If on battery power only, low or dead e. Check all Entrapment Protection Device inputs for a “stuck on” sensor
batteries f. Check all vehicle detector inputs for a “stuck on” detector
e. Entrapment Protection Device active
f. Vehicle loop detector or vehicle probe
active
Operator does not a. Check XMITTER LED when wireless a. Activate wireless control and check XMITTER LED is on. Re-learn
respond to a control is active wireless control/transmitter to control board. Replace wireless control as
wireless control or b. Stop button is active needed.
transmitter c. Reset button is stuck b. Check Stop button is not “stuck on”
d. Poor radio reception c. Check Reset button
d. Check if similar wired control operates correctly. Check if wireless
controls works properly when within a few feet of operator. Check
operator’s antenna and antenna wire. Check other wireless controls or
devices.
Gate stops during a. Control (Open, Close) becoming active a. Check all Open and Close inputs for an active input
travel and reverses b. Vehicle loop detector active b. Check all vehicle detector inputs for an active detector
immediately. c. Low battery voltage c. Battery voltage must be 23.0 Vdc or higher. Charge batteries by AC or
solar power or replace batteries
38
TROUBLESHOOTING
39
TROUBLESHOOTING
40
APPENDIX
Bracket Types
Pull-to-Open
Push-to-Open
41
APPENDIX
Solar Zones
Solar panel recommendations are based upon the average solar radiation and the temperature effects on batteries in the given zones as shown on the map
below. Local geography and weather conditions may require additional solar panels. Solar powered gate operator installations are not supported in
northern climates due to cold weather and a reduced number of hours of sunlight during the winter months. The cycles/day ratings are approximations.
Ratings vary based on gate construction, installation, and temperature. Solar panels cannot be installed in areas that experience long periods of heavy fog,
lake effect snow, or rain.
42
APPENDIX
43
APPENDIX
Position
The location of the panel(s) is critical to the success of the installation. In general, the panel(s) should be mounted using the provided angle bracket facing
due south. The solar panel(s) should be mounted in an area clear of all obstructions and shade from buildings and trees. If the panel(s) is not casting a
shadow, the battery is not being charged.
NOTE: Tall trees or buildings that do not shade the solar panel(s) in the summer could shade the solar panel(s) during the winter months when the sun sits
lower in the sky.
Installation
Solar panel(s) MUST be installed facing south. Use a compass to determine direction. Below are general instructions for installing the solar panel(s). Your
installation may vary slightly depending on the solar panel purchased.
1. Position the mounting bracket on the mounting surface. Mark and drill holes.
2. Secure the solar panel to the mounting bracket using the hex bolts, hex nuts and washers provided.
3. Secure the solar panel to the mounting surface using lag screws provided.
44
APPENDIX
45
APPENDIX
46
REPAIR PARTS
47
WIRING DIAGRAM
48
ACCESSORIES
Entrapment Protection
Remote controls
LiftMaster monitored through beam LiftMaster offers a variety of LiftMaster remote controls to satisfy your
photoelectric sensor application needs. Single-button to 4-button, visor or key chain. The following
Models LMTBUL and LMTBU remote controls are compatible with operators manufactured by LiftMaster after
1993. Contact your authorized LiftMaster dealer for additional details and
options.
3-button remote control
LiftMaster monitored retro-reflective
The 3-button remote control can be programmed to
photoelectric sensor
control the operator. Includes visor clip.
Models LMRRUL and LMRRU
Model 893MAX
Plastic channel
8 ft. (2.4 m) for both small and large profile edges (pack of 10).
Model L50CHP
Aluminum channel
10 ft. (3.1 m) for both small and large edge profiles (pack of 8).
Model L50CHAL
LiftMaster large profile monitored edges (4ft.,5ft., 6ft.)
Model L504AL, L505AL, L506AL
LiftMaster small profile monitored edges (4ft.,5ft., 6ft.)
Model S504AL, S505AL, S506AL
Edge cutting tool
Model ETOOL
49
ACCESSORIES
Wire harness
Between main control board and expansion board.
Model K94- 34778
50
WARRANTY
LiftMaster warrants to the first purchaser of this product, for the structure in which this product is originally installed, that it is free from defect in materials
and/or workmanship for a period of TWO years from the date of purchase. The proper operation of this product is dependent on your compliance with the
instructions regarding installation, operation, maintenance and testing. Failure to comply strictly with those instructions will void this limited warranty in
its entirety.
If, during the limited warranty period, this product appears to contain a defect covered by this limited warranty, call 1-800-528-2806, toll free, before
dismantling this product. Then send this product, pre-paid and insured, to our service center for warranty repair. You will be advised of shipping
instructions when you call. Please include a brief description of the problem and a dated proof-of purchase receipt with any product returned for warranty
repair. Products returned to Seller for warranty repair, which upon receipt by Seller are confirmed to be defective and covered by this limited warranty, will
be repaired or replaced (at Seller’s sole option) at no cost to you and returned pre-paid. Defective parts will be repaired or replaced with new or factory-
rebuilt parts at Seller’s sole option.
ALL IMPLIED WARRANTIES FOR THE PRODUCT, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO THE TWO YEAR LIMITED WARRANTY PERIOD SET FORTH ABOVE, AND NO IMPLIED
WARRANTIES WILL EXIST OR APPLY AFTER SUCH PERIOD. Some states do not allow limitations on how long an implied warranty lasts, so the
above limitation may not apply to you. THIS LIMITED WARRANTY DOES NOT COVER NON-DEFECT DAMAGE, DAMAGE CAUSED BY IMPROPER
INSTALLATION, OPERATION OR CARE (INCLUDING, BUT NOT LIMITED TO ABUSE, MISUSE, FAILURE TO PROVIDE REASONABLE AND NECESSARY
MAINTENANCE, UNAUTHORIZED REPAIRS OR ANY ALTERATIONS TO THIS PRODUCT), LABOR CHARGES FOR REINSTALLING A REPAIRED OR
REPLACED UNIT, OR REPLACEMENT OF BATTERIES.
THIS LIMITED WARRANTY DOES NOT COVER ANY PROBLEMS WITH, OR RELATING TO, THE GATE OR GATE HARDWARE, INCLUDING BUT NOT
LIMITED TO THE GATE SPRINGS, GATE ROLLERS, GATE ALIGNMENT OR HINGES. THIS LIMITED WARRANTY ALSO DOES NOT COVER ANY
PROBLEMS CAUSED BY INTERFERENCE. ANY SERVICE CALL THAT DETERMINES THE PROBLEM HAS BEEN CAUSED BY ANY OF THESE ITEMS
COULD RESULT IN A FEE TO YOU.
UNDER NO CIRCUMSTANCES SHALL SELLER BE LIABLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES ARISING IN CONNECTION WITH
USE, OR INABILITY TO USE, THIS PRODUCT. IN NO EVENT SHALL SELLER’S LIABILITY FOR BREACH OF WARRANTY, BREACH OF CONTRACT,
NEGLIGENCE OR STRICT LIABILITY EXCEED THE COST OF THE PRODUCT COVERED HEREBY. NO PERSON IS AUTHORIZED TO ASSUME FOR US ANY
OTHER LIABILITY IN CONNECTION WITH THE SALE OF THIS PRODUCT.
Some states do not allow the exclusion or limitation of consequential, incidental or special damages, so the above limitation or exclusion may not apply to
you. This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
51
TEMPLATE FOR POST BRACKET MOUNTING
7
6
5
4
3
2
1
7 6 5 4 3 2 1
01-39384B