Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Fire Sentry FS24X SPECIFICATIONS

Multi-Spectrum QuadBand™ Triple IR


Flame Detector
General Specifications
Field of View 90° Full 100% Cone of vision, ± 45° from on axis OR 110° Full 100% Cone of vision, ± 55° from on axis
Sensitivity Very High, High, Medium and Low – Switch Selectable
Response Time 3-5 Seconds to 1 sq. ft. n-Heptane fire at 100 ft.
3-10 Seconds to 1 sq. ft. n-Heptane fire at 200 ft.
Spectral Sensitivity Visible: 400 – 700 nanometers
Near Band IR: 0.7 – 1.1 microns
Wide Band IR: 1.1 – 3 microns
Wide Band IR: 3.0 – 5.0 microns
Operating Voltage 24 VDC nominal (18-32 VDC) - Regulated
Power Consumption Operating: 56 mA @ 24 VDC nominal
Alarm: 106 mA @ 24 VDC nominal
Heater: 155 mA – additional
Note: Heater will turn on at 0ºF (-17ºC)
Output Relays Fire Alarm: SPDT (NO / NC) – De-Energized/Energized, Latching/Non-Latching
Fault: SPST (NO) – Normally Energized, Latching/Non-Latching
Auxiliary: SPDT (NO / NC) – De-Energized/Energized, Latching/Non-Latching
Contacts rating: 1 amp @ 24 VDC
Analog Output 0 - 20 mA stepped - Source or Sink User Selectable
Loop resistance 50 - 400 Ohms
Communication One of the following – User Selectable:
• RS-485, ModBus Protocol
• RS-485, FireBus II
• HART, Optional plug-in module
Visual Indications Green LED: Power
Red LED: Alarm
Yellow LED: Fault
Temperature Range Operating: 110° Field of View FS24X: -40 to +185ºF (-40 to +85ºC); 90° Field of View FS24X: -76 to +185°F (-60 to +85°C)
Storage: -67 to +230ºF (-55 to +110ºC)
Humidity Range 5 to 98% relative humidity, non-condensing
Vibration Meets or exceeds MilSpec 810C Method 514.2, Curve AW12
Wiring 14 AWG (2.5mm2) to 22 AWG (0.326mm2); Shielded Cable Recommended
Conduit Entries Standard: Two ¾” NPT or two M25
Enclosure Materials Copper-Free Powder Coated Aluminum or 316 Stainless Steel
Enclosure Type NEMA 4 & 4X, IP66
Certifications FM: Class I, Div. 1 & 2, Groups B, C, & D; Class II, Div. 1 & 2, Groups E, F, & G; Class III
ATEX: II 2 G Ex db IIC T (see description; dependent on T code), II 2 D Ex tb IIIC T135°C
110° Field of View FS24X: T4 (Ta: -40 to +110°C), T5 (Ta: -40 to +75°C), T6 (Ta: -60 to +60°C)
90° Field of View FS24X: T4 (Ta: -60 to +110°C), T5 (Ta: -60 to +75°C), T6 (Ta: -60 to +60°C)
CE: Complies with EN6100-6-4 & EN50130-4
SIL Rating: FMEDA is available upon request
Shipping Weight Aluminum: 3.6 lbs (1.6 kg)
Stainless Steel: 7 lbs (3.2 kg)
Mounting Swivel Bracket Assembly - Optional
Warranty Three years from date of shipping

Find out more General Dimensions


www.honeywellanalytics.com Side and Back Views
(All Dimensions in Inches)
Toll-free: 800.538.0363

Please Note:
While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions.
Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations,
standards, and guidelines. This publication is not intended to form the basis of a contract.

SS01145_v8 11/14
© 2014 Honeywell Analytics

You might also like