Acegafxr 360 T 2 ML

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Model: ACEGAFXR360T2ML Date of Selection: 04/04/2024 / 16:05:25

Software Version: 4.06 Application Name: Voltas Chiller Selection Program

Customer : Engineer Name : admin


Project : SCREW CHILLER ISP/SSP :
Consultant : Location :
AIR COOLED EFFICIENT SCREW R134A Package Technical Specifications
Manufacturer: : VOLTAS LIMITED, INDIA Chiller Series: : ENERGY EFFICENT AC
Actual Capacity: : 354.6 Tons FLOODED CHILLER
Chiller Package Model: : ACEGAFXR360T2ML Refrigerant:- : R-134a
Nominal Capacity: : 354.6 Tons
Additional Features required if any: Refer Annexure

Unit Operation Condition Evaporator

Fluid WATER
Fluid Inlet Temp °C 12.00
Fluid Outlet Temp °C 7.00
Fouling Factor M² °K/kW 0.0180
Ambient Temp °C 35.0
Altitude mtr 0.00
Chiller Performance Data at full load condition Evaporator

Fluid Flow Rate L/s 59.65


Fluid Pressure Drop Kpa 63.6

Capacity Tons 354.6 kW/Ton 0.995


Unit Power Consumption KW 352.8 COP (kW/kW) 3.534
Unit Operating Current Amp 613.85 EER (Btu/W-h) 12.060

Tolerance on above parameters as per AHRI Standard


Special Note :-
Part Load Performance at AHRI condition: Reducing Ambient Temperature(IPLV)

% LOAD AMBIENT CAPACITY INPUT IKW/TR FLOWRATE PRESSURE INLET OUTLET


TEMP. ( °C) (TR) POWER (KW) ( L/s) DROP ( Kpa) TEMP. ( °C) TEMP. ( °C)

100 35.0 354.6 352.8 0.9950 59.65 63.6 12.00 7.00


75 27.0 265.9 213.8 0.8040 59.65 63.6 10.74 7.00
50 19.0 177.3 126.0 0.7110 59.65 63.6 9.50 7.00
25 13.0 88.60 60.50 0.6820 59.65 63.6 8.25 7.00

IPLV.SI (kW/Ton) = 0.7455 (COP) = 3.534 IPLV.SI (COP) ((kW/kW)) = 4.718


Certified in accordance with the AHRI Air-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at www.ahridirectory.org

Page 1 of 4
Model: ACEGAFXR360T2ML Date of Selection: 04/04/2024 / 16:05:25
Software Version: 4.06 Application Name: Voltas Chiller Selection Program

Part Load Performance at AHRI condition: Reducing Ambient Temperature(NPLV)

% LOAD AMBIENT CAPACITY INPUT IKW/TR FLOWRATE PRESSURE INLET OUTLET


TEMP. ( °C) (TR) POWER (KW) ( L/s) DROP ( Kpa) TEMP. ( °C) TEMP. ( °C)

100 35.0 354.6 352.8 0.9950 59.65 63.6 12.00 7.00


75 27.0 265.9 213.8 0.8040 59.65 63.6 10.74 7.00
50 19.0 177.3 126.0 0.7110 59.65 63.6 9.50 7.00
25 13.0 88.60 60.50 0.6820 59.65 63.6 8.25 7.00

NPLV.SI (kW/Ton) = 0.7455 (COP) = 3.534 NPLV.SI (COP) ((kW/kW)) = 4.718


Certified in accordance with the AHRI Air-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at www.ahridirectory.org

Chiller Package General Information


Voltage - Phase - Frequency (V-X-Hz) : 400V+/- 10% - 3Ph - 50Hz +/- 3%
Control Voltage (Volts) : 210-240 V
Minimum % capacity reduction :
Chiller Package Size (L x W x H, mm) : 14000 X 2236 X 2885
Approx Refrigerant Charge (kgs.) : 508

BMS Link : With MODBUS or BACNET Protocol


Start Mode : Star-Delta Standard
Shipping Weight (kgs.) : 15050
Operating Weight (kgs.) : 15790

Page 2 of 4
Model: ACEGAFXR360T2ML Date of Selection: 04/04/2024 / 16:05:25
Software Version: 4.06 Application Name: Voltas Chiller Selection Program

Compressor Details
Type : Semi Hermetic Screw
Model : VLAF-12 & VLAF-12
RPM : 2950
Quantity Per Unit : 2
Oil Type : HBR-B08
Oil Charge (Lit), per Comp : 28
Unit Starting Current at 400V (Amps) : 1129
Max. allowable operating current : 312/312
(Amps) at 400V, per Compressor
Evaporator and Condenser Details

Evaporator Condenser
Type Shell and Tube - Flooded
Model J1R-1p 9AV40
Quantity Per Unit no. 2 24
No Of Passes no. 2 0
Water Connection Size NB 150
Additional Features

Part No: ACEGAFXR360T2ML

Page 3 of 4
Model: ACEGAFXR360T2ML Date of Selection: 04/04/2024 / 16:05:25
Software Version: 4.06 Application Name: Voltas Chiller Selection Program

Note: 1. Product development is a continuous process in Voltas, hence specifications and technical data subject to
alterations without notice.
2. Extended Capacity Models are available on request

Page 4 of 4