Hardware Manual ACS800-07 Drives (500 To 2800 KW)
Hardware Manual ACS800-07 Drives (500 To 2800 KW)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
FIRMWARE MANUALS, SUPPLEMENTS AND GUIDES (appropriate documents are included in the delivery) Standard Control Program Firmware Manual 3AFE64527592 (English) System Application Program Firmware Manual 3AFE64670646 (English) Application Program Template Firmware Manual 3AFE64616340 (English) Master/Follower 3AFE64590430 (English) Pump Control Application Program Firmware Manual 3AFE68478952 (English) Extruder Control Program Supplement 3AFE64648543 (English) Centrifuge Control Program Supplement 3AFE64667246 (English) Traverse Control Program Supplement 3AFE64618334 (English) Crane Control Program Firmware Manual 3BSE11179 (English) Adaptive Programming Application Guide 3AFE64527274 (English) OPTION MANUALS (delivered with optional equipment) Fieldbus Adapters, I/O Extension Modules etc.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Update Notice
The notice concerns the following ACS800-07 Drives (500 Code: 3AUA0000059446 Rev A to 2800 kW) Hardware Manuals: Valid: from 01.02.2010 until the release of the next revision of the manual Code Revision Language 3AFE64731165 3AFE64772911 3AFE64772929 3AFE64772937 3AFE64774239 3AFE64772945 3AFE68588235 3AFE64772953 E E E E E E E E English German Spanish Finnish French Italian Russian Swedish EN DE ES FI FR IT RU SV Contents: The headings in this update notice refer to the modified subsections in the original English manual. Each heading also includes a page number and a classifier NEW, CHANGED, or DELETED. The page number refers to the page number in the original English manual. The classifier describes the type of the modification.
Update Notice
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Update Notice
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Update Notice
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
WARNING! The Safe torque off function does not disconnect the voltage of the main and auxiliary circuits from the drive. Therefore maintenance work on electrical parts of the drive or the motor can only be carried out after isolating the drive system from the main supply. Note: The Safe torque off function can be used for stopping the drive in emergency stop situations. In the normal operating mode, use the Stop command instead. If a running drive is stopped by using the function, the drive will trip and stop by coasting. If this is not acceptable, e.g. causes danger, the drive and machinery must be stopped using the appropriate stopping mode before using this function. Note concerning permanent magnet motor drives in case of a multiple IGBT power semiconductor failure: In spite of the activation of the Safe torque off function, the drive system can produce an alignment torque which maximally rotates the motor shaft by 180/p degrees. p denotes the pole pair number. Note: If you add or modify the wiring in the drive safety circuits, ensure that the appropriate standards (e.g. IEC 61800-5-1, EN 62061, EN/ISO 13849-1 and -2) and the ABB guidelines are met.
Update Notice
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Action Close the disconnector and switch the power on. Test the operation of the STO function when the motor is stopped: - Give a stop command for the drive (if running) and wait until the motor shaft is at standstill. - Activate the STO circuit and give a start command for the drive. - Ensure that the motor stays at standstill. - Deactivate the STO circuit. Restart the drive and check that the motor runs normally. Test the operation of the STO function when the motor is running: - Start the drive and ensure that the motor is running. - Activate the STO circuit. - Ensure that the motor stops and the drive trips. - Reset the fault and try to start the drive. - Ensure that the motor stays at standstill. - Deactivate the STO circuit. Restart the drive and check that the motor runs normally.
Additional information
[...]
Cabinets with option +Q968: 0 to 2000 m
Update Notice
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Update Notice
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Safety instructions
What this chapter contains
This chapter contains safety instructions you must follow when installing, operating and servicing the drive. If ignored, physical injury or death may follow, or damage may occur to the drive, the motor or driven equipment. Read the safety instructions before you work on the unit.
Safety instructions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Only qualified electricians are allowed to install and maintain the drive. The main switch on the cabinet door does not remove the voltage from the input busbars of the drive. Before working on the drive, isolate the whole drive from the supply. Never work on the drive, the motor cable or the motor when main power is applied. After switching off the input power, always wait for 5 min to let the intermediate circuit capacitors discharge before you start working on the drive, the motor or the motor cable. Measure the voltage between terminals UDC+ and UDC- (L+ and L) with a multimeter (impedance at least 1 Mohm) to ensure that the drive is discharged before beginning work. Apply temporary grounding before working on the unit. Do not work on the control cables when power is applied to the drive or to the external control circuits. Externally supplied control circuits may cause dangerous voltages to exist inside the drive even when the main power of the drive is switched off. Do not make any insulation or voltage withstand tests on the drive or drive modules. When reconnecting the motor cable, always check that the phase order is correct. When joining shipping splits (if any), check the cable connections at the joints before switching on the supply voltage. Live parts on the inside of the doors are protected against direct contact. Special attention shall be paid when handling metallic shrouds.
Note:
The motor cable terminals on the drive are at a dangerously high voltage when the input power is on, regardless of whether the motor is running or not. The brake control terminals (UDC+, UDC-, R+ and R- terminals) carry a dangerous DC voltage (over 500 V). Depending on the external wiring, dangerous voltages (115 V, 220 V or 230 V) may be present on the relay outputs of the drive system. The Prevention of Unexpected Start function does not remove the voltage from the main and auxiliary circuits.
Safety instructions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
WARNING!
During the installation procedure, the inverter modules may have to be temporarily extracted from the cabinet. The modules have a high centre of gravity. In order to minimise the danger of toppling over, keep the support legs of the modules extended whenever manoeuvring the modules outside the cabinet. Electrically conductive dust inside the unit may cause damage or lead to malfunction. Make sure that dust from drilling does not enter the drive when installing. Fastening the cabinet by riveting or welding is not recommended. However, if welding is necessary, ensure the return wire is properly connected in order not to damage the electronic equipment in the cabinet. Also ensure that welding fumes are not inhaled. Ensure sufficient cooling of the unit. Cooling fans may continue to rotate for a while after the disconnection of the electrical supply. Some parts inside the drive cabinet, such as heatsinks of power semiconductors, remain hot for a while after the disconnection of the electrical supply.
WARNING!
The printed circuit boards contain components sensitive to electrostatic discharge. Wear a grounding wrist band when handling the boards. Do not touch the boards unnecessarily.
Safety instructions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Grounding These instructions are intended for all who are responsible for the grounding of the drive. Incorrect grounding can cause physical injury, death or equipment malfunction and increase electromagnetic interference. WARNING!
Ground the drive, the motor and adjoining equipment to ensure personnel safety in all circumstances, and to reduce electromagnetic emission and pickup. Make sure that grounding conductors are adequately sized as required by safety regulations. In a multiple-drive installation, connect each drive separately to protective earth (PE). Do not install a drive equipped with an EMC (line) filter to an ungrounded power system or a high resistance-grounded (over 30 ohms) power system.
Note:
Power cable shields are suitable for equipment grounding conductors only when adequately sized to meet safety regulations. As the normal leakage current of the drive is higher than 3.5 mA AC or 10 mA DC (stated by EN 50178, 5.2.11.1), a fixed protective earth connection is required.
Handle the fibre optic cables with care. When unplugging optic cables, always grab the connector, not the cable itself. Do not touch the ends of the fibres with bare hands as the fibre is extremely sensitive to dirt. The minimum allowed bend radius is 35 mm (1.4).
Safety instructions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Operation
These warnings are intended for all who plan the operation of the drive or operate the drive. Ignoring the instructions can cause physical injury or death or damage the equipment. WARNING!
If the drive is equipped with an optional brake unit, make sure there are inverters connected to the intermediate circuit before start. As a rule of thumb, the sum capacitance of the inverters connected must be at least 30% of the sum capacitance of all inverters. Close the switch fuses of all parallel-connected inverters before start. Do not open the DC switch fuse of an inverter when the inverter is running.
WARNING! Before adjusting the drive and putting it into service, make sure that the motor and all driven equipment are suitable for operation throughout the speed range provided by the drive. The drive can be adjusted to operate the motor at speeds above and below the speed provided by connecting the motor directly to the power line. Do not activate automatic fault reset functions of the Standard Application Program if dangerous situations can occur. When activated, these functions will reset the drive and resume operation after a fault. Do not control the motor with the disconnecting device (means); instead, use the control panel keys and , or commands via the I/O board of the drive. The maximum allowed number of charging cycles of the DC capacitors (i.e. power-ups by applying power) is five in ten minutes.
Note:
If an external source for start command is selected and it is ON, the drive (with Standard Application Program) will start immediately after fault reset unless the drive is configured for 3-wire (a pulse) start/stop. When the control location is not set to Local (L not shown in the status row of the display), the stop key on the control panel will not stop the drive. To stop the drive using the control panel, press the LOC/REM key and then the stop key .
Safety instructions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
10
Safety instructions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
11
Table of contents
ACS800 Single Drive Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety instructions What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Usage of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Permanent magnet motor drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Application program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Table of contents About this manual What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Common chapters for multiple products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Categorization according to the frame size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation and commissioning flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product and service inquiries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Product training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Providing feedback on ABB Drives manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardware description What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . The ACS800-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabinet line-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Swing-out frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabling direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Single-line circuit diagram of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Door switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Load switch-disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary voltage switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Earthing/Grounding switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other door controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Supply unit control electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 21 21 23 24 25 26 26 26 26 26 26 27 17 17 17 17 17 18 19 19 19 20
Table of contents
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
12
Reading and setting of values (page 1 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28 Reading and setting of values (page 2 of 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 Terminal blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30 Digital input and relay output terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Emergency stop input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 Earth (ground) current function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Power loss ride-through function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Inverter unit control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 Motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 Reduced run capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 Mechanical installation What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39 Moving the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 by crane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 by fork-lift or pallet truck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 on rollers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 Laying the unit on its back . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41 Final placement of the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42 Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 Installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 Fastening the cabinet to the floor (Non-marine units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 Clamping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 Holes inside the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46 Fastening the unit to the floor and wall (Marine units) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47 Joining the shipping splits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 Connecting the DC busbars and the PE busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 DC busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 PE busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Cable duct in the floor below the cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Cooling air intake through bottom of cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52 Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52 Electric welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53 Planning the electrical installation What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Motor selection and compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Protecting the motor insulation and bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 Requirements table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 Permanent magnet synchronous motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 Thermal overload and short-circuit protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 Thermal overload protection of the drive and the input and motor cables . . . . . . . . . . . . . . .59
Table of contents
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
13
Thermal overload protection of the motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protection against short-circuit in the motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protection against short-circuit inside the drive or in the supply cable . . . . . . . . . . . . . . . . . Earth fault (Ground fault) protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Emergency stop devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Restarting after an emergency stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Prevention of unexpected start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alternative power cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor cable shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Additional US requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Conduit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Armored cable / shielded power cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power factor compensation capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Equipment connected to the motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation of safety switches, contactors, connection boxes, etc. . . . . . . . . . . . . . . . . . . . . Bypass connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Before opening an output contactor (in DTC motor control mode) . . . . . . . . . . . . . . . . . . . . Relay output contacts and inductive loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relay cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control panel cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Coaxial cable (for use with Advant Controllers AC 80/AC 800) . . . . . . . . . . . . . . . . . . . . . . . Connection of a motor temperature sensor to the drive I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation sites above 2000 metres (6562 feet) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Routing the cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control cable ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical installation What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Before installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor and motor cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the earth fault (ground fault) trip level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grounded systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input power connection Units without load switch-disconnector or air circuit breaker . . . . . . . . . Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-pulse connection, two supply modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-pulse connection, two supply modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Use of the dual-cable screw lug connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removal of the dual-cable screw lug connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input power connection Units with load switch-disconnector or air circuit breaker . . . . . . . . . . . Connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-pulse connection, two supply modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-pulse connection, two supply modules in parallel . . . . . . . . . . . . . . . . . . . . . . . . . .
60 60 60 60 61 61 61 61 61 63 63 63 64 64 65 65 65 65 65 66 67 67 67 67 68 68 68 69
71 71 71 71 72 72 72 72 73 73 73 74 75 76 76 77 77 77 78
Table of contents
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
14
Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79 Motor connection Units without common motor terminal cubicle . . . . . . . . . . . . . . . . . . . . . . . . .80 Output busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82 Motor connection Units with common motor terminal cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . .84 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84 Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84 Control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 Drive control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 Supply unit control connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85 Connection procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86 Installation of optional modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 Cabling of I/O and fieldbus modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 Cabling of pulse encoder interface module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 Fibre optic link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88 Connections and tap settings of the auxiliary voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . .89 Installation of brake resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89 Motor control and I/O board (RMIO) What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 To which products this chapter applies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 Note on cabinet-installed ACS800 drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 Note on terminal labelling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 Note on external power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92 Parameter settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92 External control connections (non-US) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93 External control connections (US) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94 RMIO board specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 Constant voltage output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 Auxiliary power output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 Relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96 DDCS fibre optic link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96 24 VDC power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96 Installation checklist and start-up Installation checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99 Start-up procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Basic checks with no voltage connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Connecting voltage to input terminals and auxiliary circuit . . . . . . . . . . . . . . . . . . . . . . . . . .100 Starting the supply unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101 Checks with the supply unit running . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101 Application program set-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101 On-load checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101
Table of contents
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
Maintenance What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replacing the PPCS branching unit (APBU-xx) memory backup battery . . . . . . . . . . . . . . . . . . . Checking and replacing the air filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cooling fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power module cooling fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Supply module fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inverter module fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control and I/O cubicle cooling fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Air circuit breaker cubicle fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP54 (UL type 12) fan replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Heatsinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capacitor replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other maintenance actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power module replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault tracing What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Supply unit status, fault and warning LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113 Other LEDs of the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 Technical data What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ACS800-07 frame sizes and power module types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Internal AC fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC fuses at inverter module input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuses for main circuit voltage measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC fuses for the DSU module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tightening torques for power connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 117 118 118 118 118 119 120 121 121 121 122 124 125 126 126 126 127 127 127 103 103 104 105 106 106 107 107 107 108 109 110 110 112 112 112 112 112 112
Table of contents
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
16
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128 Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128 Compliance with the EN 61800-3 + Amendment A11 (2000) . . . . . . . . . . . . . . . . . . . . . . . .128 First environment (restricted distribution) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128 Second environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129 Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129 C-tick marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130 Compliance with IEC 61800-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130 First environment (restricted distribution) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130 Second environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131 Dimensions Cabinet line-ups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .133 Frame size 1D4 + 2R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138 Frame size 1D4 + 2R8i (with load switch-disconnector) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141 Frame size 1D4 + 2R8i (with top entry/exit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147 Frame size 2D4 + 2R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .150 Frame size 2D4 + 2R8i (with load switch-disconnector) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153 Frame size 2D4 + 3R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .156 Frame size 2D4 + 3R8i (with load switch-disconnector) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .159 Frame size 2D4 + 3R8i (with air circuit breaker) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163 Frame size 3D4 + 4R8i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .167 Frame size 3D4 + 4R8i (with load switch-disconnector) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .170 Frame size 3D4 + 4R8i (with air circuit breaker) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .174 Common motor terminal cubicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178 300 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178 400 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179 600 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .180 Resistor braking What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181 Resistor braking options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181 Chopper/Resistor combinations Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182 Brake resistors Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182 Verifying the capacity of the braking equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183 Custom resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183 Calculating the maximum braking power (Pbr) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184 Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184 Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184 Example 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185 Custom resistor installation and wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .186 Brake circuit commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .187
Table of contents
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
17
Target audience
This manual is intended for people who plan the installation, install, commission, use and service the drive. Read the manual before working on the drive. The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. The manual is written for readers worldwide. Both SI and imperial units are shown. Special US instructions for installations within the United States that must be installed per the National Electrical Code and local codes are marked with (US).
Contents
The chapters of this manual are briefly described below. Safety instructions gives safety instructions for the installation, commissioning, operation and maintenance of the drive. About this manual introduces this manual. Hardware description describes the drive. Mechanical installation instructs how to move, place and mount the drive. Planning the electrical installation provides advice on motor and cable selection, the protective functions of the drive, and cable routing. Electrical installation describes the cabling and wiring of the drive.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
18
Motor control and I/O board (RMIO) shows external control connections to the motor control and I/O board and its specifications. Installation checklist and start-up helps in checking the mechanical and electrical installation of the drive. Maintenance contains preventive maintenance instructions. Fault tracing contains troubleshooting instructions. Technical data contains the technical specifications of the drive, e.g. ratings, frame sizes and technical requirements, provisions for fulfilling the requirements for CE and other markings and warranty policy. Dimensions contains information on the dimensions of the drive. Resistor braking describes how to select, protect and wire optional brake choppers and resistors.
Check the ambient conditions, ratings, required Planning the electrical installation cooling air flow, input power connection, compatibility Option manuals (if optional equipment is of the motor, motor connection, and other technical included) data. Select the cables.
Unpack and check the units. Check the type code indicated by the type designation label with the original order. If the drive is about to be connected to an IT (ungrounded) system, check that the drive is not equipped with EMC/RFI filtering +E202. Check that all necessary optional modules and equipment are present and correct.
Mechanical installation Hardware description For instructions on how to disconnect the EMC/ RFI filtering, contact your local ABB representative. If the converter has been non-operational for more than one year, the converter DC link capacitors need to be reformed. Contact your local ABB representative for more information.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
19
Task
See
Connect the power cables. Connect the control and the auxiliary control cables.
Mechanical installation, Planning the electrical installation, Electrical installation, Resistor braking (optional)
Resistor braking
Product training
For information on ABB product training, navigate to ABB website and select Drives Training courses.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
20
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
21
Hardware description
What this chapter contains
This chapter describes the construction of the drive in short.
The ACS800-07
The ACS800-07 is a cabinet-mounted drive for controlling AC motors. Cabinet line-up The drive consists of several cubicles that contain the supply and motor terminals, 1 to 4 diode supply module(s), 2 to 6 inverter modules, and optional equipment. The actual arrangement of the cubicles vary from type to type and the selected options. See the chapter Dimensions for the different line-up variations. The picture below shows the main components of a frame 1D4 + 2R8i drive.
No. 1 2 Description Supply (input) cable lead-throughs. Top entry optional. Supply module. Input terminals (behind module). Input cables connect here if a load switch-disconnector cubicle is not present. Chassis socket for quick supply module connection (behind module). Supply module switch-disconnector. Not present if the drive is equipped with an optional load switch-disconnector cubicle. Supply unit control board (DSSB; mounted sideways). Contains an actual value display and status LEDs. Inverter DC fuses. Inverter modules. Chassis socket for inverter module output connection (behind each module). Output terminals (behind each module). Motor cables connect here if a common motor terminal cubicle is not present. Motor (output) cable lead-throughs. Not used if optional common motor terminal cubicle is present. Swing-out frame. Contains the drive control unit with I/O terminals, and provides space for standard and optional electrical equipment. Auxiliary voltage transformer (accessible by opening the swing-out frame). Auxiliary voltage switch with fuses.
14 6 7
3 4 5
8 4 12 3 9 2 10 9 10
7 8 9 10
11 12
13 1 11 11
13 14
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
22
The following drawing represents a 2D4 + 2R8i drive with optional load switchdisconnector.
17 9
10
8 11 7 7
15 3 6 13 2 13 12 12
16 1 14 14
No. 1 2 3 4
Description Supply (input) cable lead-throughs. Top entry optional. Input busbars. Load switch-disconnector. Earthing/Grounding switch (optional).
No. 10 11 12 13
Description Inverter DC fuses. Inverter modules. Chassis socket for inverter module output connection (behind each module). Output terminals (behind each module). Motor cables connect here if a common motor terminal cubicle is not present. Motor (output) cable lead-throughs. Not used if optional common motor terminal cubicle is present. Swing-out frame. Contains the drive control unit with I/O terminals, and provides space for standard and optional electrical equipment. Auxiliary voltage transformer (accessible by opening the swing-out frame). Auxiliary voltage switch.
5 6
AC fuses. Only present if the drive is equipped with a load switch-disconnector or air circuit breaker. Supply modules.
14 15
7 8
Chassis socket for quick supply module connection (behind each module). Supply module switch-disconnectors (coupled to an operating handle on the cabinet door). Not present if the drive is equipped with a load switch-disconnector or air circuit breaker. Supply unit control board (DSSB; mounted sideways). Contains an actual value display and status LEDs.
16 17
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
23
Swing-out frame The swing-out frame inside the control and I/O cubicle provides space for the control electronics of the drive, I/O terminal blocks, and optional electrical equipment. The lead-throughs for I/O cables, the auxiliary voltage transformer, and further space for additional equipment are available behind the frame. The frame can be opened by removing the two locking screws (arrowed in the picture below) and moving the swing-out frame aside. (Depending on selected options, actual equipment of the drive may differ from what is depicted below.)
Remove screws (arrowed) to release swing-out frame Drive control unit (RDCU) with I/O terminal blocks Space for optional terminal block X2 Terminal block X1 I/O cable entry (into swing-out frame) Mounting rails for additional equipment
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
24
Cabling direction The drawing below shows the available power cabling directions of the drive. Note that the desired cabling direction must be specified on ordering.
4 3 3 6 6 8
1 2 3 Description Main supply Bottom entry at each supply module (without load switch-disconnector or air breaker) Main supply Bottom entry with load switch-disconnector or air circuit breaker Main supply Top entry at each supply module (without load switch-disconnector or air circuit breaker) (not for IP54) Main supply Top entry with load switch-disconnector or air circuit breaker Motor output Bottom exit at each inverter module (without common motor terminal cubicle) Motor output Top exit at each inverter module (without common motor terminal cubicle). Added depth: 130 mm Motor output Bottom exit with common motor terminal cubicle Motor output Top exit with common motor terminal cubicle Load switch-disconnector or air circuit breaker cubicle (optional) Control, I/O and supply cubicle Inverter unit cubicle Common motor terminal cubicle (optional)
4 5 6 7
5 5 2 1 1
8 A B C D
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
DC bus
400 VAC
400 VAC
M M
230/115 VAC
Main Supply
M 3~
+24 VDC 400 VAC 230/115 VAC Ground fault supervision Voltage display of DSSB Motor fan supply
Notes: The diagram represents a frame 2D4 + 2R8i drive with 2 brake chopper/resistor units (optional), and without load switch-disconnector, air circuit breaker or common motor output cubicles. The supply modules are not equipped with internal contactors if an air circuit breaker is ordered. The supply modules are not equipped with internal switch-disconnectors if a load switch-disconnector or air circuit breaker is ordered.
25
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
26
Controls
Door switches Load switch-disconnector The drive has a load switch-disconnector handle. In units without an optional load switch-disconnector (+F253), the handle operates the internal switch-disconnector contained within each supply module. WARNING! The load switch-disconnector does not switch off the auxiliary voltages inside the cabinet. In units without option +F253, the switch-disconnector does not switch off the voltage at the input terminals of the supply module(s). Note: On units without the line contactor option (+F250) and the load switchdisconnector option (+F253), the supply unit will start rectifying as soon as the switch-disconnector(s) within the supply module(s) is closed. Auxiliary voltage switch The auxiliary voltage switch controls the voltage supply to the auxiliary voltage transformer. Earthing/Grounding switch An earthing/grounding switch for temporary grounding is optionally available. Other door controls The following switches are mounted on the door of the control and I/O cubicle:
Operating switch (units with main contactors only) START position closes the main contactors and the supply unit starts rectifying. In the OFF position, the main contactors are open.
Auxiliary voltage switch-disconnector (not shown) Controls the power supply to the auxiliary voltage transformers, ground fault supervision, motor fan supply, and the voltage display of the DSSB board.
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
27
Supply unit control electronics The supply module(s) is controlled by the DSSB (Diode supply system board), located inside the control and I/O cubicle. The DSSB is connected to and powered from the supply module(s) via the quick connectors at the back of the modules. The DSSB contains the following LEDs:
Displayed actual value - Three phase voltages - Six phase currents - DC link voltage - DC link current - DC link power (default) Display selection keys
READY LED
DSU_DISPLAY.TIF
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
28
Display Mode
autoexit (2 s.)
Press up key Press down key Press up and down keys simultaneously
autoexit (2s.) Direction of display change Setting accepted 1) For more information, see section Power loss ride-through function on page 34. 2) For more information, see section Earth (ground) current function on page 33. Display Mode
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
29
EFC peak 4)
module count 5)
Display Mode
LED on LED off 3) 4) 5) 6) No. of modules (1...5). DSSB needs the value for scaling the current output signal connected to current meters on cabinet door (optional equipment). Displays earth current peak value Displays module count set in AOS Displays VAC phase balance
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
30
Terminal blocks
X500 X2 1 2 X3 1 2 3 X4 1 2 3 X5 X6, X7 X8 X9 Ribbon cable to DSCB board via module quick connector Measurement for actual value display (factory-wired) DC+ DCMeasurement for actual value display (factory-wired) U V W -24V +24V Ground Phase voltage Phase voltage Phase voltage Power supply output: +24 VDC / max. 3 A and -24 VDC / max. 0.5 A (or 48 VDC / max 0.5 A) Note: Terminals can also be used to supply DSU control boards externally during input power break. Use two 24 V / 1 A floating power supplies. Connect between +24V & Ground and Ground & -24V. Intermediate circuit voltage (+ and - busbars)
24 V (or 48 V) output, short-circuit protected, live when AC power input of DSU is live
Remote digital inputs See Digital input and relay output terminals on page 31. Relay outputs See Digital input and relay output terminals on page 31. Emergency stop input See Emergency stop input on page 32. Phase current output for an external display device (e.g. a meter on the cabinet door). For scaling, see Reading and setting of values (page 2 of 2) on page 29. Use single phase meters. Connect the meter between the current output terminal and ground (cabinet frame). Type tested and used by ABB: BQ307 by Iskra (www.iskra-mis.si). U1.1 V1.1 W1.1 U1.2 V1.2 W1.2 Phase current value as a 01 mA signal (= 0nominal DSU current) Phase current value as a 01 mA signal (= 0nominal DSU current) Phase current value as a 01 mA signal (= 0nominal DSU current) Phase current value as a 01 mA signal (= 0nominal DSU current) Phase current value as a 01 mA signal (= 0nominal DSU current) Phase current value as a 01 mA signal (= 0nominal DSU current)
1 2 3 4 5 6 X10
Local digital inputs See Digital input and relay output terminals on page 31.
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
31
Digital input and relay output terminals The DSU can be controlled through two control interfaces: local and remote. The operation switches placed on the cabinet door are connected to the local control interface. The remote control interface can be used in parallel when control by other external devices is needed.
S11 1 3 S11
1 0
0 1 START 3 4
2 4
Local digital inputs START 0 -> 1: DSU closes main contactors and starts rectifying. Note: Local ON input must be switched on. ON +24 V RESET 1: DSU is rectifying.1) 0: DSU stops rectifying and opens contactors. +24 VDC 0 -> 1: Reset
2 3
S21
X1 13
S21 13 14
4 5
X1
RESET LED Ground for reset button LED +24 V +24 VDC
0 1
X2
X2 14
6 X5 1-2
Digital input data Input voltage: 1 = 1548 VDC or 15230 VAC. All inputs must be of the same type (AC or DC). Internal connection:
DI
Relay output data Contact rating: 230 VAC / 1 A continuous Internal connection: RO
Remote digital inputs 2) ON 1: DSU is rectifying.1) 0: DSU stops rectifying and opens contactors. Note: If start command was given through local START input, DSU stops only after local ON input is switched off. START 0 -> 1: DSU closes main contactors and starts rectifying. Note: Local and remote ON inputs must be switched on. RESET 0 -> 1: Reset EXT.FAULT 1: External fault. DSU trips. 0: No external fault. Relay outputs 2) RO1 Off: Fault RO2 On: Running Relay outputs 2) RO3 Overtemperature warning RO4 Off: Earth (ground) fault detected RO5 Off: Emergency stop acknowledgement to inverter
1) After the power switch-on, the DSU first charges the contactor control capacitors (~ 3 s at first start) and checks the fault status. DSU starts rectifying only after the contactors are closed by the START input. 2) These DSSB board terminals are wired to a separate terminal block to which the user connections are to be made. See the circuit diagrams delivered with the unit.
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
32
Emergency stop input The DSSB board has a built-in logic that fulfils the emergency stop requirements according to IEC/EN60204-1 / Category 0 (Immediate removal of power) provided that: the Diode Supply Unit (DSU) is equipped with optional main contactors, and an emergency stop button is wired to the emergency stop input of the DSU. See the figure below for connection to the DSSB board. When the emergency stop is activated, the DSU stops and opens the main contactors. Normal operation resumes after the emergency stop is deactivated and the DSU is reset. Note: Emergency stop according to category 0 and category 1 (controlled emergency stop) are available as factory-installed options. The category 1 option requires additional wirings that are not visible in the figure below. See the circuit diagrams delivered with the unit for more information.
Emergency stop button wired to DSSB board DSSB board terminals X4 1 2 3 X8 1 2 -24V +24V Ground -24 VDC +24 VDC Ground
Note: The DSSB board terminals are wired to a separate terminal block to which the user connections are made. See circuit diagrams delivered with the unit. Additional emergency stop buttons can be connected in series.
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
33
Earth (ground) current function The control board (DSSB) measures the input currents of the diode supply unit. The earth current function constantly monitors the sum of the phase currents. The chart below describes the operation.
START
No
Yes
No
Yes
No
Yes
DSU trips to a fault, illuminates earth fault LED and energizes relay output (earth current fault).
DSU continues operation and energizes relay output (earth current warning).
1) Function is inactive when the wake up level is set to NONE (default setting). See page 28. 2) See page 28 for setting/checking the wake up level of the earth current function. 3) See page 28 for the fault trip selection (ON = fault trip, OFF = warning).
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
34
Power loss ride-through function The power loss ride-through function keeps the supply unit operative over an unexpected input power break. The user can activate the function by setting the power loss ride-through delay with the buttons on the DSSB board. Note: Units with an air circuit breaker require an external UPS for the function to be available. The table below describes the operation of the function.
Duration of the break Shorter than power loss ridethrough time. What happens during the break If the DC voltage drops less than 30%, the diode bridge stays in normal operating mode, and the supply unit keeps the internal contactors energised. If the DC voltage drops more than 30%, the diode bridge switches into charging mode and further into stand-by (only the DSSB board is kept live by a backup capacitor), relay output RO2 (Running) de-energises, and the internal contactors open. Longer than power loss ridethrough time. The supply unit stops and opens the main contactors. The supply unit wakes up automatically and closes the internal contactors, charges the DC bus, starts rectifying, and energises relay output RO2. Operation continues only after manual reset and restart. What happens after the break The supply unit resumes rectifying automatically.
The delay setting range is 0 to 40 seconds. For instructions on the setting, see page 28. Inverter unit control The inverter unit is controlled by an RDCU drive control unit located in the swing-out frame. The RDCU is connected to the inverter modules by a fibre optic link, distributed through an optical branching unit. In the inverter modules, the optic link connects to the AINT board, the terminals of which are accessible through a hole on the front panel of the module. A control panel (type CDP-312R) is installed on the door of the drive. The CDP-312R is the user interface of the inverters of the drive, providing the essential controls such as Start/Stop/Direction/Reset/Reference, and the parameter settings for the drive application program. See the Firmware Manual for further information.
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
35
Control panel
Optional module 1: I/O extension (RAIO, RDIO), pulse encoder interface (RTAC), or fieldbus adapter (e.g. RMBA, RDNA, RPBA)
Optional module 2: I/O extension (RAIO, RDIO) or pulse encoder interface (RTAC) Optional module 3: DDCS communication option (RDCO-01, RDCO-02 or RDCO-03)
To motor
Motor control The motor control is based on the Direct Torque Control (DTC) method. Two phase currents and DC link voltage are measured and used for the control. The third phase current is measured for earth fault protection. Reduced run capability If one of parallel-connected supply or inverter modules must be taken out of the cabinet for service, it is possible to continue operation using the remaining modules, albeit at reduced power. For directions, contact your local ABB representative.
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
36
Type code
The type code of the drive is indicated on the type designation label, attached on the supply cubicle door. The type code contains information on the specifications and configuration of the drive. The first digits from left express the basic configuration (e.g. ACS800-07-0610-3). The optional selections are given thereafter, separated by + signs (e.g. +E202). The main selections are described below. Note: The information below is for quick reference only and does not contain all conditions and details. For more information, refer to ACS800 Ordering Information (code: 64556568), available through ABB representatives.
Selection Product series Type Alternatives ACS800 product series 07 = cabinet-mounted When no options are selected: IP21 (UL Type 1), main switch/ disconnector(s), 230 V auxiliary voltage, du/dt filtering (+E205), common mode filtering (CMF) (+E208), EMC/RFI filtering for second environment (+E210), Standard Application Program, bottom entry/exit of cables, coated circuit boards, set of English manuals. Refer to Technical data: Ratings. 3 = 380/400/415 VAC 5 = 380/400/415/440/460/480/500 VAC 7 = 525/575/600/690 VAC Refer to ACS800 Ordering Information (3AFY64556568 [English]).
Size Voltage range (nominal rating in bold) + options I/O options Fieldbus adapter Application program Degree of protection
Construction
Filters
Resistor braking
B053 = IP22 (UL Type 1) B054 = IP42 (UL Type 1) B055 = IP54 (UL Type 12) (Not available with +C134) B059 = IP54R (with connection to air outlet duct) C121 = Marine construction (reinforced mechanical parts and fastening, marking of conductors [A1], door handles, self-extinctive materials) C129 = UL Listed (115 V AC auxiliary voltage, cable conduit entries, all components UL listed/recognized, max. supply voltage 600 V; +F253, +F260 and top entry of cables are standard) C134 = CSA Approved (as +C129, with CSA approved components) E202 = EMC/RFI filtering for first environment TN (grounded) system, restricted (A-limits). Only for 6-pulse ACS800-07-0610-3 and -0760-5. Requires +F253 and +F260. E206 = Sine output filters (Not available with +C121, +C129 or +C134) Note: du/dt filtering (+E205), common mode filtering (CMF) (+E208), and EMC/RFI filtering for second environment (+E210) are standard equipment. D150 = brake choppers D151 = brake resistors (not available in IP54 or IP54R)
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
37
Alternatives F250+Q951 = line contactor + emergency stop (Category 0) F250+Q952 = line contactor + emergency stop (Category 1) F253+F260 = aR AC fuses + load switch-disconnector (6-pulse) (Load switch-disconnectors in DSU modules removed) A004+F253+F260 = aR AC fuses + load switch-disconnector (12-pulse) (Load switch-disconnectors in supply modules removed) (with +C129 and +C134, second cubicle for load switch-disconnector added) F255+F260+Q951 = air circuit breaker + emergency stop (Category 0) (6-pulse only) (Not available with frame 1D4 + nR8i) (Load switchdisconnectors and main contactors in supply modules removed) F255+F260+Q952 = air circuit breaker + emergency stop (Category 1) (6-pulse only) (Not available with frame 1D4 + nR8i) (Load switchdisconnectors and main contactors in supply modules removed) F259 = earthing switch (only with +F253 or +F255) (Not available with +C129 or +C134) Cabling H351 = top entry (IP54 and IP54R require +F253 or +F255) H353 = top exit H358 = US/UK gland/conduit plate (standard with +C129 and +C134) H359 = common motor terminal cubicle Auxiliary voltage G304 = 115 VAC auxiliary voltage (standard with +C129 and +C134) Cabinet options G300 = cabinet heaters (external supply) (Not available with +C129 or +C134) G313 = motor heater output (external supply) G307 = terminals for external control voltage (UPS) G317 = busbar supply conductors (6-pulse only) (Requires +F253 or +F255) G330 = halogen-free wiring and materials (Not available with +C129 or +C134) Language of manuals Rxxx Refer to ACS800 Ordering Information (3AFY64556568 [English]). Starter of auxiliary motor M602 = 2.5 4 A (1, 2 or 4 pcs) fan M603 = 4 6.3 A (1, 2 or 4 pcs) M604 = 6.3 10 A (1, 2 or 4 pcs) M605 = 10 16 A (1 or 2 pcs) M606 = 16 25 A (1 pc) Safety features Q950 = prevention of unexpected start (Category 3) Q954 = earth fault monitoring (IT [ungrounded] system) Q959 = red-coloured trip pushbutton for external breaker Special P902 = customised (described in Technical appendix on ordering) P904 = extended warranty P913 = special colour
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
38
Hardware description
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
39
Mechanical installation
What this chapter contains
This chapter describes the mechanical installation procedure of the drive.
General
See chapter Technical data for allowable operating conditions and requirements for free space around the unit. The unit should be installed in an upright vertical position. The floor that the unit is installed on should be of non-flammable material, as smooth as possible, and strong enough to support the weight of the unit. The floor flatness must be checked with a spirit level before the installation of the cabinets into their final position. The maximum allowed deviation from the surface level is 5 mm in every 3 metres. The installation site should be levelled, if necessary, as the cabinet is not equipped with adjustable feet. The wall behind the unit should be of non-flammable material. Provide the drive with the amount of fresh cooling air given in Technical data. Note: Very wide cabinet line-ups are delivered as shipping splits.
Required tools
The tools required for moving the unit to its final position, fastening it to the floor and tightening the connections are listed below. crane, fork-lift or pallet truck (check load capacity!); iron bar, jack and rollers Pozidrive and Torx (2.56 mm) screwdrivers for the tightening of the frame screws torque wrench set of wrenches or sockets for joining shipping splits.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
40
IP54 units Allowed minimum height of lifting ropes or slings for IP54 units is 2 metres.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
41
The centre of gravity may be quite high. Be therefore careful when transporting the unit. Tilting the cabinets must be avoided. The units are to be moved only in the upright position. If using a pallet truck, check its load capacity before attempting to move the unit.
Support
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
42
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
43
Before installation
Delivery check The drive delivery contains: drive cabinet line-up optional modules (if ordered) installed into the control rack at the factory ramp for extracting supply and inverter modules from the cabinet hardware manual appropriate firmware manuals and guides optional module manuals delivery documents. Check that there are no signs of damage. Before attempting installation and operation, check the information on the type designation label of the drive to verify that the unit is of the correct type. The label includes an IEC and NEMA rating, C-UL US, and CSA markings, a type code and a serial number, which allow individual recognition of each unit. The first digit of the serial number refers to the manufacturing plant. The next four digits refer to the units manufacturing year and week respectively. The remaining digits complete the serial number so that there are no two units with the same serial number. The type designation label is located on the supply unit door.
Each power module (i.e. supply and inverter module) is also individually labelled.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
44
Installation procedure
1
See detailed instructions in the following few pages. (1) The cabinet can be installed with its back against a wall, or back-to-back with another unit. Fasten the unit (or first shipping split) to the floor with fastening clamps or through the holes inside the cabinet. See section Fastening the cabinet to the floor (Non-marine units). With marine versions, fasten the unit (or first shipping split) to the floor and wall/roof as described in section Fastening the unit to the floor and wall (Marine units). Note: A clearance of 400 mm minimum above the basic roof level of the cabinet (see inset on left) is required for cooling. Note: Leave some space at the left-hand and right-hand sides of the line-up (A) to allow the doors to open sufficiently. Note: Any height adjustment must be done before fastening the units or shipping splits together. Height adjustment can be done by using metal shims between the bottom frame and floor. (2) Remove the lifting bars (if present). In marine units, also replace the lifting lugs with L-profiles (see below). Use the original bolts to block any unused holes. (3) If the line-up consists of shipping splits, fasten the first split to the second. Each shipping split includes a joining cubicle where the busbars connect to the next split. (4) Fasten the second shipping split to the floor. (5) Join the DC busbars and the PE busbars. (6) Repeat steps (2) to (5) for the remaining shipping splits.
Top clearances
> 320 mm (12.3) for fan replacement > 400 mm (15.75)
IP22/42
IP54
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
45
Distances between slots Cubicle Width (mm) 300 400 Distance in millimetres and (inches)
Cabinet frame
150 (5.9) 250 (9.85) 450 (17.7) 550 (21.65) 650 (25.6)
Cabinet frame
Cabinet top Fastening the cabinet at the top with L-brackets (side view)
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
46
Holes inside the cabinet The cabinet can be fastened to the floor using the fastening holes inside the cabinet, if they are accessible. The recommended maximum distance between the fastening points is 800 mm (31.5). If there is not enough working space behind the cabinet for mounting, replace the lifting lugs at the top with L-brackets (not included) and fasten the top of the cabinet to the wall.
Fastening holes inside the cabinet (arrowed)
25 mm (0.985)
Cabinet top Fastening the cabinet at the top with L-brackets (side view)
Distances between fastening holes Bolt size: M10 to M12 (3/8 to 1/2). Cubicle Width Distance between holes Outer 31 mm (1.22) 150 mm (5.9) 250 (9.85) 450 (17.7) 550 (21.65) 650 (25.6)
Added width: Side panels of the cabinet: 15 mm (0.6) Back panel of the cabinet: 10 mm (0.4) Gap between cubicles (mm): IP 20...42 IP 54
0.5
(0.02)
(0.04)
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
47
Bolt the unit to the floor through the holes in each flat bar at the base of the cabinet using M10 or M12 screws. If there is not enough room behind the cabinet for installation, clamp the rear ends of the flat bars as shown in figure (2). Fasten the top of the cabinet to the rear wall and/or roof using brackets.
Use M10 or M12 screws; welding is not recommended (see section Electric welding below).
2
Back panel of cabinet Flat bars at base of cabinet
3
L-bracket M16 bolt
Clamps
Cabinet
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
48
Procedure
Fasten the front post of the joining section with 7 screws to the front frame post of the next cubicle.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
49
Remove any intermediate or partitioning plates covering the rear posts of the joining cubicle.
Partitioning plate
Intermediate plate
Fasten the rear post of the joining section with seven screws (below the busbar joining part) to the rear post of the next cubicle. Replace all partitioning plates in the upper part of it after connecting the DC busbars (see section Connecting the DC busbars and the PE busbar). Connecting the DC busbars and the PE busbar Horizontal main DC busbars and the PE busbar are connected from the front of the joining cubicle. All necessary materials are located in the joining cubicle. Remove the front metal partitioning plate located in the busbar joining cubicle. Unscrew the bolts of the joint pieces. Connect the busbars with the joint pieces (see figure below). For aluminium busbars, suitable anti-oxidant joint compound must be used to avoid corrosion and to ensure good electrical connection. The oxide layer must be scrubbed off from the joints before applying the compound. Refit all shrouds for safety of personnel.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
50
1 1 1 1
1 Joint pieces
PE busbar The PE busbar runs continuously through the line-up near the floor at the back. The connection is shown below. No separate nuts are needed.
Top view PE busbar
Tighten the screws to 5570 Nm (4050 ft.-lbs.) Shipping split A Shipping split B
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
51
Miscellaneous
Cable duct in the floor below the cabinet A cable duct can be constructed below the 400 mm wide middle part of the cabinet. The cabinet weight lies on the two 100 mm wide transverse sections which the floor must carry.
Viewed from above Side view
Prevent the cooling air flow from the cable duct to the cabinet by bottom plates. To ensure the degree of protection for the cabinet use the original bottom plates delivered with the unit. With user-defined cable entries, take care of the degree of protection, fire protection and EMC compliance.
Cables
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
52
Cooling air intake through bottom of cabinet Units with air intake through the bottom of the cabinet (optional feature) are intended for installation on an air duct in the floor. The required air inlets in the floor are as listed below. Refer also to the dimensional drawings delivered with the unit. for DSU supply cubicles: w 505 mm, where w equals cubicle width 50 mm for ISU supply cubicles, inverter unit cubicles, control cubicles, switch/breaker cubicles: w 400 mm, where w equals cubicle width 50 mm w 130 mm at the back of the cabinet line-up, where w equals the total width of adjacent cubicles with air inlets. This area may or may not be consistent through the width of the whole line-up. Example
Diode supply cubicle Cubicle width: 700 mm Air inlet size: 650 505 mm
Load switch-disconnector cubicle Cubicle width: 400 mm Air inlet size: 350 400 mm
Inverter cubicle Cubicle width: 600 mm Air inlet size: 550 400 mm
Notes: The plinth of the cabinet must be supported all round. The air duct must be able to supply a sufficient volume of cooling air. The minimum air flow values are given in the Technical data section of the Hardware Manual. The cubicles of diode supply units require a larger air inlet area than other cubicles. Some cubicles (mainly those without active, heat-generating components) require no air inlet.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
53
Electric welding It is not recommended to fasten the cabinet by welding. Cabinets without flat bars at the base Connect the return conductor of the welding equipment to the cabinet frame at the bottom within 0.5 metres of the welding point. Cabinets with flat bars at the base Weld only the flat bar under the cabinet, never the cabinet frame itself. Clamp the welding electrode onto the flat bar about to be welded or onto the floor within 0.5 metres of the welding point. WARNING! If the welding return wire is connected improperly, the welding circuit may damage electronic circuits in the cabinet. The thickness of the zinc coating of the cabinet frame is 100 to 200 micrometres; on the flat bars the coating is approximately 20 micrometres. Ensure that the welding fumes are not inhaled.
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
54
Mechanical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
55
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
56
4. Consult the motor manufacturer before using a motor in a drive system where the motor nominal voltage differs from the AC power source voltage. 5. Ensure that the motor insulation system withstands the maximum peak voltage in the motor terminals. See the Requirements table below for the required motor insulation system and drive filtering. Example: When the supply voltage is 440 V and the drive is operating in motor mode only, the maximum peak voltage in the motor terminals can be approximated as follows: 440 V 1.35 2 = 1190 V. Check that the motor insulation system withstands this voltage. Protecting the motor insulation and bearings The output of the drive comprises regardless of output frequency pulses of approximately 1.35 times the equivalent mains network voltage with a very short rise time. This is the case with all drives employing modern IGBT inverter technology. The voltage of the pulses can be almost double at the motor terminals, depending on the attenuation and reflection properties of the motor cable and the terminals. This in turn can cause additional stress on the motor and motor cable insulation. Modern variable speed drives with their fast rising voltage pulses and high switching frequencies can cause current pulses that flow through the motor bearings, which can gradually erode the bearing races and rolling elements. The stress on motor insulation can be avoided by using optional ABB du/dt filters. du/dt filters also reduce bearing currents. To avoid damage to motor bearings, the cables must be selected and installed according to the instructions given in this manual. In addition, insulated N-end (nondriven end) bearings and output filters from ABB must be used according to the following table. Two types of filters are used individually or in combinations: du/dt filtering (protects motor insulation system and reduces bearing currents). common mode filtering (CMF) (mainly reduces bearing currents).
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
57
Requirements table The following table shows how to select the motor insulation system and when an optional ABB du/dt filter, insulated N-end (non-driven end) motor bearings and ABB common mode filters are required. The motor manufacturer should be consulted regarding the construction of the motor insulation and additional requirements for explosion-safe (EX) motors. Failure of the motor to fulfil the following requirements or improper installation may shorten motor life or damage the motor bearings.
Motor type Manufacturer Nominal mains voltage (AC line voltage) Requirement for Motor insulation system ABB du/dt filter, insulated N-end bearing and ABB common mode filter PN < 100 kW and frame size < IEC 315 PN < 134 HP and frame size < NEMA 500 Randomwound M2_ and M3_ UN < 500 V Standard or Reinforced 600 V < UN < 690 V Reinforced Form-wound HX_ and AM_ 380 V < UN < 690 V Standard + du/dt n.a. +N + du/dt + N + N + CMF + N + CMF + du/dt + N + CMF PN < 500 kW: + N + CMF PN > 500 kW: + N + CMF + du/dt Old* formwound HX_ and modular Randomwound HX_ and AM_ ** N O N A B B or Reinforced: LL = 1600 V, 0.2 s rise time 500 V < UN < 600 V Reinforced: LL = + du/dt 1600 V + N or CMF + N + CMF Randomwound and form-wound 380 V < UN < 690 V Check with the motor manufacturer. 0 V < UN < 500 V 500 V < UN < 690 V UN < 420 V Enamelled wire with fibre glass taping Standard: LL = 1300 V + du/dt with voltages over 500 V + N + CMF + du/dt 500 V < UN < 600 V Standard 100 kW < PN < 350 kW or frame size > IEC 315 134 HP < PN < 469 HP or frame size > NEMA 500 +N + du/dt + N PN > 350 kW or frame size > IEC 400 PN > 469 HP or frame size > NEMA 580 + N + CMF + du/dt + N + CMF
A B B
+ N + CMF + du/dt + N + CMF + du/dt + N or CMF + du/dt + N or + du/dt + CMF + N + CMF + du/dt + N + CMF
+ du/dt + N + CMF
or Reinforced: LL = 1800 V 600 V < UN < 690 V Reinforced: LL = + du/dt 1800 V Reinforced: LL = 2000 V, 0.3 s rise time *** + N or CMF + du/dt + N N + CMF + N + CMF + du/dt + N + CMF N + CMF
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
58
* manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer. *** If the intermediate DC circuit voltage of the drive will be increased from the nominal level by resistor braking or by the IGBT supply unit control program (parameter selectable function), check with the motor manufacturer if additional output filters are needed in the applied drive operation range.
Note 2: Explosion-safe (EX) motors The motor manufacturer should be consulted regarding the construction of the motor insulation and additional requirements for explosion-safe (EX) motors. Note 3: High-output motors and IP 23 motors For motors with higher rated output than what is stated for the particular frame size in EN 50347 (2001) and for IP 23 motors, the requirements of ABB random-wound motor series M3AA, M3AP, M3BP are given below. For other motor types, see the Requirements table above. Apply the requirements of range 100 kW < PN < 350 kW to motors with PN < 100 kW. Apply the requirements of range PN > 350 kW to motors within the range 100 kW < PN < 350 kW. In other cases, consult the motor manufacturer.
Manufacturer Motor type Nominal mains voltage (AC line voltage) Requirement for Motor insulation system ABB du/dt filter, insulated N-end bearing and ABB common mode filter PN < 55 kW PN < 74 HP A B B Randomwound M3AA, M3AP, M3BP UN < 500 V Standard or Reinforced 600 V < UN < 690 V Reinforced + du/dt +N + du/dt + N + N + CMF + du/dt + N + CMF + du/dt 55 kW < PN < 200 kW 74 HP < PN < 268 HP +N + du/dt + N PN > 200 kW PN > 268 HP + N + CMF + du/dt + N + CMF
Note 4: HXR and AMA motors All AMA machines (manufactured in Helsinki) for drive systems have form-wound windings. All HXR machines manufactured in Helsinki starting 1.1.1998 have form-wound windings. Note 5: ABB motors of types other than M2_, M3_, HX_ and AM_ Use the selection criteria given for non-ABB motors. Note 6: Resistor braking of the drive When the drive is in braking mode for a large part of its operation time, the intermediate circuit DC voltage of the drive increases, the effect being similar to increasing the supply voltage by up to 20 percent. The voltage increase should be taken into consideration when determining the motor insulation requirement. Example: Motor insulation requirement for a 400 V application must be selected as if the drive were supplied with 480 V. Note 7: Drives with an IGBT supply unit
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
59
If voltage is raised by the drive (this is a parameter selectable function for special applications only), select the motor insulation system according to the increased intermediate circuit DC voltage level, especially in the 500 V supply voltage range. Note 8: Calculating the rise time and the peak line-to-line voltage The peak line-to-line voltage at the motor terminals generated by the drive as well as the voltage rise time depend on the cable length. The requirements for the motor insulation system given in the table are worst case requirements covering installations with 30-metre and longer cables. The rise time can be calculated as follows: t = 0.8 LL/(du/dt). Read LL and du/dt from the diagrams below. Multiply the values of the graph by the supply voltage (UN). In case of drives with an IGBT supply unit or resistor braking, the LL and du/dt values are approximately 20% higher. 3.0 2.5 2.0 1.5 1.0 0.5 0.0 100 200 300 Cable length (m) With du/dt Filter du/dt ------------ (1/s) UN LL/UN 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 100 200 300 Cable length (m) Without du/dt Filter LL/UN du/dt ------------ (1/s) UN
Note 9: Sine filters Sine filters protect the motor insulation system. Therefore, a du/dt filter can be replaced with a sine filter. The peak phase-to-phase voltage with a sine filter is approximately 1.5 UN.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
60
switch or a circuit breaker must be used for protecting each cable and motor. These devices may require a separate fuse to cut off the short-circuit current. Thermal overload protection of the motor According to regulations, the motor must be protected against thermal overload and the current must be switched off when overload is detected. The drive includes a motor thermal protection function that protects the motor and switches off the current when necessary. Depending on a drive parameter value, the function either monitors a calculated temperature value (based on a motor thermal model) or an actual temperature indication given by motor temperature sensors. The user can tune the thermal model further by feeding in additional motor and load data. See the firmware manual for more information on the motor thermal protection, and the connection and use of the temperature sensors. Protection against short-circuit in the motor cable The drive protects the motor cable and the motor in a short-circuit situation when the motor cable is dimensioned according to the nominal current of the drive. No additional protection devices are needed. Protection against short-circuit inside the drive or in the supply cable If the drive is equipped with internal AC fuses (option code +F260), install external protection (such as fuses) at the supply to protect the input cable. If the drive is not equipped with AC input fuses, install external fuses at the supply to protect the input cable and the drive. Use the AC fuse types listed in the chapter Technical data on page 120, or equivalent fuses. Six fuses are needed for each DSU module. WARNING! Circuit breakers are not capable of providing sufficient protection because they are inherently slower than fuses. Always use fuses with circuit breakers.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
61
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
62
The cable must be able to carry the drive load current. See chapter Technical data for the rated currents. The cable must be rated for at least 70 C maximum permissible temperature of conductor in continuous use. For US, see Additional US requirements. The inductance and impedance of the PE conductor/cable (grounding wire) must be rated according to permissible touch voltage appearing under fault conditions (so that the fault point voltage will not rise excessively when an ground fault occurs). 600 VAC cable is accepted for up to 500 VAC. For 690 VAC rated equipment, the rated voltage between the conductors of the cable should be minimum 1 kV. For drive frame size R5 and larger, or motors larger than 30 kW, symmetrical shielded motor cable must be used (figure below). A four-conductor system can be used up to frame size R4 with up to 30 kW motors, but shielded symmetrical motor cable is recommended. Note: When continuous conduit is employed, shielded cable is not required. A four-conductor system is allowed for input cabling, but shielded symmetrical cable is recommended. To operate as a protective conductor, the shield conductivity must be as follows when the protective conductor is made of the same metal as the phase conductors:
Cross-sectional area of the phase conductors S (mm2) S < 16 16 < S < 35 35 < S Minimum cross-sectional area of the corresponding protective conductor Sp (mm2) S 16 S/2
Compared to a four-conductor system, the use of symmetrical shielded cable reduces electromagnetic emission of the whole drive system as well as motor bearing currents and wear. Note: The cabinet configuration of the drive may require multiple supply and/or motor cabling. Refer to the connection diagrams in Electrical installation. The motor cable and its PE pigtail (twisted screen) should be kept as short as possible in order to reduce electromagnetic emission as well as capacitive current.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
63
Alternative power cable types Power cable types that can be used with the drive are represented below.
Recommended Symmetrical shielded cable: three phase conductors and a concentric or otherwise symmetrically constructed PE conductor, and a shield PE conductor and shield Shield A separate PE conductor is required if the conductivity of the cable shield is < 50 % of the conductivity of the phase conductor. Shield
PE
PE
PE
Shield
Not allowed for motor cables with phase conductor cross section larger than 10 mm2 (motors > 30 kW).
Motor cable shield To effectively suppress radiated and conducted radio-frequency emissions, the shield conductivity must be at least 1/10 of the phase conductor conductivity. The requirements are easily met with a copper or aluminium shield. The minimum requirement of the motor cable shield of the drive is shown below. It consists of a concentric layer of copper wires with an open helix of copper tape. The better and tighter the shield, the lower the emission level and the bearing currents.
Insulation jacket Copper wire screen Helix of copper tape Inner insulation
Cable core
Additional US requirements Type MC continuous corrugated aluminum armor cable with symmetrical grounds or shielded power cable must be used for the motor cables if metallic conduit is not used. For the North American market, 600 VAC cable is accepted for up to 500 VAC. 1000 VAC cable is required above 500 VAC (below 600 VAC). For drives rated over 100 amperes, the power cables must be rated for 75 C (167 F).
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
64
Conduit Where conduits must be coupled together, bridge the joint with a ground conductor bonded to the conduit on each side of the joint. Bond the conduits also to the drive enclosure. Use separate conduits for input power, motor, brake resistors, and control wiring. When conduit is employed, type MC continuous corrugated aluminum armor cable or shielded cable is not required. A dedicated ground cable is always required. Do not run motor wiring from more than one drive in the same conduit. Armored cable / shielded power cable The motor cables can be run in the same cable tray as other 460 V or 600 V power wiring. Control and signal cables must not be run in the same tray as power cables. Six conductor (3 phases and 3 ground) type MC continuous corrugated aluminum armor cable with symmetrical grounds is available from the following suppliers (trade names in parentheses): Anixter Wire & Cable (Philsheath) BICC General Corp (Philsheath) Rockbestos Co. (Gardex) Oaknite (CLX). Shielded power cables are available from Belden, LAPPKABEL (LFLEX) and Pirelli, among others.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
65
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
66
Firmware Manual of the drive for the required parameter settings.) Otherwise, the contactor will be damaged. In scalar control, the contactor can be opened with the drive running.
Varistor
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
67
Run analogue and digital signals in separate, shielded cables. Relay-controlled signals, providing their voltage does not exceed 48 V, can be run in the same cables as digital input signals. It is recommended that the relay-controlled signals be run as twisted pairs. Never mix 24 VDC and 115 / 230 VAC signals in the same cable. Relay cable The cable type with braided metallic screen (e.g. LFLEX LAPPKABEL, Germany) has been tested and approved by ABB. Control panel cable In remote use, the cable connecting the control panel to the drive must not exceed 3 metres (10 ft). The cable type tested and approved by ABB is used in control panel option kits. Coaxial cable (for use with Advant Controllers AC 80/AC 800) 75 ohm RG59, diameter 7 mm or RG11, diameter 11 mm Maximum cable length: 300 m (1000 ft)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
68
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
69
Not allowed unless the 24 V cable is insulated for 230/120 V or insulated with insulation sleeving for 230/120 V.
Lead 24 V and 230/120 V control cables in separate ducts inside the cabinet.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
70
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
71
Electrical installation
What this chapter contains
This chapter describes the electrical installation procedure of the drive. WARNING! Only qualified electricians are allowed to carry out the work described in this chapter. Follow the Safety instructions on the first pages of this manual. Ignoring the safety instructions can cause injury or death.
WARNING! During the installation procedure, the supply and inverter modules may have to be temporarily extracted from the cabinet. The modules are heavy, and have a high centre of gravity. In order to minimise the danger of toppling over, keep the sheet metal support supplied with the drive attached to the modules whenever manoeuvring them outside the cabinet.
Before installation
Checking the insulation of the assembly Every drive has been tested for insulation between the main circuit and the chassis (2500 V rms 50 Hz for 1 second) at the factory. Therefore, do not make any voltage tolerance or insulation resistance tests (e.g. hi-pot or megger) on any part of the drive. When checking the insulation of the assembly, proceed in the following manner: WARNING! Check the insulation before connecting the drive to the supply. Make sure that the drive is disconnected from the supply (input power). Motor and motor cable Check the insulation of the motor and motor cable as follows: 1. Check that the motor cable is connected to the motor, and disconnected from the drive output terminals U2, V2 and W2. 2. Measure the insulation resistance of the motor cable and motor between each phase and the Protective Earth using a measuring voltage of 500 VDC. The insulation resistance of an ABB motor must exceed 10 Mohm (reference value at 25 C). For the insulation resistance of other motors, please consult the manufacturer's instructions.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
72
Note: Moisture inside the motor casing will reduce the insulation resistance. If this is suspected, dry the motor and repeat the measuring.
U1 V1
ohm
M 3~
PE
W1
IT (ungrounded) systems EMC filter +E202 is not suitable for use in an IT (ungrounded) system. If the drive is equipped with EMC filter +E202, disconnect the filter before connecting the drive to the supply network. For detailed instructions on how to do this, please contact your local ABB representative. WARNING! If a drive with EMC filter +E202 is installed on an IT system [an ungrounded power system or a high resistance-grounded (over 30 ohms) power system], the system will be connected to earth potential through the EMC filter capacitors of the drive. This may cause danger or damage the unit. Setting the earth fault (ground fault) trip level Grounded systems See page 28. IT (ungrounded) systems On ungrounded systems, an external monitoring unit (Bender IRDH265 or IRDH275, option +Q954) is used. Refer to its documentation for set-up instructions. Note: On ungrounded systems, the internal earth current monitoring must be deactivated. See page 28.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
73
Input power connection Units without load switch-disconnector or air circuit breaker
Connection diagrams 6-pulse connection, two supply modules in parallel
PE PE L11 L21 L31 L12 L22 L32 L1 L2 L3 L11 L21 L31 L12 L22 L32
*)
*)
Notes: No parallel cabling is shown here. Each input terminal of the supply modules must be fed through a dedicated fuse. The fuses are specified in Technical data. *) Contactors are optional
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
74
*)
*)
Notes: No parallel cabling (for each module) is shown here. It is also possible to connect all input power terminals of module 1 to the transformer Y-output and module 2 to the transformer D-output. Note, however, that then the two bridges inside a single module do not form a 12-pulse connection any more. This means that the benefits of the 12-pulse connection are not available during a temporary operation with one module out of use (e.g. for maintenance). Each input terminal of the supply modules must be fed through a dedicated fuse. The fuses are specified in Technical data. The secondaries of the transformer must not be grounded. *) Contactors are optional
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
75
Connection procedure
WARNING! The supply modules are heavy and have a high centre of gravity. Be careful when manoeuvring the modules. Removal of module: (1) Turn the supply (rectifier) module switch-disconnector handle to open position. (2) Release the door handle and open the supply unit door. (3) Remove the fastening screws at the top of the module. (3b) Units with marine construction (+C121) only: Remove fan (see page 107 for instructions) and the two fastening screws at the rear bottom of the module frame. (4) Loosen the connector locking screw (hexagonal socket head). (5) Place the module pull-out ramp against the cabinet base. Make sure the ramp is secured to the cabinet frame. (6) Pull the module carefully out of the cabinet along the ramp. 4 6 3
3b
5 Remove the plastic insulators covering the input power terminals. Lead the cables into the inside of the cabinet. Make the 360 earthing arrangement at the cable entries as shown below.
Grommet (in IP54 units only) Connect the cables as follows: Twist the cable shields to bundles and connect to cabinet PE (ground) busbar. Connect the separate ground conductors/cables to cabinet PE (ground) busbar. Connect the phase conductors to the input power terminals (U1.1 ). Depending on the cable size, use cable lugs or dual-cable screw lug connectors. For details on the terminals and tightening torques, see Technical data Input power connection on page 122, and section Use of the dual-cable screw lug connector below. Refit the plastic insulators onto the input power terminals. Push the module back in mind your fingers and tighten the fastening screws. Tighten the connector locking screw to 4 Nm (3 lbf.ft). Please note that the module can only mate with the quick connector when the switch-disconnector is in open position. Remove the module pull-out ramp and close the cubicle doors.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
76
1 2 3 4
1 2 3
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
77
Input power connection Units with load switch-disconnector or air circuit breaker
Connection diagrams 6-pulse connection, two supply modules in parallel
PE PE 1L1 1L2 1L3 Switching, breaking, disconnecting and grounding devices
*)
L1 L2 L3
**)
***)
Incoming cubicle
***)
Notes: *) Fuses are not required if the input power line is constructed of busbars that withstand the transformer short circuit current. **) The cable lead-through details (number and size of holes), and cable connection details (number and dimensions of busbars, tightening torque) are given in chapter Technical data, section Input power connection. ***) There are no contactors inside the supply module(s) when the drive is equipped with an air circuit breaker.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
78
*)
***)
Switching, breaking, disconnecting and grounding devices
**)
Incoming cubicle
***)
Notes: *) Fuses are not required if the input power line is constructed of busbars that withstand the transformer short circuit current. **) No bridging (connecting 1L1 to 2L1, 1L2 to 2L2, and 1L3 to 2L3) is allowed! There are two separate incoming cubicles one for terminals 1L1, 1L2 and 1L3, the other for 2L1, 2L2 and 2L3 if a) the unit is equipped with air circuit breakers, b) the drive is UL listed, or c) the incoming cubicle is designed for a busbar connection. The cable lead-through details (number and size of holes), and cable connection details (number and dimensions of busbars, tightening torque) are given in chapter Technical data, section Input power connection. ***) There are no contactors inside the modules when the drive is equipped with air circuit breakers.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
79
Connection procedure
Open the door of the incoming (load switch-disconnector or air circuit breaker) cubicle. Remove any shrouds covering the input terminals and cable entries. Lead the cables into the cubicle. Make the 360 earthing arrangement at the cable entries as shown below.
Cut the cables to suitable length. Strip the cables and conductors. Twist the cable screens into bundles and connect to cabinet PE (ground) busbar. Connect the separate ground conductors/cables to cabinet PE (ground) busbar. Connect the phase conductors to the input terminals using the torques given in chapter Technical data, section Input power connection. Refit the shrouds removed earlier. Close the door.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
80
M 3~
The recommended cable types are given in chapter Planning the electrical installation.
Whenever the inverter unit consists of parallel-connected inverter modules, all the modules (two are shown below) are to be cabled separately to the motor.
PE U2 V2 W2 U1 V1 W1 U2 V2 W2 PE
M 3~
The recommended cable types are given in chapter Planning the electrical installation.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
81
WARNING! The cabling from all inverter modules to the motor must be physically identical considering cable type, cross-sectional area, and length.
PE U2 V2 W2 U1 V1 W1 U2 V2 W2 PE
M 3~
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
82
Connection procedure
WARNING! The inverter modules are heavy and have a high centre of gravity. Be careful when manoeuvring the modules. In order to minimise the danger of toppling over, keep the support legs of the modules extended whenever manoeuvring the modules outside the cabinet. Extract each inverter module from the cubicle as follows: (1) Open the door of the inverter cubicle. (2) Remove the shroud covering the upper part of the cubicle. (3) Open the transparent cover on the front of the inverter module and disconnect the fibre optic cables. Move the cables aside. (4) Remove the L-shaped DC busbars on top of the module. (5) Disconnect the terminal block (X50) next to the DC busbars. (6) Remove the two module fastening screws (6a) at the top. At the base of the module, loosen the two fastening screws (6b) but leave them in place; lift the bracket (6c) into the up position. (7) Insert the module pull-out ramp under the two screws at the base of the module and tighten. (8) Pull the module carefully out of the cubicle along the ramp. Make sure the wires do not catch. (9) Extend the support legs of the module. Keep the legs extended until the module is about to be inserted back into the cubicle.
6a 3 4 8
7 9a 9b
6c
6b
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
83
Lead the cables into the cabinet below each inverter module. Make the 360 earthing arrangement at the cable entry as shown.
Cut the cables to suitable length. Strip the cables and conductors. Twist the cable screens into bundles and connect to cabinet PE (ground) busbar. Connect any separate ground conductors/cables to cabinet PE (ground) busbar. Connect the phase conductors to the output terminals. Use the tightening torques specified in Technical data Motor connection on page 124. Insert each inverter module into the cubicle as follows: (1) Move the inverter module close to the ramp, then retract the support legs of the module. (2) Push the module back into the cubicle mind your fingers. (3) Refasten the module fixing screws at the top, reconnect the DC busbars. (4) Reconnect the cables (X50, fibre optic cables). (5) Loosen the module fastening screws at the base of the module and remove the pull-out ramp. Flip the module fastening bracket into the down position and tighten the screws. Close the doors. At the motor, connect the cables according to instructions from the motor manufacturer. Pay special attention to the phase order. For minimum radio frequency interference: ground the cable shield 360 degrees at the lead-through of the motor terminal box
Conductive gaskets or ground the cable by twisting the shield as follows: flattened width > 1/5 length.
b > 1/5 a a b
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
84
U2 V2 W2
U1 V1 W1 PE
M 3~
The recommended cable types are given in chapter Planning the electrical installation.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
85
Control connections
Drive control connections The control connections are made on the terminal blocks provided in the swing-out frame of the drive. Refer to the circuit diagrams delivered with the drive, and to the chapter Motor control and I/O board (RMIO). Supply unit control connections The supply unit is controlled using the local control devices mounted on the cabinet door, or the buttons on the DSSB board. No external control connections by the user are needed. However, the user can connect certain external devices to the supply module. It is possible to: control the supply unit through the remote control inputs (On, Start, Reset, External fault) halt the supply unit by an external emergency stop button (if the unit is equipped with a local emergency stop button) read supply units status information through the relay outputs (Fault, Running, External 48 VDC supply on, Earth fault, emergency stop) feed the supply units control boards from an external +48 VDC supply. Refer to the circuit diagrams delivered with the drive for the connection terminals for the external control devices. For additional information on the control connections see the ACA631/633 Cabinet-installed Diode Supply Unit (DSU) Users Manual (Code: 64735501 [English]), available through ABB representatives.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
86
Connection procedure
Turn the supply (rectifier) unit switch-disconnector into open position. Release the door handle and open the door of the control and I/O cubicle. Remove the two locking screws at the edge of the swing-out frame and open the frame. Run the cables into the inside of the cabinet through the grommets provided. Top entry units only: If several cables need to be run through one grommet, use Loctite 5221 (cat. no. 25551) under the grommet to seal the cable entry. Run the cables between the EMI conductive cushions as shown below. Strip the cable at this location to enable proper connection of the bare shield and the cushions. Tighten the cushions firmly onto the cable shields. Side view Strain relief
Grommet
Lead-through plate
If the outer surface of a cable shield is non-conductive, turn the shield inside out as shown below and apply copper foil to keep the shielding continuous. Do not cut the grounding wire (if present). Stripped cable Conductive surface of the shield exposed Stripped part covered with copper foil
Copper foil
Cable shield
On top entry units, sort the cables so that the thinnest and thickest cables are at opposite ends of the opening. Top view
Thickest cable
Thinnest cable
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
87
Run the cables to the swing-out frame as shown below. Wherever possible, use the existing cable trunking (1) in the cabinet. Use sleeving wherever the cables are laid against sharp edges. Leave some slack in the cable at the hinge (2) to allow the frame to open fully. Tie the cables to the braces (3) to provide strain relief. Swing-out frame open Cable routing example
Cut the cables to suitable length. Strip the cables and conductors. Twist the cable shields into bundles and connect them to the ground terminal nearest to the terminal block. Keep the unshielded portion of the cables as short as possible. Connect the conductors to appropriate terminals (see the chapter Motor control and I/O board (RMIO) and the circuit diagrams delivered with the unit). Close the swing-out frame, refasten, and close the doors.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
88
To nearest PE terminal
CHASSIS
RTAC-01
GND
SHLD
C BD A E
SHLD CHA+ CHACHB+ CHBCHZ+ CHZ0V 0V V OUT +15V V IN +24V CHA CHB
F01 9 78
X2
X1
Note 1: If the encoder is of unisolated type, ground the encoder cable at the drive end only. If the encoder is galvanically isolated from the motor shaft and the stator frame, ground the encoder cable shield at the drive and the encoder end. Note 2: Twist the pair cable wires.
12345678 123456
45 23 6
Fibre optic link A DDCS fibre optic link is provided via the RDCO optional module for PC tools, master/follower link, NDIO, NTAC, NAIO, AIMA I/O module adapter and fieldbus adapter modules of type Nxxx. See RDCO Users Manual [3AFE 64492209 (English)] for the connections. Observe colour coding when installing fibre optic cables. Blue connectors go to blue terminals, and grey connectors to grey terminals. When installing multiple modules on the same channel, connect them in a ring.
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
89
Secondary
Primary
Output
3~ input
Supply voltage 690 V 660 V 600 V 575 V 525 V 500 V 480 V 460 V 440 V 415 V 400 V 380 V Terminals A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 A1, B1, C1 Tap settings A1 to... C2 C2 C3 C3 C4 C4 C5 C5 C6 C6 C7 C7 B1 to C1 to A2 A2 A3 A3 A4 A4 A5 A5 A6 A6 A7 A7 B2 B2 B3 B3 B4 B4 B5 B5 B6 B6 B7 B7 Supply voltage 690 V 660 V 600 V 575 V 525 V 500 V 480 V 460 V 440 V 415 V 400 V 380 V 230 V Terminals a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1 a3, n1
1~ output
115 V Terminals a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 a4, n1 Tap setting 115 115+ 115 115+ 115 115+ 115 115+ 115 115+ 115 115+ Tap setting 230 230+ 230 230+ 230 230+ 230 230+ 230 230+ 230 230+
3~ output
400 V (50 Hz) Terminals a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 a1, b1, c1 320 V (60 Hz) Terminals a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2 a2, b2, c2
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
90
Electrical installation
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
91
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
92
WARNING! If the RMIO board is powered from two power supplies (connected to X23 and X34), and the external power supply connected to X23 is also used to power external equipment, equip the RMIO branch of the circuit with a diode as shown below. The diode ensures that the RMIO board will not be damaged by overcurrent in case the external power supply fails.
X34 2 3 X23 1 2 +24V GND Auxiliary voltage output and input, non-isolated, 24 V DC 250 mA
RMIO
+24 V DC
+ Other equipment
Parameter settings In the Standard Application Program, set parameter 16.09 CTRL BOARD SUPPLY to EXTERNAL 24V if the RMIO board is powered from an external supply.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
93
rpm
0...motor nom.
Output current 0(4)...20 mA = 0...motor nom. current, RL < 700 ohm Stop/Start Forward/Reverse 1) Not in use Acceleration & deceleration select 2) Constant speed select 3) Constant speed select 3) +24 VDC max. 100 mA Digital ground Digital ground Start interlock (0 = stop) 4) Auxiliary voltage output and input, nonisolated, 24 VDC 250 mA 5) Relay output 1: ready
0 = open, 1 = closed parameters 22.02 and 22.03 parameters 22.04 and 22.05 See par. group 12 CONSTANT SPEEDS. 0 0 1 1 Set speed through AI1 Constant speed 1 Constant speed 2 Constant speed 3
FUNC.
5) Total maximum current shared
Fault
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
94
rpm
0...motor nom.
Output current 0(4)...20 mA = 0...motor nom. current, RL < 700 ohm Start ( ) Stop ( ) Forward/Reverse 1) Acceleration & deceleration select 2) Constant speed select 3) Constant speed select 3) +24 VDC max. 100 mA Digital ground Digital ground Start interlock (0 = stop) 4) Auxiliary voltage output and input, nonisolated, 24 VDC 250 mA 5) Relay output 1: ready
0 = open, 1 = closed parameters 22.02 and 22.03 parameters 22.04 and 22.05 See par. group 12 CONSTANT SPEEDS. 0 0 1 1 Set speed through AI1 Constant speed 1 Constant speed 2 Constant speed 3
FUNC.
5) Total maximum current shared
Fault
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
95
Analogue outputs
Resolution Inaccuracy Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm 0.1 % (10 bit) 1 % (Full Scale Range) at 25 C (77 F). Temperature coefficient: 200 ppm/C ( 111 ppm/F) max.
Digital inputs
With Standard Application Program six programmable digital inputs (common ground: 24 VDC, -15 % to +20 %) and a start interlock input. Group isolated, can be divided in two isolated groups (see Isolation and grounding diagram below). Thermistor input: 5 mA, < 1.5 kohm 1 (normal temperature), > 4 kohm (high temperature), open circuit 0 (high temperature). 0
Isolation test voltage Logical thresholds Input current Filtering time constant
Internal supply for digital inputs (+24 VDC): short circuit proof. An external 24 VDC supply can be used instead of the internal supply. 500 VAC, 1 min < 8 VDC 0, > 12 VDC 1 DI1 to DI 5: 10 mA, DI6: 5 mA 1 ms
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
96
Relay outputs
Switching capacity Minimum continuous current Maximum continuous current Isolation test voltage Three programmable relay outputs 8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC 5 mA rms at 24 VDC 2 A rms 4 kVAC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also fulfil the requirements and the installation site is below 2000 m (6562 ft). Above 2000 m (6562 ft), see page 68.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
97
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
98
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
99
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
100
Start-up procedure
Action WARNING! Ensure that the disconnector of the supply transformer is locked to open position, i.e. no voltage is, or cannot be connected to drive inadvertently. Check also by measuring that there is no voltage connected. Additional information
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
101
Action
Additional information
Units with line contactors: Close the contactors and start the supply unit by turning the start switch on the cabinet door from 0 into START position for 2 seconds.
On-load checks
Check that the Prevention of Unexpected Start function (if installed) works: Start and Stop the drive and wait until the motor has stopped. Open the Prevention of Unexpected Start switch (mounted on a control desk). Give a Start command. The drive should not start. Reset the drive. Check that the cooling fans rotate freely in the right direction, and the air flows upwards. Check the direction of rotation of the motor. Check the correct operation of the emergency-stop circuits from each operating location. Check visually that the fans rotate in the direction indicated by an arrow on the fan housing. Optional function. See delivery specific circuit diagrams.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
102
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
103
Maintenance
What this chapter contains
This chapter contains preventive maintenance instructions.
Safety instructions
Only a qualified electrician is allowed to perform the maintenance. Before starting work inside the cabinet, isolate the drive from the supply (note that the switch-disconnector on the door does not switch off the voltage from the input terminals) wait for 5 minutes to let the intermediate circuit capacitors discharge open the cabinet doors ensure there is no dangerous voltage present by measuring the voltage of the input terminals and the intermediate circuit terminals.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
104
Maintenance intervals
If installed in an appropriate environment, the drive requires very little maintenance. This table lists the routine maintenance intervals recommended by ABB.
Interval Every year of storage Every 6 to 12 months (depending on dustiness of environment) Every year (IP22 and IP42 units) Every year (IP54 units) Every 3 years Every 3 years Every 6 years Every 6 years Every 10 years (if drive subjected to high ambient temperature) Every 12 years Maintenance action Capacitor reforming Heatsink temperature check and cleaning Air filter check; replacement if necessary Air filter replacement Cooling fan check; replacement if necessary Power connections check and cleaning Cooling fan change PPCS branching unit (APBU-xx) Memory backup battery renewal Capacitor change Capacitor change Instructions See document ACS 600/800 Capacitor Reforming Guide (Code: 3BFE 64059629 [English]) and Capacitors. See Heatsinks.
See Replacing the PPCS branching unit (APBU-xx) memory backup battery.
See Cooling fans. See Power connections. See Cooling fans. Locate the APBU unit. See section Replacing the PPCS branching unit (APBU-xx) memory backup battery on page 105. See Capacitors. See Capacitors.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
105
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
106
Power connections
1. Read and repeat the steps in section Safety instructions above. 2. Open the cabinet doors. 3. Extract one supply or inverter module from the cabinet as described in the connection procedures in the chapter Electrical installation. 4. Check the tightness of the cable connections at the quick connector. Use the tightening torque table in Technical data. 5. Clean all contact surfaces of the quick connector and apply a layer of suitable joint compound (e.g. Isoflex Topas NB 52 from Klber Lubrication) onto them. 6. Re-insert the supply/inverter module. 7. Repeat steps 3 to 6 for all remaining supply and inverter modules.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
107
Cooling fans
Power module cooling fans The lifespan of the cooling fans of the supply and inverter modules is about 50 000 hours. The actual lifespan depends on the running time of the fan, ambient temperature and dust concentration. Each supply and inverter module has its own cooling fan. Replacements are available from ABB. Do not use other than ABB specified spare parts. The application program keeps track of the running time of the cooling fan of the inverter modules. See the Firmware Manual delivered with the drive for the actual signal which indicates the running time. Supply module fan replacement 1. Read and repeat the steps in section Safety instructions above. 2. Open the supply cubicle doors. 3. Loosen the locking screw (1). 4. Disconnect the fan wiring plug (2). 5. Pull out the fan (3). 6. Install a new fan in reverse order.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
108
Inverter module fan replacement 1. Read and repeat the steps in section Safety instructions above. 2. Open the inverter cubicle doors. 3. Disconnect the fan wiring plug (1). 4. Remove the locking screws (2). 5. Pull the fan out along its sliding rails (3). 6. Install a new fan in reverse order.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
109
Control and I/O cubicle cooling fans The cooling fans inside the control and I/O cubicle can be replaced as follows: 1. Read and repeat the steps in section Safety instructions above. 2. Open the door of the control and I/O cubicle (or combined control, I/O and supply cubicle). 3. Detach the wiring from each fan (AC plug and grounding wire). 4. Undo the four fastening screws of the fan assembly and pull the assembly outwards to gain access to the fan fastening screws. 5. Undo the fastening screws of the fans (there are four for each fan) from below. Remove the fans. 6. Install new fans in reverse order. Before fastening the fans, make sure the airflow arrow on both fans is pointed up.
4 3 3 5 4
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
110
Air circuit breaker cubicle fans Some IP2x/IP4x units with an air circuit breaker are also fitted with two fans at the air outlet on the roof. The fans are fastened to the grating (1) which can be removed by undoing the four screws (2). If necessary, undo the screws labelled (3) to remove the airflow guide (4).
1 2 2 3 4 3
IP54 (UL type 12) fan replacement 1. Remove the front and back gratings of the fan cubicle by lifting them upwards. 2. Remove the shrouds by undoing the fastening screws. 3. Undo the fastening screws of the side/top cover of the fan. 4. Lift the side/top cover of the fan off. 5. Disconnect the fan supply wire connector from the cabinet roof (on top and inside the cabinet). 6. Undo the fastening screws of the fan cassette at each corner. 7. Lift the fan cassette off. 8. Undo the cable ties on the top of the fan cassette. 9. Disconnect the cables (detachable terminals). 10. Remove the fan capacitor by undoing the fastening screw of the clamp. 11. Undo the fastening screws of the fan. 12. Pull the fan out. 13. Install the new fan and fan capacitor in reverse order to the above. Ensure that the fan is centred and rotates freely.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
111
2 1 3 2 3
7 5 5
10 8 9 8 8
11
12 11
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
112
Heatsinks
The heatsink fins of the power modules pick up dust from the cooling air. The module runs into overtemperature warnings and faults if the heatsinks are not clean. In a normal environment (not especially dusty nor clean) the heatsinks should be checked annually, in a dusty environment more often. Whenever necessary, clean the heatsinks as follows: 1. Remove the cooling fan (see section Cooling fans). 2. Blow dry clean compressed air from bottom to top and simultaneously use a vacuum cleaner at the air outlet to trap the dust. Note: Prevent the dust from entering adjoining equipment. 3. Refit the cooling fan.
Capacitors
The inverter modules employ several electrolytic capacitors. Their lifespan is at least 90 000 hours depending on the operating time of the drive, loading and ambient temperature. Capacitor life can be prolonged by lowering the ambient temperature. It is not possible to predict capacitor failure. Capacitor failure is usually followed by damage to the unit and an input cable fuse failure, or a fault trip. Contact ABB if capacitor failure is suspected. Reforming Reform (re-age) spare part capacitors once a year according to ACS 600/800 Capacitor Reforming Guide (code: 64059629 [English], available through your local ABB representative. Capacitor replacement Contact an ABB service representative.
Maintenance
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
113
Fault tracing
What this chapter contains
This chapter instructs in interpreting the LED indications of the ACS800-07. Note: Information on warnings and faults reported by the application program (and displayed on the CDP-312R drive control panel on the cabinet door) are contained within the Firmware Manual delivered with the drive.
O P h P h P h
,0 m m ,1 3 m m
D C . u s , 0 e 0 , 0m . . a n . v e r T e m p . a s e L 1 .1 M a s e L 2 .1 M a s e L 3 .1 M
,0 m m 0 ma m i l m u r e , a 0 0 i l mu rm e , 0a 0 i l m u m r e
, 0 , m 0 0 m, 0 m m m m
i, 0 s 0 s m i n m g is s in g is s in g
P o . a O v P h P h P h
w e r n . u ll S p e rT e m p a s e L 1 .2 a s e L 2 .2 a s e L 3 .2
e e d W a r M is M is M is
,0 m m
n in s in s in s in g
g g g
,0 m m
, 0 0 ,m 0 m m m
C o d e : 6 x 4 x 6 x 9 x 4 x x8 x 8 x 3
LED
Cause
What to do
LEDs on the DSSB board FAN FAILURE SUPPLY MISSING Cooling fan failure. LED blinks and Phase L_._ Missing LED on module cover blinks: Main circuit AC fuse has blown, fuse on DSAB-01C board has blown, or input power terminal is loose. LED blinks but no Phase L_._ Missing LED on module cover blinks: Auxiliary circuit AC fuse of Diode Supply Unit has blown, main circuit AC fuse of branches L1.1, L2.1 or L3.1 of the first DSU module has blown, or input power terminal is loose. LED on: DSU overload or faulty DSSB control board. Change fan. Change main circuit AC fuse. Change fuse on DSAB board or DSAB board. Check and tighten input power terminals.
Change blown auxiliary circuit AC fuse. Change blown main circuit AC fuse. Check and tighten input power terminals.
Check load. Are all parallel-connected supply modules in place? Decrease load or replace missing module. Change faulty DSSB board.
Fault tracing
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
114
Cause Supply unit has exceeded temperature fault limit. DC fuse blown. Digital input indicates external fault. Blinking: Internal fault detected by DSU control program, e.g: - DSU charging failed or exceeded allowed duration (5 s.). - Module switch-disconnectors do not open/close, or DSSB board receives false switch-disconnector status signal (auxiliary contact). - Emergency stop circuit is open, or not connected correctly. - Loose connectors -X4 or -X8 on DSSB board. - 4A fuse(s) blown on DSSB board.
What to do Check ambient temperature. Check cooling air flows freely. Check fan operation. Check inlet and outlet air filters. Check heatsink for dust pick-up. Change DC fuse. Fix external fault. Check status of digital input. Check fuses on circuit boards. Reset DSU and restart. Check operation of switch-disconnectors (optional equipment). Check status signal. Check/tighten signal connections. Replace module (or switchdisconnector.) Release emergency stop button. Check connections of the emergency stop circuit. Check that connectors -X4 and -X8 are properly fastened. Measure +/-24VDC from DSSB board connectors -X4 and -X8. Change the 4A circuit board fuses F1 and F2 of DSSB board. Check operation of contactors (optional). Check status signal. Check/tighten signal connections. Replace module (or contactor). Reset DSU and restart. Check motor, and motor cable. Ensure there are no power factor correction capacitors or surge absorbers connected to the system. If all of the above are OK, raise earth fault trip level; see the ACA631/633 Users Manual for Cabinet-installed Diode Supply Unit (code: 64735501 [English]). See OVER TEMP FAULT above. Contactors off: Close contactors. Contactors on: Wait until supply unit has charged intermediate circuit (i.e LED illuminates steadily) and start to load the unit.
On: - Module contactors do not open, or DSSB board receives false contactor status signal (auxiliary contact). EARTH FAULT Supply load imbalance due to earth fault leakage current in drive, motor cable or motor.
Supply unit has exceeded temperature warning limit. Blinking: Supply module contactor is off or module is charging intermediate circuit. Input terminals are live and module switch-disconnectors are switched on. However, unit cannot be loaded yet. On: DSU is in operation and can be loaded; Input terminals are live, module switch-disconnectors and contactors are on, intermediate circuit capacitors have been charged.
Load/control DSU.
LEDs on supply module front DC Fuse Failure Power See DC FUSE above. See READY above. See DC FUSE above. See READY above.
Fault tracing
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
115
LED Fan Failure Fan Full Speed Over Temp Fault Over Temp Warning Phase L_._ Missing
Cause See FAN FAILURE above. Cooling fan rotates at maximum speed. See OVER TEMP FAULT above. See OVER TEMP WARN above. See SUPPLY MISSING above.
What to do See FAN FAILURE above. See OVER TEMP FAULT above. See OVER TEMP FAULT above. See SUPPLY MISSING above.
Note: A fault indication LED normally stays lit after the fault is detected. However, the LED will blink during an input power break to minimise back-up battery current consumption. The battery discharge time is 30 60 minutes.
AINT board (visible through the transparent cover on the front of the inverter modules)
Fault tracing
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
116
Fault tracing
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
117
Technical data
What this chapter contains
This chapter contains the technical specifications of the drive, e.g. ratings, frame sizes and technical requirements, provisions for fulfilling the requirements for CE and other markings, and warranty information.
Ratings
The ratings for the ACS800-07 with 50 Hz and 60 Hz supplies are given below. The symbols are described below the table.
ACS800-07 type Nominal ratings Icont.max A 879 1111 1255 1452 1770 2156 2663 883 1050 1258 1372 1775 2037 2670 628 729 885 953 1258 1414 1774 1866 2321 2665 2770 Imax A 1315 1521 1877 1988 2648 2951 3894 1321 1524 1882 1991 2655 2956 3901 939 1091 1324 1426 1882 2115 2654 2792 3472 3987 4144 No-overload use Pcont.max kW 500 630 710 800 1000 1200 1450 630 710 900 1000 1250 1450 1900 630 710 800 900 1200 1400 1700 1900 2300 2600 2800 Lightoverload use I2N A 844 1067 1205 1394 1699 2070 2556 848 1008 1208 1317 1704 1956 2563 603 700 850 915 1208 1357 1703 1791 2228 2558 2659 PN kW 500 630 710 800 1000 1200 1450 630 710 900 1000 1200 1400 1850 630 710 800 900 1200 1400 1700 1800 2200 2500 2700 Heavy-duty Heat disAir flow use sipation I2hd A 657 831 939 1086 1324 1613 1992 660 785 941 1026 1328 1524 1997 470 545 662 713 941 1058 1327 1396 1736 1993 2072 Phd kW 400 450 500 630 710 900 1120 500 560 630 710 900 1120 1400 500 560 630 710 900 1000 1250 1400 1600 1900 2100 kW 13.0 17.2 18.5 23.9 27.5 35.4 42.7 14.0 17.2 19.9 23.8 29.4 35.0 45.4 13.9 17.1 18.4 20.8 27.0 32.5 40.1 43.3 51.5 58.0 63.6 m3/h 3120 3840 3840 3840 5040 5760 6960 3120 3840 3840 3840 5040 5760 6960 3120 3120 3120 3840 5040 5040 6240 6960 8160 9360 10080 Noise level dBA 73 74 74 74 75 76 76 73 74 74 74 75 76 76 73 73 73 74 75 75 76 76 77 78 78
Three-phase supply voltage 380 V, 400 V or 415 V ACS800-07-0610-3 ACS800-07-0770-3 ACS800-07-0870-3 ACS800-07-1030-3 ACS800-07-1230-3 ACS800-07-1540-3 ACS800-07-1850-3 ACS800-07-0760-5 ACS800-07-0910-5 ACS800-07-1090-5 ACS800-07-1210-5 ACS800-07-1540-5 ACS800-07-1820-5 ACS800-07-2310-5 ACS800-07-0750-7 ACS800-07-0870-7 ACS800-07-1060-7 ACS800-07-1160-7 ACS800-07-1500-7 ACS800-07-1740-7 ACS800-07-2120-7 ACS800-07-2320-7 ACS800-07-2900-7 ACS800-07-3190-7 ACS800-07-3490-7
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
PDM-184674-0.36
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
118
Symbols
Nominal ratings Icont.max Continuous RMS output current. No overloadability at 40 C. Maximum output current. Allowable for 10 seconds at start, otherwise as long as allowed Imax by drive temperature. Typical ratings for no-overload use Pcont.max Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage (400, 500 or 690 V). Typical ratings for light-overload use (10% overloadability) Continuous rms current. 10% overload is allowed for 1 minute every 5 minutes. I2N Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage PN (400, 500 or 690 V). Typical ratings for heavy-duty use (50% overloadability) Continuous rms current. 50% overload is allowed for 1 minute every 5 minutes. I2hd Typical motor power. The power ratings apply to most IEC 34 motors at nominal voltage Phd (400, 500 or 690 V).
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres (3281 ft), or if the ambient temperature exceeds 40 C (104 F). Temperature derating In the temperature range +40 C (+104 F) to +50 C (+122 F), the rated output current is decreased by 1% for every additional 1 C (1.8 F). The output current is calculated by multiplying the current given in the rating table by the derating factor. Example If the ambient temperature is 50 C (+122 F), the derating factor is 100 % - 1 % 10 C = C 90% or 0.90. The output current is then 0.90 I or 0.90 I .
2N cont.max
Altitude derating At altitudes from 1000 to 4000 m (3281 to 13123 ft) above sea level, the derating is 1% for every 100 m (328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than 2000 m (6600 ft) above sea level, please contact your local ABB distributor or office for further information.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
119
Three-phase supply voltage 380 V, 400 V or 415 V ACS800-07-0610-3 ACS800-07-0770-3 ACS800-07-0870-3 ACS800-07-1030-3 ACS800-07-1230-3 ACS800-07-1540-3 ACS800-07-1850-3 ACS800-07-0760-5 ACS800-07-0910-5 ACS800-07-1090-5 ACS800-07-1210-5 ACS800-07-1540-5 ACS800-07-1820-5 ACS800-07-2310-5 ACS800-07-0750-7 ACS800-07-0870-7 ACS800-07-1060-7 ACS800-07-1160-7 ACS800-07-1500-7 ACS800-07-1740-7 ACS800-07-2120-7 ACS800-07-2320-7 ACS800-07-2900-7 ACS800-07-3190-7 ACS800-07-3490-7
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
120
Internal AC fuses
ACS800-07 type Input current (A)
6 12 12 12 12 18 18 6 12 12 12 12 18 18 6 6 6 12 12 12 12 18 18 18 24
Qty.
Type (IEC/UL/CSA)
Voltage (V)
I2t Pre-arc
UN = 400 V (Range 380-415 V) -0610-3 790 -0770-3 999 -0870-3 1128 -1030-3 1305 -1230-3 1591 -1540-3 1938 -1850-3 2394 UN = 500 V (Range 380-500 V) -0760-5 793 -0910-5 944 -1090-5 1131 -1210-5 1233 -1540-5 1596 -1820-5 1831 -2310-5 2400 UN = 690 V (Range 525-690 V) -0750-7 565 -0870-7 655 -1060-7 795 -1160-7 856 -1500-7 1131 -1740-7 1271 -2120-7 1595 -2320-7 1678 -2900-7 2086 -3190-7 2396 -3490-7 2490
170M4417 Bussmann
700
690
69500
465000
170M4417 Bussmann
700
690
69500
465000
170M4417 Bussmann
700
690
69500
465000
*If the drive is not equipped with internal AC fuses (option code +F260), install specified fuses externally at the AC supply. See the diagram on page 73 for the cabling arrangement at each supply module.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
121
Qty.
Type (IEC)
Type (UL/CSA)
170M6216 Bussmann 170M6219 Bussmann
Voltage (V)
UN = 400 V (Range 380-415 V) -0610-3 790 -0770-3 999 -0870-3 1128 -1030-3 1305 -1230-3 1591 -1540-3 1938 -1850-3 2394 UN = 500 V (Range 380-500 V) -0760-5 793 -0910-5 944 -1090-5 1131 -1210-5 1233 -1540-5 1596 -1820-5 1831 -2310-5 2400 UN = 690 V (Range 525-690 V) -0750-7 565 -0870-7 655 -1060-7 795 -1160-7 856 -1500-7 1131 -1740-7 1271 -2120-7 1595 -2320-7 1678 -2900-7 2086 -3190-7 2396 -3490-7 2490
690
1600
690
1250
690
1600
690
170M8647 Bussmann
170M8637 Bussmann
800
1000
170M8650 Bussmann
170M8639 Bussmann
1000
1000
Type
170M4417 Bussmann 170M4467 Bussmann
Voltage (V)
690 690
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
122
Frequency Imbalance Fundamental power factor (cos phi1) Transformer for 12-pulse supply
Connection Phase shift between secondaries Voltage difference between secondaries Short-circuit impedance of secondaries Short-circuit impedance difference between secondaries Other
Dy 11 d0 or Dyn 11 d0 30 electrical < 0.5% > 5% < 10% of short-circuit impedance No grounding of the secondaries allowed. Static screen recommended
Units without load switch-disconnector or air circuit breaker: 4 60 mm (2.36) at each supply module Units with load switch-disconnector (+F253): 9 60 mm (2.36) (frame 1D4 + 2R8i) 12 60 mm (2.36) (frame 2D4 + nR8i) 18 60 mm (2.36) (frame 3D4 + nR8i and 4D4 + nR8i) Units with air circuit breaker (+F255): 18 60 mm (2.36)
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
123
Input terminals at each supply module (units without Conductor size load switch-disconnector or air IEC Cabling circuit breaker) < 150 mm2 185 240 mm2
Max. no. and size of cable lugs per phase 2 150 mm2 OL 2 185-240 mm2 (with dual-cable screw lug included with delivery)
Lug hole
Bolt
Tightening torque 40 Nm 15 Nm
1 11
M10
2 1
7/16
30 lbf.ft
Busbar dimensions
No. of busbars 2)
Bolt size
Tightening torque
13 [0.51]
40 [1.57]
See below
M12 or
70 Nm (50 lb.ft)
50 [1.97]
Number of input busbars (6-pulse units) No. of busbars per connection point 1L1 1L2 1L3 1 1 1 2 2 2 3 3 3 3 3 3
Number of input busbars (12-pulse units) No. of busbars per connection point 1L1 1L2 1L3 2L1 2L2 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3
2L3 1 2 3 3
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
124
Motor connection
Voltage (U2) Frequency 0 to U1, 3-phase symmetrical, Umax at the field weakening point DTC mode: 0 to 3.2 fFWP. Maximum frequency 300 Hz. fFWP = UNmains UNmotor fNmotor
where fFWP = frequency at field weakening point; UNmains = mains (input power) voltage; UNmotor = rated motor voltage; fNmotor = rated motor frequency Frequency resolution Current Power limit Field weakening point Switching frequency Motor cable lead-throughs 0.01 Hz See section Ratings. 2 Phd. After approximately 2 minutes at 2 Phd, the limit is set at Pcont.max. 8 to 300 Hz 2 kHz (average) 3 60 mm at each inverter module (units without common motor terminal cubicle) Units with common motor terminal cubicle: See the chapter Dimensions.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
125
Output terminals at each R8i inverter module (units without common motor terminal cubicle)
Bottom exit
Side view Bolt size: M12 or Tightening torque: 70 Nm (52 lbf.ft)
Top exit
Side view Bolt size: M12 or Tightening torque: 70 Nm (52 lbf.ft)
Cabling direction
Cabling direction
68265631-A0
cabinet_400_generic.asm
Output terminals (units with common motor terminal cubicle) Maximum recommended motor cable length
100 m (328 ft). Motor cables up to 500 m (1640 ft) long are allowed but EMC filtering within the specified limits will not be realised.
Efficiency
Approximately 98% at nominal power level
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
126
Cooling
Method Filter material Internal fans, flow direction from bottom to top Inlet (door) IP22/IP42 units Luftfilter airTex G150 IP54 units Luftfilter airComp 300-50 See chapter Mechanical installation. See Ratings. Outlet (roof) Luftfilter airTex G150
Degrees of protection
IP21; IP22; IP42; IP54, IP54R (with air outlet duct)
Ambient conditions
Environmental limits for the drive are given below. The drive must be used in a heated, indoor controlled environment. Operation Storage Transportation installed for stationary use in the protective package in the protective package Installation site altitude 0 to 4000 m (13123 ft) above sea level [above 1000 m (3281 ft), see section Derating] Air temperature -15 to +50 C (5 to 122 F), -40 to +70 C (-40 to +158F) -40 to +70 C (-40 to +158F) no frost allowed. See section Derating. Relative humidity 5 to 95% Max. 95% Max. 95% No condensation allowed. Maximum allowed relative humidity is 60% in the presence of corrosive gases. Contamination levels No conductive dust allowed. (IEC 60721-3-3, IEC 60721-3- Boards without coating: Boards without coating: Boards without coating: 2, IEC 60721-3-1) Chemical gases: Class 3C1 Chemical gases: Class 1C2 Chemical gases: Class 2C2 Solid particles: Class 3S2 Solid particles: Class 1S3 Solid particles: Class 2S2 Boards with coating: Chemical gases: Class 3C2 Solid particles: Class 3S2 70 to 106 kPa 0.7 to 1.05 atmospheres Max. 1 mm (0.04 in.) (5 to 13.2 Hz), max. 7 m/s2 (23 ft/s2) (13.2 to 100 Hz) sinusoidal Not allowed Not allowed Boards with coating: Chemical gases: Class 1C2 Solid particles: Class 1S3 70 to 106 kPa 0.7 to 1.05 atmospheres Max. 1 mm (0.04 in.) (5 to 13.2 Hz), max. 7 m/s2 (23 ft/s2) (13.2 to 100 Hz) sinusoidal Max. 100 m/s2 (330 ft./s2), 11 ms 100 mm (4 in.) for weight over 100 kg (220 lb) Boards with coating: Chemical gases: Class 2C2 Solid particles: Class 2S2 60 to 106 kPa 0.6 to 1.05 atmospheres Max. 3.5 mm (0.14 in.) (2 to 9 Hz), max. 15 m/s2 (49 ft/s2) (9 to 200 Hz) sinusoidal Max. 100 m/s2 (330 ft./s2), 11 ms 100 mm (4 in.) for weight over 100 kg (220 lb)
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
127
Materials
Cabinet Hot-dip zinc-coated (thickness approx. 20 m) steel sheet (thickness 1.5 mm) with polyester thermosetting powder coating (thickness approx. 80 m) on visible surfaces except back panel. Colour: RAL 7035 (light beige, semigloss). Tin- or silver-plated copper Insulating materials and non-metallic items: Mostly self-extinctive
Frame: Wood or plywood. Plastic wrapping: PE-LD. Bands: PP or steel. The drive contains raw materials that should be recycled to preserve energy and natural resources. The package materials are environmentally compatible and recyclable. All metal parts can be recycled. The plastic parts can either be recycled or burned under controlled circumstances, according to local regulations. Most recyclable parts are marked with recycling marks. If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the printed circuit boards contain lead, both of which are classified as hazardous waste within the EU. They must be removed and handled according to local regulations. For further information on environmental aspects and more detailed recycling instructions, please contact your local ABB distributor.
Applicable standards
EN 50178 (1997) EN 60204-1 (1997) The drive complies with the following standards. The compliance with the European Low Voltage Directive is verified according to standards EN 50178 and EN 60204-1. Electronic equipment for use in power installations. Safety of machinery. Electrical equipment of machines. Part 1: General requirements. Provisions for compliance: The final assembler of the machine is responsible for installing - an emergency-stop device - a supply disconnecting device. Degrees of protection provided by enclosures (IP code). Insulation coordination for equipment within low-voltage systems. Part 1: Principles, requirements and tests. EMC product standard including specific test methods UL Standard for Safety, Power Conversion Equipment, second edition Industrial control equipment
EN 60529: 1991 (IEC 529) IEC 60664-1 (1992) EN 61800-3 (1996) + Amendment A11 (2000) UL 508C CSA C22.2 No. 14-95
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
128
CE marking
A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low Voltage and EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/EEC, as amended by 93/68/EEC).
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to operate without problems within an electromagnetic environment. Likewise, the equipment must not disturb or interfere with any other product or system within its locality. First environment includes establishments connected to a low-voltage network which supplies buildings used for domestic purposes. Second environment includes establishments connected to a network not supplying domestic premises. Restricted distribution: mode of sales distribution in which the manufacturer restricts the supply of equipment to suppliers, customers or users who separately or jointly have technical competence in the EMC requirements of the application of drives. Unrestricted distribution: mode of sales distribution in which the supply of equipment is not dependent on the EMC competence of the customer or user for the application of drives.
Compliance with the EN 61800-3 + Amendment A11 (2000) First environment (restricted distribution)
The requirements of the EMC Directive can be met as follows for restricted distribution: 1. The drive is equipped with EMC filter +E202. 2. The motor and control cables are selected as specified in the Hardware Manual. 3. The drive is installed according to the instructions given in the Hardware Manual. 4. Maximum cable length is 100 metres (328 ft). WARNING! The drive may cause radio interference if used in a residential or domestic environment. The user is required to take measures to prevent interference, in addition to the requirements for CE compliance listed above, if necessary. Note: It is not allowed to install a drive equipped with EMC filter +E202 on IT (unearthed) systems. The supply network becomes connected to earth potential through the EMC filter capacitors which may cause danger or damage the unit.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
129
Second environment
The requirements of the EMC Directive can be met as follows: 1. The drive is equipped with EMC filter +E210. The filter is suitable for TN (earthed) and IT (unearthed) networks. 2. The motor and control cables are selected as specified in the drive manuals. 3. The drive is installed according to the instructions given in the drive manuals. 4. Maximum cable length is 100 metres (328 ft). If the above listed provisions cannot be met, the requirements of the EMC Directive can be met as follows for restricted distribution: 1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In some cases, the natural suppression in transformers and cables is sufficient. If in doubt, the supply transformer with static screening between the primary and secondary windings can be used.
Medium voltage network Supply transformer Neighbouring network
Static screen
Point of measurement Low voltage Equipment (victim) Equipment Equipment Low voltage Drive
2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available from the local ABB representative. 3. The motor and control cables are selected as specified in the drive manuals. 4. The drive is installed according to the instructions given in the drive manuals.
Machinery Directive
The drive complies with the European Union Machinery Directive (98/37/EC) requirements for an equipment intended to be incorporated into machinery.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
130
C-tick marking
A C-tick mark is attached to each drive in order to verify compliance with the relevant standard (IEC 61800-3 (1996) Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods), mandated by the Trans-Tasman Electromagnetic Compatibility Scheme.
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to operate without problems within an electromagnetic environment. Likewise, the equipment must not disturb or interfere with any other product or system within its locality. The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced by the Australian Communication Authority (ACA) and the Radio Spectrum Management Group (RSM) of the New Zealand Ministry of Economic Development (NZMED) in November 2001. The aim of the scheme is to protect the radiofrequency spectrum by introducing technical limits for emission from electrical/electronic products. First environment includes establishments connected to a low-voltage network which supplies buildings used for domestic purposes. Second environment includes establishments connected to a network not supplying domestic premises. Restricted distribution: mode of sales distribution in which the manufacturer restricts the supply of equipment to suppliers, customers or users who separately or jointly have technical competence in the EMC requirements of the application of drives. Unrestricted distribution: mode of sales distribution in which the supply of equipment is not dependent on the EMC competence of the customer or user for the application of drives.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
131
Second environment
The drive complies with the limits of IEC 61800-3 with the following provisions: 1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In some cases, the natural suppression in transformers and cables is sufficient. If in doubt, the supply transformer with static screening between the primary and secondary windings is strongly recommended.
Medium voltage network Supply transformer Neighbouring network
Static screen
Point of measurement Low voltage Equipment (victim) Equipment Equipment Low voltage Drive
2. The drive is installed according to the instructions given in the drive manuals. 3. The motor and control cables used are selected as specified in the drive manuals.
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
132
Technical data
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
133
Dimensions
Cabinet line-ups
The drive consists of cubicles built into a cabinet line-up. The tables below show the composition of cabinet line-ups for each frame size and the standard combinations of options. The dimensions are in millimetres. Notes: The side panels increase the total line-up width by 30 millimetres (1.2). The standard depth of the cabinet line-up is 650 mm (excluding door equipment such as switches and air inlet gratings). This is increased by 130 millimetres (5.1) with top entry/exit models as well as units with cooling air intake through the bottom of the cabinet. The measurements given apply to 6-pulse-input, non-UL/CSA units. For dimensions of 12-pulse-input or UL/CSA units, contact your local ABB representative. The tables are followed by example dimensional drawings.
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
134
1D4 + 2R8i *Brake chopper 1 *Brake chopper 2 *Brake chopper 3 *Brake resistor 1 *Brake resistor 2 *Brake resistor 3 Common motor terminal cubicle Joining cubicle EMC/RFI filter Control, I/O & supply cubicle Shipping split widths Line-up width
Load switchdisconnector
700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 300 400 400 300 400 400 300 400 400 300 400 400 300 400 400 300 400 400 300 400 400 300 400 400 300 400 400 300 400 400
600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 200 200 200 300 300 300 300 300 300 200 200 200 300 300 300 300 300 300 300 300 300 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 800 800 800 800 800 800 800 800 800 800 800 800 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 800 800 800 800 800 800 800 800 800 800 800 800 400 400 400 400 400 400 400 400 400 400 400 400 800 800 800 800 800 800
1300 2000 1700 1600 2300 2000 2100 2800 2500 2400 3100 2800 1500 + 2400 2200 + 2400 1900 + 2400 1600 + 2400 2300 + 2400 2000 + 2400 2500 3200 2900 2800 3500 3200 1500 + 3600 2200 + 3600 1900 + 3600 1600 + 3600 2300 + 3600 2000 + 3600
1300 2000 1700 1600 2300 2000 2100 2800 2500 2400 3100 2800 3900 4600 4300 4000 4700 4400 2500 3200 2900 2800 3500 3200 5100 5800 5500 5200 5900 5600
980 + 800 1580 + 800 1280 + 800 1060 + 800 1660 + 800 1360 + 800 1430 2030 1730 1600 2200 1900 980 + 1200 1580 + 1200 1280 + 1200 1060 + 1200 1660 + 1200 1360 + 1200
*The number of brake choppers depends on drive type. See the chapter Resistor braking.
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Net weight (kg approx.) 890 1490 1190 1060 1660 1360 1250 1850 1550 1420 2020 1720
Inverter unit
135
2D4 + 2R8i Air circuit breaker *Brake chopper 1 *Brake chopper 2 *Brake chopper 3 *Brake resistor 1 *Brake resistor 2 *Brake resistor 3 Common motor terminal cubicle Joining cubicle Shipping split widths Line-up width
Load switchdisconnector
400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 600 500 600 500 600 500 600 500 600 500 600 500 600 500 600 500 600 500 600
600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600
600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 200 200 200 300 300 300 300 300 300 200 200 200 300 300 300 300 300 300 300 300 300 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 800 800 800 800 800 800 800 800 800 800 800 800 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 800 800 800 800 800 800 800 800 800 800 800 800 400 400 400 400 400 400 400 400 400 400 400 400 800 800 800 800 800 800
1600 2100 2200 1900 2400 2500 2400 2900 3000 2700 3200 3300 1800 + 2400 2300 + 2400 2400 + 2400 1900 + 2400 2400 + 2400 2500 + 2400 2800 3100 3400 3100 3600 3700 1800 + 3600 2300 + 3600 2400 + 3600 1900 + 3600 2400 + 3600 2500 + 3600
1600 2100 2200 1900 2400 2500 2400 2900 3000 2700 3200 3300 4200 4700 4800 4300 4800 4900 2800 3100 3400 3100 3600 3700 5400 5900 6000 5500 6000 6100
1290 + 800 1670 + 800 1990 + 800 1370 + 800 1750 + 800 2070 + 800 1740 2120 2440 1910 2290 2610 1290 + 1200 1670 + 1200 1990 + 1200 1370 + 1200 1750 + 1200 2070 + 1200
*The number of brake choppers depends on drive type. See chapter Resistor braking.
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
Net weight (kg approx.) 1200 1580 1900 1370 1750 2070 1560 1940 2260 1730 2110 2430
Inverter unit
Supply unit
136
2D4 + 3R8i Control & I/O cubicle 400 400 400 400 400 400 500 600 500 600 Load switchdisconnector Air circuit breaker Supply unit Inverter unit 600 600 600 600 600 600 800 800 800 800 800 800 400 400 400 Common motor terminal cubicle Shipping split widths 1800 2300 2400 2200 2700 2800 Line-up width 1800 2300 2400 2200 2700 2800 Net weight (kg approx.) 1350 1730 2050 1540 1920 2240
2D4 + 4R8i Control & I/O cubicle 400 400 400 400 400 400 500 600 500 600 Load switch- Air circuit disconnector breaker Supply unit 600 600 600 600 600 600 Inverter unit (1) 600 600 600 600 600 600 400 400 400 Common motor terminal cubicle Inverter unit (2) 600 600 600 600 600 600 Shipping split widths 2200 2700 2800 2600 3100 3200 Line-up width 2200 2700 2800 2600 3100 3200 Net weight (kg approx.) 1680 2060 2380 1870 2250 2570
3D4 + 3R8i Control & I/O cubicle 400 400 400 400 400 400 600 600 600 600 Load switchdisconnector Air circuit breaker Supply unit Inverter unit 800 800 800 800 800 800 800 800 800 800 800 800 400 400 400 Common motor terminal cubicle Shipping split widths 2000 2600 2600 2400 3000 3000 Line-up width 2000 2600 2600 2400 3000 3000 Net weight (kg approx.) 1540 1940 2240 1730 2130 2430
3D4 + 4R8i Control & I/O cubicle 400 400 400 400 400 400 600 600 600 600 Load switch- Air circuit disconnector breaker Supply unit 800 800 800 800 800 800 Inverter unit (1) 600 600 600 600 600 600 400 400 400 Common motor terminal cubicle Inverter unit (2) 600 600 600 600 600 600 Shipping split widths 2400 3000 3000 2800 3400 3400 Line-up width 2400 3000 3000 2800 3400 3400 Net weight (kg approx.) 1870 2270 2570 2060 2460 2760
3D4 + 5R8i Control & I/O cubicle 400 400 400 400 400 400 600 600 600 600 Load switch- Air circuit disconnector breaker Supply unit 800 800 800 800 800 800 Inverter unit (1) 800 800 800 800 800 800 400 400 400 Common motor terminal cubicle Inverter unit (2) 600 600 600 600 600 600 Shipping split widths 2600 3200 3200 3000 3600 3600 Line-up width 2600 3200 3200 3000 3600 3600 Net weight (kg approx.) 2020 2420 2720 2210 2610 2910
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
137
3D4 + 6R8i Control & I/O cubicle 400 400 400 400 400 400 600 600 600 600 Load switch- Air circuit disconnector breaker Supply unit 800 800 800 800 800 800 Inverter unit (1) 800 800 800 800 800 800 600 600 600 Common motor terminal cubicle Inverter unit (2) 800 800 800 800 800 800 Shipping split widths 2800 3400 3400 3400 4000 4000 Line-up width 2800 3400 3400 3400 4000 4000 Net weight (kg approx.) 2170 2570 2870 2390 2790 3090
4D4 + 6R8i Control & I/O cubicle 400 400 400 400 400 400 600 600 600 600 Load switchdisconnector Air circuit breaker Supply unit 600 + 600 600 + 600 600 + 600 600 + 600 600 + 600 600 + 600 Inverter unit (1) 800 800 800 800 800 800 600 600 600 Common motor terminal cubicle Inverter unit (2) 800 800 800 800 800 800 Shipping split widths 3200 3800 3800 3800 4400 4400 Line-up width 3200 3800 3800 3800 4400 4400 Net weight (kg approx.) 2520 2920 3220 2740 3840 4140
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
138
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
139
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
140
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
141
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
142
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
143
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
144
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
145
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
146
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
147
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
148
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
149
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
150
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
151
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
152
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
153
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
154
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
155
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
156
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
157
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
158
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
159
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
160
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
161
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
162
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
163
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
164
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
165
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
166
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
167
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
168
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
169
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
170
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
171
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
172
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
173
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
174
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
175
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
176
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
177
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
178
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
179
400 mm
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
180
600 mm
Dimensions
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
181
Resistor braking
What this chapter contains
This chapter describes the resistor braking options of the ACS800-07.
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
182
Chopper/Resistor combinations Technical data The following table contains the technical data of some chopper/resistor combinations.
R (ohm) Pbrmax (kW) Pcont (kW) Imax (A) Duty Cycle (10/60 s) Pbr (kW) 287 575 862 287 575 862 287 575 862 Irms (A) 444 888 1332 355 710 1065 355 514 771 Duty Cycle (1/5 min) Pbr (kW) 167 333 500 167 333 500 167 333 500 Irms (A) 257 514 771 206 412 618 206 298 447
UN
Chopper(s)
Resistors
1 NBRA-659 400 V 2 NBRA-659 3 NBRA-659 1 NBRA-659 500 V 2 NBRA-659 3 NBRA-659 1 NBRA-669 690 V 2 NBRA-669 3 NBRA-669
UN = Nominal voltage R = Resistance of specified resistors (per chopper) Pbrmax = Maximum short-term (1 min every 10 mins) braking power Pcont = Maximum continuous braking power Imax = Maximum peak current Pbr = Braking power for the specified duty cycle Irms = Corresponding RMS current
Brake resistors Technical data The following table contains the technical data for the resistors supplied by ABB.
Type SAFUR125F500 SAFUR210F575 SAFUR200F500 SAFUR180F460 UN R ER PRcont UN (V) 500 575 500 460 R (ohm) 4.0 3.4 2.7 2.4 ER (kJ) 3600 4200 5400 6000 PRcont (kW) 9.0 10.5 13.5 15.0
Nominal voltage Resistance Short energy pulse that the resistor assembly will withstand each 400 seconds Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER dissipates in 400 seconds.
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
183
3. Check the resistors selection. The energy generated by the motor during a 400second period must not exceed the heat dissipation capacity ER.
If the ER value is not sufficient, it is possible to use a four-resistor assembly in which two standard resistors are connected in parallel, two in series. The ER value of the four-resistor assembly is four times the value specified for the standard resistor.
Custom resistors Resistors other than the standard resistors can be used provided that: the resistance is not lower than with the standard resistors WARNING! Never use a brake resistor with a resistance below the value specified for the particular drive / brake chopper / resistor combination. The drive and the chopper are not able to handle the overcurrent caused by the low resistance. the resistance does not restrict the braking capacity needed, i.e., Pmax < where
Pmax UDC maximum power generated by the motor during braking voltage over the resistor during braking, e.g., 1.35 1.2 415 VDC (when supply voltage is 380 to 415 VAC), 1.35 1.2 500 VDC. (when supply voltage is 440 to 500 VAC) or R 1.35 1.2 690 VDC (when supply voltage is 525 to 690 VAC). resistor resistance (ohm) UDC R
2
the heat dissipation capacity (ER) of the resistors is sufficient for the application (see step 3 above).
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
184
Calculating the maximum braking power (Pbr) Braking energy transferred during any ten minute period must be less than or equal to the energy transferred during the reference braking cycle. The braking power must not exceed the rated maximum value Pbrmax. 1. 2. n Pbr tbr n Pbr tbr < Pbrmax 60 s Pbr < Pbrmax = Number of braking pulses during a ten minute period = Maximum allowed braking power (kW). = Braking time (s)
Example 1 Duration of a braking cycle is 30 minutes. The braking time is 15 minutes. Result: If the braking time exceeds 10 minutes, the braking is considered continuous. The allowed continuous braking power is 10% of the Maximum Braking Power (Pbrmax). Example 2 Duration of a braking cycle is three minutes. The braking time is 40 seconds. 1. Pbr Pbrmax Pbr < Pbrmax 60 s = 0.375 Pbrmax 4 40 s
tbr
2.
O.K.
Result: The maximum allowed braking power for the cycle is 37 % of the rated value given for the reference cycle.
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
185
Example 3 Duration of a braking cycle is three minutes. The braking time is 10 seconds. 1. Pbr Pbrmax Pbr < Pbrmax 60 s = 1.5 Pbrmax 4 10 s
tbr
2.
Not allowed.
Result: The maximum allowed braking power for the cycle is equal to the Maximum Braking Power (Pbrmax) given for the reference cycle.
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
186
Note: For the ENABLE input wiring, use cable rated as follows: twisted pair (screened type recommended) rated operating voltage between a core and earth (U0): 750 V insulation test voltage > 2.5 kV
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
187
The following is a wiring diagram example of the resistor connection. Brake chopper
X1 R+ R 1 2
R+
Brake resistor
Resistor braking
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]