Qdoc - Tips - Dst4600a User Manual
Qdoc - Tips - Dst4600a User Manual
A
0
0
6
4
T
S
D
Product:
DST4600A
Revision
Revision Date Pages Notes
4. Faults ...................................
.....................................................
....................................
....................................
....................................
....................................
........................
...... 17
4.1 LIST OF F
XX C ODES
ODES ....................................
......................................................
...................................
...................................
.................................
............... 18
4.2 ALARMS ..................................
....................................................
....................................
....................................
....................................
..................................
................ 18
4.2.1 Low oil pressure
pressure ..................................
.....................................................
....................................
...................................
..............................
............ 18
4.2.2 High Cooling Water Temperature .......................................................................... 19
4.2.3 Starting Battery Fault ............................................................................................. 19
4.2.4 Minimum Fuel Level in the Tank ............................................................................ 19
4.2.5 Maximum Fuel Level in the Tank ........................................................................... 20
4.2.6 Auxiliary Alarm
Alarm ..................
......... ..................
..................
..................
..................
..................
..................
..................
..................
..................
.............
.... 20
4.2.7 KR close
close failure.........
failure...........................
....................................
....................................
....................................
....................................
.....................
... 20
4.2.8 KG close
close failure
failure ....................................
......................................................
....................................
....................................
.............................
........... 21
4.2.9 Max power
power ....................................
......................................................
....................................
....................................
....................................
.................... 21
4.3 DEACTIVATIONS .....................................
.......................................................
....................................
....................................
....................................
.................... 21
4.3.1 Generator’s Voltage Under Minimum Threshold (“UNDERVOLTAGE”) ........... ...... 21
4.3.2 Generator’s Frequency Under the Minimum Threshold (“UNDERFR (“ UNDERFREQUENCY” EQUENCY”)) . 21
4.4 BLOCKS ...................................
.....................................................
...................................
...................................
....................................
..................................
................ 22
4.4.1 Emergency
Emergency STOP..................................................
....................................................................
....................................
..............................
............ 22
4.4.2 Manual Stop in AUTO ............................................................................................ 22
4.4.3 Fuel END ...................................
.....................................................
....................................
....................................
....................................
......................
.... 22
4.4.4 Low Oil Pressure
Pressure ....................................
......................................................
....................................
....................................
...........................
......... 22
4.4.5 High Cooling Water Temperature .......................................................................... 23
4.4.6 Non-masked Auxiliary Block .................................................................................. 23
4.4.7 Masked Auxiliary Block .......................................................................................... 23
4.4.8 Generator’s Voltage Over the Maximum Threshold (“OVERVOLTAGE”) (“OVERVOLTAGE”) ............... ......... ...... 24
4.4.9 Generator’s Frequency Over O ver the Maximum Threshold (“OVERFREQUENCY”) (“OVERFREQUENCY”)..... 24
4.4.10 Engine Over speed ................................................................................................ 24
4.4.11 Overload
Overload ....................................
......................................................
....................................
....................................
...................................
......................
..... 24
4.4.12 Short
Short circuit
circuit..................................................
...................................................................
....................................
....................................
......................
..... 25
4.4.13 Belt Break ..................................
....................................................
....................................
....................................
....................................
......................
.... 25
4.4.14 Operating Speed not reached ................................................................................ 25
4.4.15 “OVERCRA
“OVERCRANK” NK”...................................
.....................................................
....................................
....................................
...............................
............. 26
4.4.16 Hardware
Hardware fault fault ....................................
......................................................
....................................
....................................
...............................
............. 26
4.4.17 Shutdown
Shutdown Failure
Failure ..................................
....................................................
....................................
....................................
.............................
........... 26
4.4.18 Energy
Energy Inversion
Inversion...................................................
....................................................................
....................................
................................
............. 26
4.4.19 Inhibition of the generator set Use ......................................................................... 26
4.4.20 Engine not in thresholds when KG closed................. ........ ..................
..................
..................
..................
..................
......... 26
5. Operating
Operating Sequence
Sequence ..................................
....................................................
....................................
....................................
....................................
.................... 27
1.1 Definitions
Throughout this document the word “BLOCK” is used to indicate an alarm that makes
generation function impossible and causes the automatic generator shutdown with the
emergency procedure (without cooling cycle).
The word “DEACTIVATION” is used to indicate an alarm that makes generation function
impossible and causes the automatic generator shutdown with the normal procedure (with
cooling cycle).
The word “ALARM” is used to indicate a warning that requires an operator action but doesn’t
require the automatic generator shutdown.
Throughout this document the words “SOFTWARE” and “FIRMWARE are used as
synonymous if they are referred to the board firmware.
Software code is reported in short format on the board back panel. It is in the form xx.yy.uu,
where xx is the firmware short identified code, yy is the major version number and uu is the
minor version number.
The complete SW identification number for the DST4600A for asynchronous engines is
EB0220029yyuu reported in back panel as (for example) 29.07.39.
The minor version is consistent between the two types of software ( uu field is kept aligned).
The major version for the DST4600A/P is increased by 5 respect the standard version.
The major version for the DST4600A for asynchronous engines is increased by 7 respect the
standard version.
Thus the SWs 08.00.39, 12.05.39 and 29.07.39 share the same main features and
functions.
1.2 Symbols
In this document a vertical bar on the right margin or a gray background indicates that the
chapter or the paragraph has been amended with respect to the last document’s version.
This manual is valid starting from SW 00.38 release; for previous SW release, please check
manual version 09 or previous. Otherwise use this version very carefully checking document
version notes on page ii.
If the SW version number is greater than this, this manual maybe nevertheless consistent;
please in case check for new document release.
2. Front Panel
Substantially, the panel is divided into the three operational areas as described below.
It corresponds to the right bottom part of the front panel. It groups all the available control
units. It includes:
• A button (“START”) for the manual starting of the generator set engine. The manual start
can be executed only with the key selector on MAN. This button, alone or combined with
the others, can also take other meanings during some particular procedures not directly
related with the management of the generator set (programming, calibration, etc.).
• A button (“STOP”) for the manual shutdown of the generator set engine. The manual
shutdown can be executed only with the key selector on MAN. By pressing this button
with the key selector in other working positions (AUTO or TEST) the engine shutdown will
be executed through the emergency procedure (see the faults management). This
button, alone or combined with the others, can also take other meanings during some
particular procedures not directly related with the management of the generator set
(programming, calibration, etc.).
• A button (bearing the symbol of a siren, from now on called “MODE / ACK”) for the faults’
acknowledgement and the consequent muting of the audible alarm and to reset the
alarms, too. This button, alone or combined with other buttons, can also have other
meanings.
• Two buttons (bearing the symbols of two arrows, from now on called “F1” and “F2”) used
to select what to show on the display “MULTIFUNCTION” (see par .2.1.1.2). These
buttons, alone or combined with other buttons, can also have other meanings.
• A key selector allowing to select the board’s controlling mode of the generator set’s
operation: OFF/RESET - PROGRAMMING - MANUAL - AUTOMATIC – TEST. The key
can be extracted only in the positions OFF/RESET and AUTOMATIC. Here follows a
short description of the operating modes:
a) OFF/RESET: in this mode the board is on, but all the functions for the control and
the running of the generator set are disabled. It is used in all the cases in which
the intervention of the generator set is not required (i.e. in order to prevent
unnecessary automatic interventions during the closing periods of a factory etc.)
and above all as a safety position during the maintenance. Actually, when the
selector is on OFF/RESET, the control device is completely disabled and
therefore the generator set cannot intervene in the event of mains voltage failure.
The mains contactor is forced at work therefore the users are powered by the
mains (if it’s present). The monitoring of the mains status, of the engine and of the
generator are anyway enabled and the indicators belonging to the “functional
status and measurements” area mirror such conditions.
By switching the selector to “OFF/RESET” the following operations are executed:
When the board is in the “OFF/RESET” mode the direct current consumption is
reduced to a minimum since the displays show only a central dash, while all the
signals are off except the indicator “KR” (turned on, only for SW type 08) as well
as the indicators “ENGINE RUNNING”, “GENERATOR LIVE” and “MAINS LIVE”
showing respectively the engine, the generator and the mains status (normally
only the indicator “MAINS LIVE” is turned on).
c) MAN. (MANUAL): in this mode the board is set to manage the manual running of
the generator set. In short:
1) The procedures for the manual starting and shutdown of the engine are
enabled, while those for the automatic starting and shutdown of the engine
are disabled (therefore the board will never automatically start the engine).
When the selector is switched on “MAN”, the engine keeps its status
(running/dead).
d) AUTO (AUTOMATIC): this is the normal operating mode of the board. In this
mode the engine is automatically started/stopped in case of mains failure or at
regular intervals to keep it efficient. In the same way, the power changeover is
automatically switched on mains or on the generator according to their status.
Warning: when the selector is on this mode any maintenance of the
generator set and/or on the electric switchboard is forbidden.
e) TEST: this mode allows starting the generator set keeping all the functions for the
management of the changeover as in the AUTOMATIC mode. By switching the
selector on TEST, a series of starting attempts will be executed (automatically,
the operator will not have to press “START”), independently from the mains
status. In the same way, by quitting the TEST mode (for the AUTOMATIC mode),
if the mains is present the engine will stop (with the usual cooling cycle). Normally,
in the TEST mode the users are switched on the mains. They can be switched on
the generator set (if it is ready to supply) only in the following two cases:
1) Mains failure
2) Explicit command of the operator (in order to test the entire system, not only
the generator set).
For the SW version 12 (/P boards), KG is activated in the TEST mode if the
generator is ready to supply power. It can be deactivated by manual command.
In this area is located a digital display (called display “MULTIFUNCTION”) showing the
measurements of various quantities that can be selected through the buttons “F1” and “F2”
and indicated to the operator through the corresponding indicators.
• “DATA – HOURS COUNT / START COUNTER”: by selecting this function the display
“MULTIFUNCTION” normally shows the number of operating hours of the generator set
engine. The hours count doesn’t consider if the users ar e connected to the generator but
the condition of engine running only. By keeping pressed the button “MODE / ACK”, you
can view the number of starts of the engine (the number refers to the performed starts,
not to the start attempts). As soon as “MODE / ACK” is released the engine’s operating
hours can be viewed again. The corresponding indicator is turned on when the display
shows the engine’s operating hours, while it flashes when the number of starting
attempts is viewed. If the number of starts of the operating hours exceeds 999, the
number is divided by 10 and displayed with a decimal point on the right digit.
It is possible to program (through the parameter P50) a number of operating hours for
the engine after which maintenance has to be carried out. When the hour-counter
reaches or exceeds such parameter (NB: it is set by tens of hours) in order to signal the
maintenance request the number of operating hours will flash alternatively to the
message “SER” (with the selector on MAN, AUTO and TEST the function to view the
operating hours is automatically selected after 60 seconds without pressing any button).
This condition stays until the hour-counter is reset or until the value of the Parameter
P50 is changed (by increasing it or by forcing it to 0). Both the counters are reset with a
common operation (they cannot be reset separately):
By pressing the “F1” and “F2” select the “DATA – HOURS COUNT / START
COUNTER” function
Press at the same time “MODE / ACK” and “STOP” for 5 seconds. After 5
seconds the counters will be reset. The display does not indicate the reset in any
way; therefore the operator has to count the 5 seconds.
There is another hour counter. It cannot be cleared in any way. Its value is not shown on
the DST4600A front panel, but can be read by the serial port.
• “BATTERY VOLTAGE (V) / APPARENT POWER (kVA)”: when this function is selected,
the display “MULTIFUNCTION” indicates the voltage measured on the battery (terminals
47-48 or 49-48) (in Volts with a decimal). If POWER DISPLAY FUNCTION is active, the
display indicates the apparent power (in this case, the measure could blink if at least one
of the current measure circuits of the board is saturated, that means that the current is
higher than the TA nominal value).
• “OIL PRESSURE (bar)”: when this function is selected, the display “MULTIFUNCTION”
shows the engine’s oil pressure measured on the analogue sensor (terminal 42) (in Bars
with a decimal). If the sensor isn’t configured (P47=0), the display will show three
dashes (“---“).
• “FUEL LEVEL (%)”: when this function is selected, the display “MULTIFUNCTION”
shows the fuel level in the tank measured on the analogue sensor (terminal 45)
(percentage). If the sensor isn’t configured (P48=0), the display will show three dashes
(“---“).
Under particular conditions, during the operation the display “MULTIFUNCTION” can show
messages having no relation with the selected function. In this situation, all indicators related
to display “MULTIFUNCTION” are turned off. In detail, the messages are the following:
• “STA” during a starting attempt, that is when the output “START” (terminal 20) is
activated.
• “PRE” during the preheating phase preceding the starting attempt in diesel engines, that
is when the “PREHEAT OUTPUT” (“AUX OUTPUT 1”, terminal 15) is activated.
• “SER” signals that the generator set requires field service maintenance.
• “F01” in presence of the deactivation for generator’s voltage under the minimum
threshold (“UNDERVOLTAGE”).
• “F02” in presence of the block for generator’s voltage over the maximum threshold
(“OVERVOLTAGE”).
• “F03” in presence of the deactivation for generator’s frequency under the minimum
threshold (“UNDERFREQUENCY”).
• “F04” in presence of the block for generator’s frequency over the maximum threshold
(“OVERFREQUENCY”).
• “F07” in presence of block for “STOP” pressed in the AUTOMATIC or in the TEST
mode.
• “F40” if the “engine in threshold” signal is missing while KR is closed (for asynchronous
engine version only)
During the shutdown cycle the display “MULTIFUNCTION” alternates, every two seconds, the
message “STO” with the message it would display if the shutdown cycle was not in progress.
In this area (right top of the front panel) is displayed the status of the generator set and of the
mains. The following signals are provided:
• Indicators “KG” and “KR” (green): indicate the status of the contactors managing the
power changeover. The indicator “KR” is not present for SW type 12 (/P boards). If the
green indicator is turned on the corresponding external connected contactor is closed.
The external connected contactors can never be both closed, while they can be both
open during the switching. The default configuration shows the KG and KR command
status, not the actual status. However it is possible to configure the board to use two
inputs to monitor the status:
When this function is enabled the indicators “KG” and “KR” work in a different way:
• Flashing at 50% duty cycle: the contactor is open but the command is on
• Flashing at 90% ON: the contactor is closed but the command is off
• Indicator “ENGINE RUNNING” (green): it indicates the status of the engine of the
generator set. It takes the following meanings:
Flashing: engine cooling (this condition occurs only in the AUTOMATIC mode).
Flashing: The generator is living but some of the parameters (voltages on one or
more phases or frequency) are not within the programmed tolerance limits,
therefore the users cannot be switched on it.
Turned on: The generator is living and all its parameters are within the programmed
tolerance limits, therefore it is possible to switch the users on it.
• “MAINS LIVE” indicator (green): It indicates the mains status. It takes the following
meanings:
Flashing: the mains is present but the voltage on one or more phases is not within
the limits of the programmed tolerance thresholds, therefore if the users are
currently switched on the generator, they will have to stay on it.
Turned on: the mains is present and within the programmed tolerance limits,
therefore the users can be switched on it.
NB: the board has an input (“MAINS SIMULATION”, terminal 24) that can be used to
inhibit the automatic operation of the genset. If this digital input is activated,
independently from what has been acquired with the mains sensor, the engine is not
automatically started.
Furthermore, there are two digital displays (each of them having 3 digits) to show the electric
quantities measured on the generator. The left display (called display “V”) shows the
generator’s voltages (phase-to-phase for three-phase systems, phase-to-neutral for single-
phase systems) Volts. The right one (called display “A”) shows the phase currents in
Amperes. The view format changes according to the set TA ratio (P17):
P17 < 10: the currents are displayed with two decimals
P17 >=10 and <100: the currents are displayed with one decimal
P17 >=100: the currents are displayed without any decimal. If the current measurement
exceeds 999 Ampere, it is displayed divided by 10 and the indicator “X10” (yellow),
located over the display “A” turns on.
If the current measured (in the board side of TA) is higher then 5 Amperes, the display “A”
blinks to indicate lower measure precision.
If the board is supplied with the power measurement option it is possible to view the power
factor (indicated by “POWER FACTOR (cos φ)”) on the display “V” and the active power
(indicated by “ACTIVE POWER (kW)”) on the display “A” (POWER DISPLAY FUNCTION).
Furthermore, it is possible to view the energy meter (kWh on the display “A” and MWh on the
display “V”). All these measures will blink if at least one of the current measurement circuits
of the board is saturated (see description at the previous paragraph).
Three yellow indicators (called “L1/L2”, “L2/L3” and “ L3/L1”) located between the two displays
are also present. They indicate to which phase the measurements displayed in any moment
refer. On single-phase systems the voltage and the current of the only present phase are
always displayed, therefore the indicator “L1/L2” is always turned on, while the “L2/L3” and
“L3/L1” are always off. On three-phase systems, the three phases are periodically alternated
every 4 seconds on the displays and the indicators “ L1/L2”, “L2/L3” and “L3/L1” show the
current phase. However, it is possible to force the display of one phase only even on three-
phase systems by pressing at the same time the buttons “F1” and “F2” when the displays
This area (top left of the front panel) contains all the indicators for the generator set’s
common faults Here follows a short description of the indicators, for a more detailed
description of all the faults, see paragraph 6. At the fault acquisition, the corresponding
indicator flashes, by pressing the “MODE / ACK“ button it stops flashing to indicate that the
operator acknowledge it.
• Indicator “TEMPERATURE” (red): it indicates the alarm or block status due to the high
cooling water temperature. The indicator flashes at a different speed to indicate an alarm
(more quickly) or a block (more slowly, as for all other blocks). It can be acquired from:
• Indicator “LOW OIL PRESSURE” (red): it indicates the alarm or block status due to the
low oil pressure of the engine. The indicator flashes at a different speed to indicate an
alarm (more quickly) or a block (more slowly, as for all other blocks). It can be acquired
from:
• Indicator “MAX LEVEL” (yellow): It indicates the alarm status due to the maximum fuel
level in the tank. It can be acquired from:
• Indicator “OVERCRANK” (red): It indicates the block status due to a failure in the
automatic start of the engine. It is produced by the operating sequence in the
AUTOMATIC mode.
• Indicator “DISCHARGED” (yellow) it indicates the alarm status due to the charge level of
the starting battery of the generator set. Such battery also powers the board DST4600A.
The alarm is produced if the battery voltage exceeds the tolerance limits:
• Indicator “MIN LEVEL” (yellow): it indicates the alarm status due to the minimum fuel
level in the tank. It can be acquired from:
• Indicator “OVERSPEED” (red): it indicates that the engine is running too fast and it could
damage the alternator or the engine itself. It can be acquired from:
• Indicator “NO FUEL” (red): it indicates the block due to the end of the fuel in the tank. It
can be acquired from:
• Indicator “EMERGENCY STOP” (red): it indicates the block that follows the pressing of
the emergency button. It can be acquired from:
Digital input “EMERGENCY STOP” (terminal 03). NB: the block is enabled when
the digital input is not activated.
3. Start Initialization
As soon as the board is powered it executes the following operations:
• Lamp Test: during this phase it turns on all the indicators in the front panel and it shows
888 (with the decimal points turned on) on the three displays. This operation lasts two
seconds and allows the identification of any failure in the front panel that could involve
visual signaling of a fault.
• Display the software level. The display “MULTIFUNCTION” shows the message “REL”
(release). The display “V” shows the main version; the display “A” shows the secondary
version. For instance, for a software level 1.23 the display “V” will indicate “1” and the
display “A” will indicate “23”. In this phase all the indicators on the front panel are turned
off. This phase lasts one second.
In the event of data errors in the non- volatile memory, the display “MULTIFUNCTION” shows,
in place of “REL” the message:
After the execution of the above-mentioned operations, the board starts executing the work
sequences, according to the position of the key selector.
• Alarms: faults that are not immediately dangerous for the generator set and for its load,
and that therefore allow the generator set to keep on working. They require an operator’s
intervention otherwise they could cause a more dangerous fault.
• Deactivations: these faults are more dangerous for the load that needs to be switched
immediately on the mains (even if there’s a mains failure) but they aren’t immediately
dangerous for the generator set and/or for the operator: the generator set will have to be
stopped in any case but it can be stopped with the standard procedure (cooling cycle,
etc.).
• Blocks: these faults can damage the generator set and sometimes the load, too. When
they are activated, the load is imm ediately switched on the mains (even if there’s a mains
failure) and the engine is stopped through the emergency procedure (without the cooling
cycle).
Any fault can be activated only if the key selector is on MAN, AUTO or TEST.
The alarms can always be activated. There may be more than one alarm at the same time.
The deactivation can be activated if in the moment the cause occurs no deactivation or block
is present, while one or more alarms can be present. There cannot be two deactivation at the
same time.
The blocks can be activated only if in the moment the cause occurs no other block is present,
while deactivation and/or alarms can be present. As a principle, there cannot be two blocks at
the same time, but actually, the blocks “NO FUEL”, “EMERGENCY STOP” and “MANUAL
STOP IN AUTO” are an exception since they can be activated even in presence of other
blocks
When a fault occurs, whatever be its category, the audible alarm is activated (“ALARM
OUTPUT”, terminal 16) as well as the corresponding visual signal. Such signal can be an
indicator on the front panel (fault area) or a message “FXX” on the display
“MULTIFUNCTION”. In the case of an indicator it flashes.
The audible alarm stays active for the time programmed through the parameter P54 than it
turns off automatically (if P54 is equal to 999 the siren does never turn off automatically, if
P54 is equal to 0 the siren never turns on), while the visual signal keeps on flashing until the
operator doesn’t ”recognize” it.
The “recognition” involves the pressing of “MODE / ACK”. As a consequence, the signal
stops flashing and stays turned on and the audible alarm (if still active) is disabled.
Once the operator has recognized the alarms, they are automatically cancelled by DST4600A
when the corresponding cause ceases to exist. If the alarm is cancelled, the visual signal
turns off, too.
While the blocks and deactivation can be cancelled only by switching the key selector to
“OFF/RESET”.
Code Description
F16 Short-circuit
F40 Engine not in thresholds when KG closed (only for asynchronous engine
version)
4.2 Alarms
Starting from revision 08.00.24 (not available for /P version and for asynchronous engine
version). Setting bit 5 of P61 at 1, it is activated a function that switch the load to Generator
set, keeping it running, in case of F13 alarm.
Starting from revision 08.00.38, this block may be masked if mains is not present by using bit
one of parameter P79.
4.3 Deactivations
4.4.11 Overload
Starting from revision 08.00.38, this block may be configured as a “deactivation” by using bit
0 of parameter P79.
This BLOCK is available from the SW release 08.00.33. Starting from revision 08.00.38, this
block may be configured as a “deactivation” by using bit 0 of parameter P79.
• P04: generator set intervention delay for mains voltage failure (s)
• P05: Mains restoration delay (closing mains contactor from mains present) (s)
Mains is considered “alive” if the voltage on all the existing phases is over of the “alive” mains
threshold. It is considered “dead” if the voltage on at least one phase is under the “dead”
mains threshold. If no phase is under the “dead” mains threshold but at least one of them is
under the “alive” mains threshold, the mains keeps the dead/alive status it previously had
(hysteresis). If the voltage on at least one phase is over the “OVERVOLTAGE” threshold, the
mains is considered “alive out of window”. Of course the parameter P15 must be over the
“alive” mains threshold.
In addition, there is the digital input “MAINS SIMULATION” (terminal 24). When such input is
enabled, the board wait for time T2 is elapsed before mains is considered “present”.
Furthermore, if the board is set to work with an external mains sensor (using only the “MAINS
SIMULATION” input and ignoring the m ains voltages), when the input “MAINS SIMULATION”
is not enabled the mains is immediately considered “absent”. Depending on the SW versions,
the delay times related to this input are different.
• Starting from SW version 08.00.22 the parameters P66 and P67 are used to set the
Generator set intervention and shutdown on “MAIN SIMULATION” deactivation and
activation
• Starting from SW version 08.00.09 to SW revision 08.00.21 the same parameters used
for the delay of the mains control are used (P.04 and P05).
• Before 08.00.09 version there were no delay time related to this function.
• Absent: “dead” or “alive out of window” from a period of time over or equal to T1
(“MAINS LIVE” indicator turned off)
• Outgoing: “dead” or “alive out of window” from a period of time under T1 (“MAINS
LIVE” indicator flashing)
The T1 and T2 times change according to the position of the key selector and if the engine is
running or dead:
SELECTOR ENGINE T1 T2
1
AUTO-TEST Dead P04 P05
As you can see, the transitional mains failure is cancelled (2 seconds) with the engine
running. In such conditions, as soon as a mains failure occurs, if the selector is on AUTO the
users are switched on the generator.
In the same way, the transitional mains restoring is cancelled (0 seconds) only if the selector
is in OFF-PROG-MAN, to avoid the engine starting or the users’ switching on the generator
set if going back to AUTO during the mains restoring.
1
Unusual case: in AUTO mode the engine is dead during the transitional mains restoration only in the event of starting
failure.
2
With selector on OFF-PROG the engine is not running.
If the voltage on at least one of the phases is over the “OVERVOLTAGE” threshold, the
generator is considered “alive out of window”. Of course, the parameter P14 must be set in
order to be over the “alive” mains threshold.
If the voltage on at least one of the phases is under the “UNDERVOLTAGE” threshold, the
generator is considered “alive out of window”. Of course, the P13 parameter must be set in
order to be over the “alive” mains threshold and over the parameter P14.
If the generator is alive but its frequency is under the “UNDERFREQUENCY” threshold, the
generator is considered “alive out of window”. Of course, the parameter P11 must be under
the parameter P12.
• Absent: “dead” or “alive out of window” from a period of time over or equal to T1
The engine is defined as “running” if at least one of the following requirements is met:
• Generator’s frequency over the threshold specified through the parameter P42 (only if
enabled with bit 6 of the parameter P49)
• Voltage on all the generator’s phases less than 80 V (not configurable). Starting from
version 08.00.23, is used the value of P03 (the default value is changed to 80V).
• Voltage at the D+WL input (terminals 39..40) over the threshold (10 or 20 V according to
the nominal voltage of the battery), only if enabled with bit 4 of the parameter P39.
3
On the DST4600A board this time act only if the generator set contactor is open. If it is closed, wait until the alarms
management starts the F01.F04 alarm and then execute the emergency stop cycle.
The engine is defined as “dead” if all the following requirements are met for at least five
seconds:
• Generator’s frequency under the threshold specified by the parameter P43 (only if
enabled with bit 6 of the parameter P49)
• Voltage on at least one generator’s phases less than 80 V (not configurable). Starting
from version 08.00.23, is used the value of P03 (the default value is changed to 80V).
• Voltage at the D+WL input (terminals 39..40) under the threshold (3 or 6 V according to
the nominal voltage of the battery), only if enabled with bit 4 of the parameter P39.
It is a series of many conditions. The most important one is the absence of any block or
deactivation. The remaining conditions depend on the key selector status:
MAN
AUTO
c) Periodical Test (if configured through the parameters P18 and P19)
TEST
The immediate stop request is given by at least one of the following conditions:
a) STOP button
The request of stop with cooling cycle is given by at least one of the following conditions:
The control board can be set to work with engines equipped with an excitation shutdown
system (usually electromagnet with control on the engine stop lever or electro-valve
interrupting the fuel supply), or dropout shutdown ones (standard versions - usually N.C. fuel
supply electro-valve or electro-magnet unlocking the engine stopping condition).
In the first case (EXCITATION SHUTDOWN), the stopping control “STOP SOLENOID”
(terminal 18) is activated for the time set with the parameter P09. If the VOLVO engine EDC
function is enabled (bit 3 of P.61) is enabled, the “STOP SOLENOID” is driven for a fixed
time of 2 seconds. The command is activated at the beginning of the shutdown phase, stays
active for all the set duration and is disabled at the end of the same period.
In the second case (DROP-OUT SHUTDOWN), the stopping command takes the meaning of
permission to the engine’s running, “FUEL SOLENOID” (terminal 22) is activated with the
engine starting command and stays active until the beginning of the stopping command.
In the MANUAL mode the board DST4600A can receive the engine start/shutdown
commands and those for the power changeover from the buttons located on the front panel.
When the selector is brought to MANUAL the following operations are executed:
• Keeping of the contactors status. From revision 00.00.39, it is possible to configure the
board for switch to mains (bit 2 of P79 parameter).
• If the engine is cooling, such phase is cancelled and the engine is kept running.
To start the generator set in the MANUAL mode press the START button and keep it pressed
until the engine is running. The START button is not accepted in presence of deactivation
and/or blocks. As a response to this command the board execute the following operations:
1. It enables the “FUEL SOLENOID” output (terminal 22). Such output is automatically
removed during the stop cycles or if for 20 seconds the engine is dead.
2. It disables the “STOP SOLENOID” output (terminal 18) (it should already disabled except
if the starting request occurs during a stop cycle), used for the dropout shutdown. If
engine is already running, the procedure stops here.
3. If the preheat function for diesel engines is enabled, it activates the “AUX OUTPUT 1”
(terminal15) for the time set with the parameter P20 (if such time is equal to 0 the
preheat function is disabled). In this phase the display “MULTIFUNCTION” shows the
message “PRE”. At the end of this phase it disable the output and passes to the phase 4
(until SW version 08.00.11 the output “FUEL SOLENOID” were activated only at the end
of this phase).
The activation sequence is always: “FUEL SOLENOID” (terminal 22), “AUX OUTPUT 1”
(PREHEAT OUTPUT) (terminal 15) and then “START” (terminal 20). Thus, it is possible to
use this feature to drive an auxiliary output that requires to be activated before the actual start
command (use parameter P38 to configure the delay time).
To stop the engine in the MANUAL mode press the STOP button. Unlike for the DST4600, it
is not necessary to keep the STOP button pressed until the shutdown has taken place:
simply press it for a second and the board execute a complete shutdown cycle. That is, it
disables the “FUEL SOLENOID” output and it enables the “STOP SOLENOID” one (terminal
18) for the time set with the parameter P09 (if it is enabled the VOLVO engine EDC this time
is fixed and of 2 seconds).
The MANUAL mode doesn’t foresee any shutdown failure block, except for the automatic
shutdown cycles following blocks or deactivation.
Normally, with the board in the MANUAL mode the users are switched on the mains. Only if
the engine is running, if the generator is “present” and the delay before the supply has
passed - P06 (or if the temperature exceeds the minimum threshold set with P55), the
operator has the opportunity to switch them on the generator. To do that, press at the same
time “MODE / ACK” and “F1” for one second (such combination is highlighted on the front
panel of the board with the indication “MANUAL CHANGE-OVER”. This command works as
“toggle”, that is, if the operator gives again the order the users are again switched on the
mains.
When the users are switched on the generator set, they are automatically switched on the
mains if the generator gets “absent” or in presence of deactivations and/or blocks.
The control sequence of the generator set in the AUTOMATIC mode develops as follows:
In this phase the engine is dead. The board waits until the mains get “absent” or for at least
one of the other start requests (see par .5.1.1).
The board tries to start automatically the engine. The number of starting attempts to execute
can be programmed through the parameter P10. If, after those attempts, the engine doesn’t
start, the start failure block is activated (“OVERCRANK”). Furthermore, the duration of the
starting impulse can be set (parameter P08) as well as the delay between two attempts
(parameter P38).
1. The “FUEL SOLENOID” output (terminal 22) is enabled. Such output is automatically
removed during shutdown cycles or when the engine is dead for 20 seconds.
2. The “STOP SOLENOID” output (terminal 18), used for the excitation shutdown, is
disabled (it should already be disabled unless the starting request occurs during a stop
cycle). If the engine is already running, the pr ocedure stops here.
3. If the preheat function for diesel engines is enabled the “AUX OUTPUT 1” (terminal 15) is
enabled for the time set with the parameter P20 (if such time is equal to 0 the preheat
function is disabled). In this phase the display “MULTIFUNCTION” shows the message
“PRE”. At the end of this phase the output is disabled passing to phase 2.
4. The “START” output (terminal 20) controlling the generator set starter, is enabled. The
output is kept for the time set with the parameter P08 or until the engine running
recognition. In this phase the display “MULTIFUNCTION” shows the message “STA”. If
the engine gets started phase 6 will follow, otherwise phase 5 will follow (unless the
starting attempts have ended,
5. The “START” output is disabled and there’s a wait for with the duration set with the
parameter P38 During this phase the preheat function for diesel engines is enabled, as
well as the “AUX OUTPUT 1” (terminal15) and the display “MULTIFUNCTION” shows
the message “PRE”.
6. Engine running.
The activation sequence is always: “FUEL SOLENOID” (terminal 22), “AUX OUTPUT 1”
(PREHEAT OUTPUT) (terminal 15) and then “START” (terminal 20). Thus, it is possible to
use this feature to drive an auxiliary output that requires to be activated before the actual start
command (use parameter P38 to configure the delay time).
Starting from SW version 08.00.12, the activation sequence is always: “FUEL SOLENOID”
(terminal 22), “AUX OUTPUT 1” (PREHEAT OUTPUT) (terminal 15) and then “START”
(terminal 20). Thus, it is possible to use this feature to drive an auxiliary output that requires
to be activated before the actual start command (use parameter P38 to configure the delay
time). This sequence is valid also in manual mode.
Starting from SW version 08.00.38, the activation sequence is subjected to the engine
stopped or the shut down cycle completed conditions.
In this phase there’s a wait until the generator reaches the operating speed, that is, when the
voltages on all the phases and the frequency are within the programmed thresholds (see par.
5.1.2). If this doesn’t take place within the time set with the parameter P32, the block
“operating speed not reached” (F08) is activated and the engine will be stopped. In this
phase, if the voltage or the frequency exceeds the maximum thresholds, the corresponding
blocks are activated (F02 and F04).
This phase is just a wait to allow the lubrication and the heating of the generator set before
connecting it to the users. The following phase takes place as soon as one of the following
requirements is met:
After the time set with the parameter P06 has passed since the generator is in window.
If the temperature analogue sensor exists, if a minimum threshold for the supply
permission has been set (P55 different from 0) and if the temperature is over such
threshold.
In this phase the blocks and deactivations F01, F02, F03 and F04 are enabled, while the
block F08 is disabled.
Please, consider that the status of each contactor cannot be inverted from the prior
command before the time set through the parameter P41 is elapsed from the last command.
The boards waits until the mains gets “present” and all the other start requests get off (see
par .5.1.1). Further, the arising of new faults of the generator set is checked.
Please, consider that the status of each contactor cannot be inverted from the prior
command before the time set through the parameter P41 is lapsed from the last command.
The engine is kept running after the users’ switching on the mains for a time programmable
through the parameter P07. The reason is that the engine cools more quickly by running
without supplying then shutting it down.
• “STOP SOLENOID” output (terminal 18) disabled. If the VOLVO engine EDC function is
enabled (bit 3 of P61), the solenoid is driven only for two seconds but the board waits in
any case until P09 is elapsed.
At the end of the cycle, if the engine is still running, the shutdown failure block (“F21”) is
activated (anyway the STOP SOLENOID output will not be enabled).
Up to revision 08.00.38, the automatic shut down cycle could be aborted if a new start
request arises. In some situations, this caused a false F01 or F03 blocks. So, from revision
08.00.39 a new start request can be processed only when the engine is stopped or when the
shutdown cycle is terminated.
The sequence in the TEST mode is fundamentally the same of that in the AUTOMATIC
mode, with the following differences:
• The engine is started in any case, independently from the start requests.
• The users’ switching normally is executed only in case of mains failure. The operator can
force it with the same procedure used in the MANUAL mode.
• The engine is never stopped automatically, except for blocks and/or deactivations.
Therefore, the TEST mode can be used to test accurately the generator set without
disconnecting the users from the mains, but at the same time assuring the users’ power
supply from the generator set in case of mains failure.
If the option is present, the generator voltages’ and currents’ true r.m.s. are displayed in the
place of the corresponding values measured in the standard version, that is on the displays
“V” and “A”.
To view the powers press at the same time “MODE / ACK” and “F2” (this combination is
highlighted on the front panel of the board with the indication “MODE + F2”: POWER
DISPLAY”). In this conditions the “ L1/L2”, “L2/L3” “L3/L1” are all of them turned on and the
display “V” shows the power factor, while the display “A” shows the active power. Further, if
through the buttons “F1” and “F2” you choose the “MAINS VOLTAGE (Vac) / REACTIVE
POWER (kvar)” function, the display “MULTIFUNCTION” shows the reactive power, if you
choose the “BATTERY VOLTAGE (V) / APPARENT POWER (kVA)” function, it shows the
apparent power.
By pressing again the buttons “F2” and “MODE / ACK” at the same time, you’ll go back to the
indications of the generator and mains voltages and of the generator current.
The value indicated by the display “V” is the system’s total power factor. It cannot be viewed
for each single phase. It is displayed with two decimals.
The eventual negative sign associated to this quantity indicates the energy inversion status.
This status also refers to the whole system: if one of the phases was in energy inversion,
probably it wouldn’t be indicated since globally the system would still supply (NB: actually, it
never occurs: if there’s an energy inversion, it is present on all the phases).
Further, through the power factor some information on the type of load, inductive or
capacitive is given to the operator. This information is provided using the decimal point of the
least significant digit of the power factor: when is turned on the load is a capacitive one.
In the place of the power factor are displayed three dashes when its value makes no sense,
that is in the absence of any current (dead engine or frequency not in window). Furthermore,
if the total active power is too low (under 10% of the system’s maximum power), the power
factor is forced to one, since its measurement for low current value gets too imprecise.
The active power (the system’s total one) is displayed in kW on the display “A” (message
“ACTIVE POWER (kW) over the display. If less than 100 kW is displayed with a decimal, if
over 1000 kW is displayed in tens of kW, with the indicator “X10” turned on. It is always
displayed in module: its sign (that would provide the true information of energy inversion) is
associated to the power factor for display problems: if it was displayed associated to the
active power one resolution digit would be lost, while by displaying it associated to the power
factor it replaces the initial zero (actually the power factor is never 1.00 but always 0.xx). This
introduces only a small rounding of the power factor: if it was 1.00 in energy inversion,
instead of –1.00 it was displayed as – .99.
The reactive power (the system’s total one) is displayed in kvar on the display
“MULTIFUNCTION” if the “MAINS VOLTAGE (Vac) / REACTIVE POWER (kvar)” function is
selected. If under 100 kvar it is displayed with a decimal, if over 1000 kvar it is displayed in
tens of kvar, by turning on the decimal point of the less significant digit to indicate that the
value has to be multiplied by 10. It is displayed with its sign, replacing the most significant
digit.
The apparent power (the system’s total one) is displayed in kVA on the display
“MULTIFUNCTION”, if the function “BATTERY VOLTAGE (V) / APPARENT POWER (kVA)”
is selected. If less than 100 kVA it is displayed with a decimal, if over 1000 kVA it is displayed
in tens of kVA, by turning on the indicator “X10”. It is, by definition, always positive, therefore
there’s no problem for the display of its sign.
The energy meter managed by DST4600A counts the energy supplied by the generator set. It
has an internal resolution under 100 Wh but it is displayed in kWh. It is updated every
second. It is displayed alternatively to the powers by pressing “MODE / ACK” (this procedure
is indicated on the front panel of the board with the indication “POWER DISPLAY + MODE:
ACTIVE ENERGY”). It uses the displays as follows:
If the energy counter exceeds 8 digits (100 GWh), it is saturated to 99.999.999 but is
displayed with the decimal point of the less significant digit turned on, to indicate the
saturation condition.
The energy counter can be reset. The reset procedure is the following one:
By pressing the “F1” and “F2” select the “DATA – HOURS COUNT / START
COUNTER” function
Press at the same time “MODE / ACK” and “START” for 5 seconds. After 5
seconds the counters will be reset. The display does not indicate the reset in any
way; therefore the operator has to count the 5 seconds.
The procedure is similar to the other counter reset procedure. The only difference is in the
used pushbutton: “START” instead of “STOP”. Until the SW version 08.00.11 the energy
meter counter were cleared only together with the hour-counter and with the start-counter.
Be sure that all the TA share the same phase connected to ground and check for the correct
phase connection. Otherwise the power measures will be wrong and it’ll possible that the
board will issue a reverse power alarm.
As a rule, connect terminal 50, 52 and 54 to ground and check that all the TA has the same
phase connected to the ground. Then, if the measured power factor is negative, reverse all
the TA connection.
Moreover, be sure that TA connections meet the generator phases connection (i.e. TA1 must
measures L1 current etc.). Otherwise the power measurement will be wrong.
There is no problem about phase rotation direction. The board will recognize if it is clockwise
or counter clockwise and will automatically set-up for correct power measurement.
7. Auxiliary Functions
7.1 Automatic recovery from KR close failure
Starting from 08.00.24 version, it is possible to avoid black-out due to KR failure. In case of
such failure the user power line remains unsupplied if the grid is present. Using this function
is possible to guarantee power availability at user level.
• Connect to “INPUT C” (terminal 12) a signal from KR that will be close to GROUND when
KR is close.
• Enable F13 alarm (warning) setting a value greater than 0 for P75.
Working with this configuration, if the board doesn’t acknowledge KR closed, after P75 time,
issues a “F13” alarm.
If bit 5 of P61 is set, the board interrupts cooling down sequence or, if engine is not running,
starts the engine and make the Generator set supplying users.
At this point the board doesn’t connect the load to the mains (even if it’s acknowledged) until
operator performs an appropriate action:
• From software release 08.00.26 this operation consists in setting the MAN mode,
manually make the mains supplying users and then set the AUTO mode again.
After these operations, if the board doesn’t acknowledge KR closed, the alarm “F13” is
issued again and the procedure is repeated.
Starting from revision 08.00.38, this block may be masked if mains is not present, by using
bit 1 of parameter P79. This mask is useful in plants where the mains breaker is powered by
the mains itself. In this situation, when the mains become unavailable, the board immediately
acquires the breaker open status. The board needs a lot of seconds in order to start the
engine and to close the load on the genset, and so the condition of breaker open while the
command is for closure remains for a lot of time. This condition causes the alarm “F13” to be
raised. But if the alarm is masked when mains is not present, this false alarm is not raised.
You can set the board to control a fuel pump for the automatic filling of the tank. The function
can be used only if the fuel level analogue sensor exists. You have to set the two operating
threshold:
The function is enabled if the parameters P29, P30 and P48 are all different from 0 and P29
is lower than P30
With the board in AUTOMATIC mode you can force the generator set start using the
“REMOTE TEST” digital input (terminal 46). Until the input stays enabled, the generator set is
on (except for deactivations and/or blocks). If in this phase it occurs a mains failure, the
users are switched on the generator.
• “ENGINE RUNNING” (terminal 25): this output is enabled when the engine is running.
• “GENERAL ALARM” (terminal 26): this output is enabled if at least one alarm is present.
• “TRIP ALARM” (terminal 27): this output is enabled if at least a deactivation or a block is
present.
• “FUEL ALARM” (terminal 28): this output is enabled if at least one fuel failure is present:
- Emergency stop
- Belt break
• “SPEED ALARM” (terminal 30): this output is enabled if at least one fault relating to the
engine’s speed is present:
• “GENERATOR ALARM” (terminal 31): this output is enabled if at least one fault
regarding the generator is present:
• “OFF-PROG-MAN” (terminal 32): this output is enabled only if the key selector is on
AUTO or on TEST
• “OFF SELECTION” (terminal 33): this output is enabled only if the key selector is on
MAN, AUTO or TEST
From the software release 08.00.25 is it possible to order as option the second serial port of
DST4600A board. It is then possible to connect to this serial port one expansion board
provided with 32 digital outputs or 16 outputs and 16 inputs. The outputs can be used as
additional remote signals. See document EAAN0022, release 03 or successive.
By using parameters from P56 to P59, it is possible to configure the board for taking some
actions related to the active power of the system. These parameters configure two power
thresholds and the related filter time. Outside the zone defined by the thresholds (P56 and
P58), the board takes some actions. Till to the revision EB02200080036 it could only signal
the low power status. From the revision EB02200080037, it can alternatively signal the
maximum power status. This function is disabled in the following situations (whatever is the
action selected):
• P56 = 0
• P58 = 0
To select an action, you have to operate with the bit 7 of parameter P61. If not set, the board
will signal the low power status, if set the board will signal the maximum power status. This is
true from revision EB02200080037, for the previous revisions the only action was the low
power signaling.
The signal is performed by a digital output (“OUTPUT 1”, terminal 37). The next two
paragraphs describe the available actions in details.
It is possible to use this feature to stop/start one or more external generator connected in
parallel. To use this function the following condition shall be met:
• Input “INPUT A” (terminal 14) must be configured to acquire the KG actual status (bit 1
parameter P61=1).
• Parameters P56 and P58 must have values greater than 0 and P58 must be greater than
P56.
This function uses also the parameter P60, in addition to those described in the previous
paragraph.
Operational procedure:
1. Generator set not supplying: “OUTPUT 1” is not activated (floating, open circuit). On
“INPUT A” (KG status) activation (ground shorted) becomes step 2.
a) Supplied active power less than P56 threshold throughout P57 time:
“OUTPUT 1” is activated.
b) Supplied active power greater than P58 threshold throughout P59 time:
“OUTPUT 1” is deactivated.
c) If the supplied power value is in the range between P56 and P58 values,
“OUTPUT 1” status is not changed from the actual status.
NB: this function assumes that the loads are applied to the generators before the time
specified by parameter P60 is elapsed. If not, the board assumes to be in a low-load situation
and then can deactivate other generators. When the loads will be applied, in the best
situation the other generators will be restarted. In the worst situation this generator will be
stopped for over-current.
This function is used to have a visible and acoustic signal of the maximum power status. It
can be used also for automatically disconnect some of the less important loads from the
generator, in order to continue to work in the normal conditions.
If the active power is higher than P58 threshold consecutively for P59 time, the maximum
power status is set and so the “OUTPUT 1” output and the “F49” warning are activated.
If the active power is lower than P56 threshold consecutively for the P57 time, the maximum
power status is reset and so the “OUTPUT 1” output and the “F49” warning are deactivated
(the “F49” warning is still present on the DST4600A panel if not acknowledged).
If the active power is between the P56 and P58 thresholds, the maximum power status and
the “OUTPUT 1” output and the “F49” warning are not modified.
The “OUTPUT 1” output can be connected to a circuit breaker for automatically disconnect
the less important loads. If it is connected to a changeover circuit, the board automatically re-
connect the less important loads when the active power back into its nominal range.
Comparing the maximum power signal function to the low power signal function, there are
the following differences:
• The genset breaker status is not used (and so is not necessary to connect it).
• The “OUTPUT 1” output is controlled in the opposite way than in low load function: it
is activated if power is greater than P58, while in the low power function it is activated
if the power is lower then P56.
Starting from SW revision 08.00.24, it is possible to install in DST4600A boards a Real Time
Clock option (RTC). The option is equipped by a lithium battery that let the watch running
also without supply. The expected duration of the battery is quite 10 years.
RTC has a full time/date management set of function (hours, minutes, seconds, day, month,
year and day of the week).
• Automatic periodical test of generator set at preset time and days of the week.
• Time Lock of Generator set operation at preset time and days of the week.
If the option is installed and in OFF/RESET mode, pressing STOP pushbutton the RTC
display mode is entered.
This mode is outlined by the light on of the dot at the least significant digit of the displays.
Pressing again “F1” and “F2” the mode will revert to hour.
From SW release 08.00.35, the displays are blinking if the RTC date/time is not reliable (and
so is required that the operator set the correct date/time).
Once in RTC display mode (see previous paragraph), pressing “MODE/ACK” the RTC setting
mode is entered.
Display “F” will show one of the following messages, while display “A” will show the proper
value:
Using “F1” and “F2” pushbuttons it is possible to select the variable to change.
To change a value, work as in programming mode (press “MODE/ACK”, lamp L1/L2 will turn
off, L2/L1 will turn on, modify using “F1” and “F2” and then press again “MODE/ACK” to exit
change mode).
If you press “START” the modified value will be stored, pressing “STOP” the new values will
be discarded. In both cases the RTC setting mode is exited.
Remember to set the DAY OF WEEK value because it is required for a correct function of
some features of RTC option.
If your board is equipped by RTC option, it is possible to use two different modes to carry out
the periodical test: one based on the RTC value and the other based on elapsed time
(standard mode).
• Set P74, configuring the day of the week when carry out the test (see par. Errore.
L'origine riferimento non è stata trovata.)
If P74 is greater than zero (RTC periodical test enabled), the standard periodical test mode is
disabled even if P18 is greater than zero.
You can periodically test the operation of the generator set by programming two parameters
that allow activating the test sequence on the basis of elapsed time. In particular:
• The parameter P18 determines the cyclical starting period of the generator set.
• The parameter P19 determines the duration of the test operation of the generator set.
If during the programming you change the value P18 the period count will restart from zero in
the moment in which you’ll exit the PROGRAMMING procedure.
The automatic periodical test is disabled if at least one of the two parameters is equal to zero
or if RTC based periodical test is enabled.
If RTC option is not installed it is possible to use only Standard mode periodical test
procedure.
From 08.00.24 SW version and with RTC option installed it is possible to enable the function
of the Generator set on time and day bases.
This function let you prevent the start of the engine when emergency supply is not required;
otherwise you can use this function to start and stop the Generator set at needed time.
It is possible to configure only one set of enable time and one set of enable days.
If P70 is equal to P71 the Generator set will be enabled 24 hours at day but only during the
days enabled by P72.
When the system is in Time Lock, the display “V” and “A” together will show the message
“DISABL”.
The only difference between DST4600A and DST4600A/P is the default of the P65 (ALARM2
(terminal 02) filter time): for DST4600A/P is 180s instead of 1s.
8.1.2 KR management
Enabling the internal MAINS VOLTAGE sensor and connecting the GRID line to the R-S-T
input terminal, KR will be deactivated if the MAINS is OK, and otherwise it will be activated.
If the internal MAINS VOLT AGE sensor is disabled, KR will be always in deactivated status.
The “MAINS SIMULATION” input (terminal 24) will never interfere on KR status.
DST4600A/P boards will drive activated KG during test operation when the Generator set will
be ready to supply.
Boards with the new SW version use P66 and P67 values as delay time related to the
“MAINS SIMULATION” input status change.
DST4600A/P has default value of 2s for P66 and 30s for P67.
Starting from SW revision 08.00.39, the software is no more the same for the asynchronous
engine version of the board. The correspondent SW version is 29.07.39. This software is built
over the DST4600A/P software. This paragraph shows the differences between this new
software and the DST4600A/P one.
The board measures the generator frequency and voltages and shows them on the panel.
But it does not use them for any protection and for engine running/stopped detection.
In the standard version, this terminal acquires the low oil pressure alarm. In this version, it
acquires the engine running status, and so the low oil pressure alarm is disabled.
In the standard version, this terminal acquires the high water temperature alarm. In this
version, it acquires the “engine in threshold” status, and so the high water temperature alarm
is disabled.
Only for this version, the board can activate a block (“F40”) when the KG is closed and the
signal on terminal 10 becomes inactive, with a fixed filter delay of 0.5 seconds.
9. References
9.1 SMS Protocol for Boards DST4600A and REMOTE SIGNALS
Document: EAAS0015
Revision: 01 or later
Document: EAAS0006
Revision: 01 or later
Document: EAAS0016
Revision: 03 or later
Document: EAAS0022
Revision: 03 or later
The disclosure by any means of this document to third parties is not allowed.